6
|
Application guidelines
Installer reference guide
46
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C‑07]
2 (
Room thermostat
): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Note:
▪
Main room = dedicated Human
Comfort Interface used as room
thermostat functionality
▪
Other rooms = external room
thermostat functionality
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7‑02]
1 (
Dual zone
): Main + additional
In case of heat pump convectors:
External room thermostat for the
additional
zone:
▪
#: [3.A]
▪
Code: [C‑06]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Bizone kit installed
:
▪
#: [9.P.1]
▪
Code: [E‑0B]
2 (
Yes
)
:
A bizone kit is installed in order
to add an additional temperature zone.
Bizone system type
:
▪
#: [9.P.2]
▪
Code: [E‑0C]
0 (
Without hydraulic
separator / no direct pump
)
1 (
With hydraulic separator /
no direct pump
)
2 (
With hydraulic separator /
with direct pump
)
(See 3 system variations described
above)
Shut-off valve output
Set to follow the thermo demand of the
main zone.
Shut-off valve
If the main zone must be shut off during
cooling mode to prevent condensation
on the floor, set it accordingly.
214] for more information on configuration of the bizone kit.
Benefits
▪
Comfort.
-
The smart room thermostat functionality can decrease or increase the desired
leaving water temperature based on the actual room temperature
(modulation).
-
The combination of the two heat emitter systems provides the excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of
the heat pump convectors.