ESIE13-02
Error Codes: Outdoor Units
133
Part 4 – Troubleshooting
4
3
4
5
4
Troubleshooting
(*) See also "Check No.11 - Outdoor Unit: Check for Power Transistor" on page 160.
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the
difference between
high and low pressure
before startup not more
than 0.2MPa?
Turn the main power supply
off, and then disconnect the
connection between the
compressor and inverter.
Is the
inverter output
voltage generated
approximately at the same
increasing speed on each
phase after turning
on again? (* )
(U-V, V-W,
W-U)
Continuity check
in the power transistor
(IGBT) Is the continuity
normal? (*)
Is the stop valve open?
Check the
installation conditions.
NO
YES
NO
YES
NO
YES
* When operating compressor
with compressor output line
disconnected, the compressor
stops due to malfunction after
elapsed time of 5 seconds.
Therefore, check the voltage
increase for 5 seconds.
Open the stop valve.
Insufficient pressure equalization
Check refrigerant system.
* Replace the inverter PC board (A1P)
ERHQ***V3* / ERLQ***V3*
* Replace the inverter PC Board (A2P)
ERHQ***W1* / ERLQ***W1*
* Replace the inverter PC board (A1P)
ERHQ***V3* / ERLQ***V3*
* Replace the inverter PC Board (A2P)
ERHQ***W1* / ERLQ***W1*
NO
YES
Compressor inspection
Inspect according to the diagnosis
procedure for abnormal noises,
vibration, operating status, etc. of the
compressor.
Содержание ESIE13-02
Страница 16: ...Introduction ESIE13 02 16 3 1 4 5...
Страница 50: ...Outdoor Unit ESIE13 02 Part 2 Specifications 50 3 1 2 5...
Страница 51: ...ESIE13 02 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Страница 52: ...ESIE13 02 Part 3 Commissioning 52 3 1 3 5...
Страница 166: ...Tips and Tricks ESIE13 02 Part 5 Repair 166 3 1 5 5 1 Tips and Tricks Not available at this moment...