EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22687-1

Operation manual

16

Tasks of the safeties menu

Listing activated safeties and checking the unit status

If the alarm buzzer is activated and the user presses the 

p

 key, the

controller automatically enters the safeties menu.

The controller will enter the 

 

 screen of the safeties

menu when a unit safety was the cause of shutdown.

The controller will enter the 

  

or

  

screen of the safeties menu when a safety of the circuit was
activated.

For a DICN system, the controller can also show: 

  %  

. This occurs when the wrong

number of slave units is defined (refer to 

"Defining the network

settings" on page 14

) or when a slave unit is missing (because

of bad connection or power supply failure).
Make sure to define the correct number of slave units and to
make correct connections.

When the unit is configured with a dual evaporator pump, the
controller will enter the 

   

  screen of the

safeties menu when a sefety on the pump was the cause of
shutdown.

1

Press the 

p

 key when the alarm buzzer is activated.

The appropriate safety screen with the basic information
appears. Press the 

q

 key to see the detailed information. These

screens provide information about the unit status at the moment
of shutdown (see 

"Safeties menu" on page 11

).

2

If more than one kind of safety is active (indicated by means of

W

X

 or 

C

), use the 

and

 h

 keys to consult them.

Tasks of the history menu

Checking the safety-info and the unit status after a reset

The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the circuit.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest shutdown.

To check the safety info and the unit status, proceed as follows:

1

Enter the 

 

. (Refer to the chapter 

"How to enter a

menu" on page 8

.)

The controller enters the last 

  screen which contains

basic information of the moment of this shutdown.

2

Press the 

and

 h

 keys to consult the other present 

screens.

3

Press the 

q

 key to see the detailed information.

Tasks of the info menu

Consulting additional unit information

1

Enter the 

  

through the main menu. (Refer to the

chapter 

"How to enter a menu" on page 8

).

The controller enters the 

 

  screen which

contains the following information: the time and date.

2

Press 

h

 to consult the first 

 

 screen. 

This screen contains information about the unit name and the
refrigerant used.

3

Press 

h

 to consult the next 

 

 screen.

This screen contains information about the controller's software
version.

4

Press 

h

 to consult the 

 

 screen.

This screen contains information about the PCB.

Tasks of the input/output menu

Checking the status of the inputs and outputs

The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.

The locked digital inputs are:

 

:  whether the emergency button has been

pressed.

 

: indicates the status of the flowswitch: activated or

de-activated.

   

:  indicates the actual status of

this safety.

   

: indicates the actual status

of this safety.

 

: indicates the actual status of this safety.

   

:  indicates the actual

status of this safety.

   

: indicates the actual

status of this safety.

The changeable digital inputs are:

%   !"

:  indicates the position of the “enable/

disable capacity limitation” switch

 

:  indicates the position of the remote dual

setpoint switch: setpoint 1 or setpoint 2.

%

: indicates the position of the remote on/off switch.

: indicates the position of the connected switch.

The locked relay outputs are:

 

: indicates whether circuit 1/2 is on/off.

 

:  indicates whether circuit 1/2 is in

starmode or not.

   

:  indicates whether circuit 1/2 is in

deltamode or not.

 *

: indicates if the 12% capacity valve of circuit 1/2 is

activated.

 

: indicates if the UP of the capacity control motor of

circuit 1/2 is activated.

 

:  indicates if the DWN of the capacity control

motor of circuit 1/2 is activated.

 

: indicates the FEEDBACK of the potentiometer

of circuit 1/2 (

).

 

: indicates if the fans of fanstep 1 for circuit 1/

2 are on or not.

 

: indicates if the fans of fanstep 2 for circuit 1/

2 are on or not.

  !

: indicates if the fans of fanstep 3 for circuit 1/

2 are on or not.

: indicates the status of this voltage free contact. It

is activated if the pump should be ON.

%  

: indicates the status of this voltage free contact. It

is activated if there is any alarm on the unit.

The changeable relay outputs are:

 

: indicates the status of the second evaporator

pump.

 

: indicates the status of the condenser pump.

$$*

: indicates when the unit is working at 100%.

 

:  indicates the status of the 3-way water valve

when the unit is in free cooling state.

 

:  indicates the closed status of the changeable

digital output.

NOTE

You can check the "found" slave units in the 2nd
screen of the network menu.

Содержание EWLD120MBYNN

Страница 1: ...OPERATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Страница 2: ...d water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first tim...

Страница 3: ...0 Condensor refer to engeneering specifications as published by the supplier of your remote condenser Evaporator Type brased plate heatexchanger Qty x model 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250...

Страница 4: ...sor 14 Digital display controller 2 Evaporator 15 Emergency stop 3 Switchbox 16 Power supply intake 4 Compressor switchbox 17 Field wiring intake 5 Charge valve 18 Holes for lifting 6 Safety valve 19...

Страница 5: ...orator The main function of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water...

Страница 6: ...omes too high If this occurs shut down the unit and contact your local dealer High pressure switch Each circuit is protected by two high pressure switches S PH which measure the condenser pressure pre...

Страница 7: ...circuit 2 BEFORE OPERATION Checks before initial start up After the installation of the unit check the following before switching on the circuit breaker 1 Field wiring Make sure that the field wiring...

Страница 8: ...he switch boxes may only be opened by a licensed electrician for maintenance purposes 3 To prevent the evaporator from freezing and to avoid damage to the LCD displays of the digital controller never...

Страница 9: ...an initialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller do...

Страница 10: ...available if voltage and current transmitters are installed This readout menu provides information concerning the voltage and the compressor current 7 Press the h key to enter the next screen of the...

Страница 11: ...s provided by the different menus In the following chapter you will find how you can set up and configure the unit using the various menu functions All menus are directly accessible using the correspo...

Страница 12: ...ot a password is needed to enter the setpoints menu To enter the service menu only a qualified installer is allowed to access this menu 2 5 4 4 2 2 1 2 2 To check the actual value of the general softw...

Страница 13: ...ther or not the discharge thermal protector or the compressor thermal protector are activated for circuit 1 To check the status of the high pressure switch the reverse phase protector and the overcurr...

Страница 14: ...to a failure circuit 1 will start up instead In the automatic mode the number of hours indicated on the display is the maximum difference between the running hours of both circuits This value is impor...

Страница 15: ...en Defining free cooling The screen of the usersettings menu allows the user to control a 3 way water valve when the unit is in free cooling state To make this possible a changeable digital output has...

Страница 16: ...the water flow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump contr...

Страница 17: ...which contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the...

Страница 18: ...en a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circum stances safety devices may be bridged or changed to a value other th...

Страница 19: ...t the inlet of the condenser may not exceed 43 C RESET After finding the cause push the button on the high pressure switch housing and reset the controller Symptom 5 4 Reverse phase protector is activ...

Страница 20: ...pecifications of the water quality Water filters Make sure to clean the waterfilter in front of the evaporator water inlet once every 4 months Check the filter for any possible damage and make sure th...

Страница 21: ...t working The diagram and table below show the default value and the upper and lower limits of the floating setpoint parameters on the evaporator INLET CONTROL Default value Lower limit Upper limit St...

Страница 22: ...ttings of groups and work similar as following example settings for group 1 ANNEX IV Free cooling working Free cooling on ambient temperature Free cooling on difference between inlet water evaporator...

Страница 23: ...2 2 q h q q g h h h g h g h g h g h g h g h g g h g h g h g h g h g h g h g h g h g h g h g h h g g g 2 f 4 4 2 5 4 4 2 4 4 4 4 4 4 4 4 4 4 0 4 4 4 4 g h g h g h q h p 2 6 g h g h 0 7 g h 3 3 2 2 2 1...

Страница 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22687 1...

Отзывы: