Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
126
3
1
4
5
4.12
“L4”
Radiation Fin Temperature Increased
Remote controller
display
L4
Method of
malfunction
detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
decision conditions
When the temperature of the inverter radiation fin increases abnormally due to faulty heat dissipation.
Supposed causes
Activation of fin thermal switch
Faulty fin thermistor
High outside air temperature
Insufficient cooling of inverter radiation fin
Blocked suction opening
Dirty radiation fin
Faulty outdoor inverter PCB