EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22687-1

Operation manual

8

How to enter a menu

Digital built-in controller
Scroll through the main menu using the 

and

 h

 keys to move

the 

 mark in front of the menu of your choice. Push the 

q

 key

to enter the selected menu. 

Digital remote controller
Press the corresponding menu key indicated in "User interface",
paragraph 

"Digital remote controller (to be ordered separately)"

on page 7

Connection to the unit

For a remote controller a cable length of up to 1000 metres
(EWLD120~260) or 300 metres (EWLD340~540) between the digital
controller and the unit is allowed. This gives the opportunity to control
the unit from a considerable distance. Refer to "Cable for digital
controller" in the installation manual for cable specifications.

For units in a DICN configuration, the digital controllers of the units
can be installed remotely at a distance of up to 50 metres by using a
6-ray telephone cable with a maximum cable resistance of 0.1 

/m.

Working with the unit

This chapter deals with the everyday usage of the unit. Here, you will
find how to perform routine tasks, such as:

"Setting the language" on page 8,

"Switching the unit on" on page 8 and "Switching the unit off" on
page 8,

"Consulting actual operational information" on page 9,

"Adjusting the temperature setpoint" on page 9,

"Resetting the unit" on page 10.

Setting the language

If desired, the operating language can be changed to any of the
following languages: English, German, French, Spanish or Italian.

1

Enter the usersettings menu. Refer to chapter 

"How to enter a

menu" on page 8

2

Go to the appropriate screen of the usersettings menu using the

and

 h

 keys.

3

Press 

q

  to change the operating language until the desired

language is active. 

Switching the unit on

1

Press the 

J

 key on the controller.

Depending on the setting of the remote ON/OFF control
parameter (refer to the service manual), the following conditions
may occur.
When the remote ON/OFF control parameter is set to NO, the
LED inside the 

J

  key  lights up and an initialization cycle is

started. Once all the timers have reached zero, the unit starts
up.
When the remote ON/OFF control parameter is set to YES, the
following table applies:

2

If the water chiller does not start after a few minutes, refer to the
chapter 

"Troubleshooting" on page 17

.

Switching the unit off

If the remote on/off control parameter is set to No:

Press the 

o

 key on the controller.

The LED inside the 

o

 key goes out.

If the remote on/off control parameter is set to Yes:

Press the 

o

 key on the controller or switch the unit off using the

remote on/off switch.
The LED inside the 

o

 key goes out in the first case and starts

blinking in the second case.

Switching units ON/OFF in a DICN system

If the 

o

 key is pressed on a unit with status 

 

 or 

, all

other units with status 

 

 or 

 will be ON or OFF.

If the 

o

 key is pressed on a unit with status 

 

,

only this unit will be ON or OFF.

a

key, to enter the user password menu.

d

key, to enter the DICN menu, also referred to as network
menu (optional).

i

key, has no effect on EWLD units

NOTE

Temperature readout tolerance: ±1°C.

Legibility of the alphanumeric display may decrease in
direct sunlight.

 

 

 

 

 

 

   

 

 

Local key

Remote switch

Unit

o

 LED

ON

ON

ON

ON

ON

OFF

OFF

Flashing

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

In case of emergency, switch off the unit by pushing the
emergency stopbutton.

NOTE

Also consult 

"Defining the schedule timer" on page 13

and “Customization in the service menu” chapter “Set-
ting of the changeable inputs and outputs” in the instal-
lation manual.

NOTE

When a remote ON/OFF switch is configured, the
remote ON/OFF contact for all units with status

 

 or 

 of a DICN network is the contact

connected to the master unit.

For units with status 

 

, the remote

contact is the contact connected to this unit.

NOTE

If the user wants 1 unit to operate on his command
only, this unit is to be set to 

 

.

It is recommended not to select the master unit for this
purpose. Even if the status of the master is set to

 

, it will still be the contact

connected to the master which will switch ON/OFF the
other units in 

 

  or 

  mode. It would

therefore never be possible to only switch the master
unit OFF remotely.

Switching OFF the master unit only, should in this case
be done by the local ON/OFF key on the master unit.

Содержание EWLD120MBYNN

Страница 1: ...OPERATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Страница 2: ...d water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first tim...

Страница 3: ...0 Condensor refer to engeneering specifications as published by the supplier of your remote condenser Evaporator Type brased plate heatexchanger Qty x model 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250...

Страница 4: ...sor 14 Digital display controller 2 Evaporator 15 Emergency stop 3 Switchbox 16 Power supply intake 4 Compressor switchbox 17 Field wiring intake 5 Charge valve 18 Holes for lifting 6 Safety valve 19...

Страница 5: ...orator The main function of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water...

Страница 6: ...omes too high If this occurs shut down the unit and contact your local dealer High pressure switch Each circuit is protected by two high pressure switches S PH which measure the condenser pressure pre...

Страница 7: ...circuit 2 BEFORE OPERATION Checks before initial start up After the installation of the unit check the following before switching on the circuit breaker 1 Field wiring Make sure that the field wiring...

Страница 8: ...he switch boxes may only be opened by a licensed electrician for maintenance purposes 3 To prevent the evaporator from freezing and to avoid damage to the LCD displays of the digital controller never...

Страница 9: ...an initialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller do...

Страница 10: ...available if voltage and current transmitters are installed This readout menu provides information concerning the voltage and the compressor current 7 Press the h key to enter the next screen of the...

Страница 11: ...s provided by the different menus In the following chapter you will find how you can set up and configure the unit using the various menu functions All menus are directly accessible using the correspo...

Страница 12: ...ot a password is needed to enter the setpoints menu To enter the service menu only a qualified installer is allowed to access this menu 2 5 4 4 2 2 1 2 2 To check the actual value of the general softw...

Страница 13: ...ther or not the discharge thermal protector or the compressor thermal protector are activated for circuit 1 To check the status of the high pressure switch the reverse phase protector and the overcurr...

Страница 14: ...to a failure circuit 1 will start up instead In the automatic mode the number of hours indicated on the display is the maximum difference between the running hours of both circuits This value is impor...

Страница 15: ...en Defining free cooling The screen of the usersettings menu allows the user to control a 3 way water valve when the unit is in free cooling state To make this possible a changeable digital output has...

Страница 16: ...the water flow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump contr...

Страница 17: ...which contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the...

Страница 18: ...en a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circum stances safety devices may be bridged or changed to a value other th...

Страница 19: ...t the inlet of the condenser may not exceed 43 C RESET After finding the cause push the button on the high pressure switch housing and reset the controller Symptom 5 4 Reverse phase protector is activ...

Страница 20: ...pecifications of the water quality Water filters Make sure to clean the waterfilter in front of the evaporator water inlet once every 4 months Check the filter for any possible damage and make sure th...

Страница 21: ...t working The diagram and table below show the default value and the upper and lower limits of the floating setpoint parameters on the evaporator INLET CONTROL Default value Lower limit Upper limit St...

Страница 22: ...ttings of groups and work similar as following example settings for group 1 ANNEX IV Free cooling working Free cooling on ambient temperature Free cooling on difference between inlet water evaporator...

Страница 23: ...2 2 q h q q g h h h g h g h g h g h g h g h g g h g h g h g h g h g h g h g h g h g h g h g h h g g g 2 f 4 4 2 5 4 4 2 4 4 4 4 4 4 4 4 4 4 0 4 4 4 4 g h g h g h q h p 2 6 g h g h 0 7 g h 3 3 2 2 2 1...

Страница 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22687 1...

Отзывы: