ESIE13-02
Error Codes: Outdoor Units
107
Part 4 – Troubleshooting
4
3
4
5
4
Troubleshooting
See also
"Check No.7 - Evaluation of Abnormal Low Pressure" on page 157.
"Check No.11 - Outdoor Unit: Check for Power Transistor" on page 160.
Replace the low pressure
sensor.
Measure the voltage
between the connector pins
(1) and (3) above.
(refer to *1)
Remove the thermistor from the
outdoor PC board and measure
resistance between the pins (5)
and (6).
Is the
relation
between low pressure
and voltage normal?
(refer to *2)
Is
the heat
exchanger distribution
pipe thermistor (connector :
X12A) properly connected
to the outdoor PC
board?
Is the
pressure sensor
(connector X17A)
properly connected to the
(A1p) PC board?
* Replace the outdoor PC board (A1P) ERHQ***V3* / ERLQ***V3*
* Replace the Control PC board (A1P) ERHQ***W1* / ERLQ***W1*
Correct the refrigerant system defect
NO
NO
YES
YES
NO
Connect the connector properly.
NO
NO
NO
YES
(In cooling operation)
Open the stop valve.
NO
YES
YES
Is the
stop valve open?
Is it in
cooling operation?
Is low
pressure
abnormally low?
Check 7
Replace the group thermistor.
Replace the low pressure
sensor.
Is it
normal?
Check 11
[* Replace the PC board equipped with resin case.]
Содержание ESIE13-02
Страница 16: ...Introduction ESIE13 02 16 3 1 4 5...
Страница 50: ...Outdoor Unit ESIE13 02 Part 2 Specifications 50 3 1 2 5...
Страница 51: ...ESIE13 02 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Страница 52: ...ESIE13 02 Part 3 Commissioning 52 3 1 3 5...
Страница 166: ...Tips and Tricks ESIE13 02 Part 5 Repair 166 3 1 5 5 1 Tips and Tricks Not available at this moment...