ESIE13-02
Error Codes: Outdoor Units
111
Part 4 – Troubleshooting
4
3
4
5
4
4.5
“E7”
Malfunction of Outdoor Unit Fan Motor
Remote controller
display
E7
Method of
malfunction
detection
Abnormality of fan motor system is detected according to the fan speed detected by hall IC when the
fan motor runs.
Malfunction
decision conditions
When the fan runs with speed less than a specified one for 15 seconds or more when the fan motor
running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Supposed causes
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty connector
Fan does not run due to foreign matters tangled
Malfunction of the outdoor (inverter) PC board
Blowout of fuse