9
|
Electrical installation
Installer reference guide
98
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
b
Round crimp-style terminal
▪
Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
c b
c
a
a
A
AA´
A´
a
Curled single-core wire
b
Screw
c
Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed
NOT allowed
Tightening torques
Outdoor unit:
Item
Tightening torque (N•m)
X1M
1.47 ±10%
X2M
M4 (earth)
Indoor unit:
Item
Tightening torque (N•m)
X1M
2.45 ±10%
X2M
0.88 ±10%
X5M
0.88 ±10%
X6M
2.45 ±10%
X10M
0.88 ±10%
M4 (earth)
1.47 ±10%
9.1.3 About electrical compliance
Only for EPRA08~12EAV3
Equipment complying with EN/IEC 61000‑3‑12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment
connected to public low-voltage systems with input current >16 A and ≤75 A per
phase.).