Operation manual

5

EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22687-1

Safety devices

The unit is equipped with three kinds of safety devices:

1

General safety devices

General safety devices shut down all circuits and stop the whole
unit. For this reason the unit has to be manually put on again
after a general safety occurred.

2

Circuit safety devices

Circuit safety devices shut down the circuit they protect. For this
reason the unit does not need to be manually put on again after
a circuit safety occurred.

3

Part safety devices

Part safety devices shut down the part they protect.

An overview of all safety devices is given below.

Overcurrent relay
The overcurrent relays (K*S) are located in the switchbox of the
unit and protect the compressor motors in case of overload,
phase failure or too low voltage. The relays are factory-set and
may not be adjusted. When activated, they must be reset
manually, followed by a reset of the controller.

Compressor thermal protectors
The compressor motors are equipped with thermal protectors
(Q*M). The protectors are activated when the compressor motor
temperature becomes too high.
When temperature returns to normal, the protectors reset
automatically, but the controller needs to be reset manually.

Flowswitch
The unit is protected by a flowswitch (S8L). 
When the water flow becomes lower than the minimum allowed
water flow, the flowswitch shuts down the unit. When the water
flow becomes normal, the controller still needs to be reset
manually.

Discharge thermal protectors
The unit is equipped with discharge thermal protectors (S*T).
The protectors are activated when the temperature of the
refrigerant leaving the compressor becomes too high. When the
temperature returns to normal the protector resets automatically
and the controller needs to be reset manually.

Freeze-up protection
The freeze-up protection  prevents the water in the evaporator
from freezing during operation. When the outlet water
temperature is too low, the controller shuts down the circuit.
When the outlet water temperature returns to normal, the unit
can start up again.
When freeze-up protection occurs several times in a certain
period, the freeze-up alarm will be activated and the unit will be
shut down. The cause of freezing up should be investigated and
after outlet water temperature has risen enough, the alarm
indicator on the controller needs to be reset manually.

Low pressure safety
When the suction pressure of a circuit is too low, the circuit
controller shuts down the circuit. When the pressure returns to
normal, the safety device can be reset on the controller.

Pressure relief safety valve
The safety valve is activated when the pressure in the refrigerant
circuit becomes too high. If this occurs, shut down the unit and
contact your local dealer.

High pressure switch
Each circuit is protected by two high pressure switches (S*PH)
which measure the condenser pressure (pressure at the outlet
of the compressor). They are installed in the compressor
housing of the circuit. When the pressure becomes too high, the
pressure switches are activated and the circuit stops. 
The switches are factory-set and may not be adjusted. When
activated, they must be reset by means of a screwdriver. The
controller still needs to be reset.

Reverse phase protector
The reverse phase protectors (R*P) prevent the screw
compressors from running in the wrong direction. If the
compressors do not start, two phases of the power supply must
be inverted.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:

A1,A2..........** ....... Current transfo / A-meter circuit 1, circuit 2

A1P........................ PCB controller

A2P,A3P................. PCB-EEV driver circuit 1, circuit 2

A11P...................... Expansion board controller 

(only for EWLD340~540)

B1P,B4P................. Low pressure transmitter circuit 1, circuit 2

B2P,B5P................. High pressure transmitter circuit 1, circuit 2

B3P,B6P................. Low pressure transmitter circuit 1 (A2P), circuit 2 

(A3P)

C11,C21 ................ Capacitor for capacity control 

(only for EWLD340~540)

E1HC,E2HC .......... Crankcase heater compressor circuit 1, circuit 2

F1U~F3U ....# ........ Main fuses

F11U~F13U ..# ........ Main fuses (only for EWLD340~540)

F21U~F23U ..# ........ Main fuses (only for EWLD340~540)

F1R,F2R ................ Fuses for reverse phase protector circuit 1, 

circuit 2

F6B ........................ Fuse for primary of TR1

F7B ........................ Fuse for secondary of TR1

F8B ........................ Fuse for EEV driver

F8U........................ Surge proof fuse for A1P

F9B ........................ Fuse for secondary of TR2

F10S,F11S ............ Circuit breakers with fuses for circuit 1, circuit 2 

(only for EWLD340~540)

F12B,F13B ............ Fuse for fan motors circuit 1, circuit 2

H1P.............*......... Indication lamp general operation

H2P.............*......... Indication lamp alarm

H3P.............*......... Indication lamp operation compressor 1

H4P.............*......... Indication lamp operation compressor 2 

(only for EWLD340~540)

H4P,H5P .....*......... Changeable input (only for EWLD120~260)

H5P,H6P .....*......... Changeable input (only for EWLD340~540)

J1........................... Power supply

J11,J23 .................. RS485 connection

J2,J3,J6,J20 .......... Analog input

J4........................... Analog output

J5,J7,J8,J19 .......... Digital input

J12~J18,J21,J22 ... Digital output

K1A,K4A ................ Auxiliary relay for safeties for circuit 1, circuit 2

K2A,K5A ................ Auxiliary relay compressor thermal protector for 

circuit 1, circuit 2

K3A,K6A ................ Auxiliary relay for discharge thermal protector for 

circuit 1, circuit 2

K7A,K8A ................ Auxiliary relay for safetty high pressure circuit 1, 

circuit 2

K7F~K9F ............... Fancontactor (only for EWLD120~260)

K7F,K10F ............... Fancontactor for circuit 1, circuit 2 

(only for EWLD340~540)

K8F,K11F ............... Fancontactor for circuit 1, circuit 2 

(only for EWLD340~540)

K9F,K12F ............... Fancontactor for circuit 1, circuit 2 

(only for EWLD340~540)

K1M,K4M............... Linecontactor for circuit 1, circuit 2

K2M,K5M............... Deltacontactor for circuit 1, circuit 2

K3M,K6M............... Starcontactor for circuit 1, circuit 2

K17S,K18S ............ Overcurrent relay for circuit 1, circuit 2

Содержание EWLD120MBYNN

Страница 1: ...OPERATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Страница 2: ...d water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first tim...

Страница 3: ...0 Condensor refer to engeneering specifications as published by the supplier of your remote condenser Evaporator Type brased plate heatexchanger Qty x model 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250...

Страница 4: ...sor 14 Digital display controller 2 Evaporator 15 Emergency stop 3 Switchbox 16 Power supply intake 4 Compressor switchbox 17 Field wiring intake 5 Charge valve 18 Holes for lifting 6 Safety valve 19...

Страница 5: ...orator The main function of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water...

Страница 6: ...omes too high If this occurs shut down the unit and contact your local dealer High pressure switch Each circuit is protected by two high pressure switches S PH which measure the condenser pressure pre...

Страница 7: ...circuit 2 BEFORE OPERATION Checks before initial start up After the installation of the unit check the following before switching on the circuit breaker 1 Field wiring Make sure that the field wiring...

Страница 8: ...he switch boxes may only be opened by a licensed electrician for maintenance purposes 3 To prevent the evaporator from freezing and to avoid damage to the LCD displays of the digital controller never...

Страница 9: ...an initialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller do...

Страница 10: ...available if voltage and current transmitters are installed This readout menu provides information concerning the voltage and the compressor current 7 Press the h key to enter the next screen of the...

Страница 11: ...s provided by the different menus In the following chapter you will find how you can set up and configure the unit using the various menu functions All menus are directly accessible using the correspo...

Страница 12: ...ot a password is needed to enter the setpoints menu To enter the service menu only a qualified installer is allowed to access this menu 2 5 4 4 2 2 1 2 2 To check the actual value of the general softw...

Страница 13: ...ther or not the discharge thermal protector or the compressor thermal protector are activated for circuit 1 To check the status of the high pressure switch the reverse phase protector and the overcurr...

Страница 14: ...to a failure circuit 1 will start up instead In the automatic mode the number of hours indicated on the display is the maximum difference between the running hours of both circuits This value is impor...

Страница 15: ...en Defining free cooling The screen of the usersettings menu allows the user to control a 3 way water valve when the unit is in free cooling state To make this possible a changeable digital output has...

Страница 16: ...the water flow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump contr...

Страница 17: ...which contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the...

Страница 18: ...en a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circum stances safety devices may be bridged or changed to a value other th...

Страница 19: ...t the inlet of the condenser may not exceed 43 C RESET After finding the cause push the button on the high pressure switch housing and reset the controller Symptom 5 4 Reverse phase protector is activ...

Страница 20: ...pecifications of the water quality Water filters Make sure to clean the waterfilter in front of the evaporator water inlet once every 4 months Check the filter for any possible damage and make sure th...

Страница 21: ...t working The diagram and table below show the default value and the upper and lower limits of the floating setpoint parameters on the evaporator INLET CONTROL Default value Lower limit Upper limit St...

Страница 22: ...ttings of groups and work similar as following example settings for group 1 ANNEX IV Free cooling working Free cooling on ambient temperature Free cooling on difference between inlet water evaporator...

Страница 23: ...2 2 q h q q g h h h g h g h g h g h g h g h g g h g h g h g h g h g h g h g h g h g h g h g h h g g g 2 f 4 4 2 5 4 4 2 4 4 4 4 4 4 4 4 4 4 0 4 4 4 4 g h g h g h q h p 2 6 g h g h 0 7 g h 3 3 2 2 2 1...

Страница 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22687 1...

Отзывы: