Error Codes: Outdoor Units
117
Part 4 – Troubleshooting
4
3
4
5
4
4.7
“F3”
Malfunctioning in Discharge Pipe Temperature
Remote controller
display
F3
Method of
malfunction
detection
Abnormality is detected according to the temperature detected by the discharge pipe temperature
sensor.
Malfunction
decision conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Supposed causes
Faulty discharge pipe thermistor
Faulty connection of discharge pipe thermistor
Insufficient refrigerant amount
Faulty compressor
Disconnection of discharge pipe thermistor