Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
116
3
1
4
5
See also
"Check No.4 - Resistance Conversion Table (Ambient, Coil, Fin)" on page 153.
"Check No.5 - Resistance Conversion Table (Discharge Pipe Sensor)" on page 155.
"Check No.13 - Check for Inadequate Refrigerant" on page 161.
"Check No.14 - Check for Excessive Refrigerant Charging" on page 162.
"Check No.15 - Check for Factors Causing Wet Operation" on page 163.
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
YES
NO
Does the
malfunction code "E9"
recur?
Restart operation.
Actually, it is in wet operation.
Refer to
Check 13,14,15
to eliminate
the causes of wet operation.
It is believed that factors
(noise, etc.,) other than failure
caused the malfunction.
* Replace the outdoor PC board
(A1P) ERHQ***V3* / ERLQ***V3*
* Replace the control PC board
(A1P) ERHQ***W1* / ERLQ***W1*
A
–0.5
–0.5
0
0.5
1.0
2.0
3.0
3.5
1.5
2.5
0.5
1.5
2.5
3.5
0
1
2
3
Output voltage V (V
DC
)
P
P = 1.38V – 0.69
P : Detected pressure (MPa)
V : Output voltage
Detected pressure PH (MPa)
*3: For thermistor temperature and
resistance characteristics, see
Check 4,5
.
*4: For voltage characteristics of the
pressure sensor, see the right
figure.
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
(Gray) 5
(White) 6
Measurement spot
1 - 5
2 - 5
3 - 5
4 - 5
Criteria
40 ~ 50
Ω
40 ~ 50
Ω
40 ~ 50
Ω
40 ~ 50
Ω
*1: Electronic expansion valve and connector No.
→
X21A
*2: Electronic expansion valve connector and
coil resistance criteria
Содержание ESIE13-02
Страница 16: ...Introduction ESIE13 02 16 3 1 4 5...
Страница 50: ...Outdoor Unit ESIE13 02 Part 2 Specifications 50 3 1 2 5...
Страница 51: ...ESIE13 02 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Страница 52: ...ESIE13 02 Part 3 Commissioning 52 3 1 3 5...
Страница 166: ...Tips and Tricks ESIE13 02 Part 5 Repair 166 3 1 5 5 1 Tips and Tricks Not available at this moment...