Installation manual

1

EKHBRD011~Y1

Indoor unit for air to water heat pump system

4PW54465-1C

C

ONTENTS

Page

Introduction ..................................................................................... 1

General information .................................................................... 1
Scope of this manual .................................................................. 2
Model identification ..................................................................... 2
Typical application examples ...................................................... 2

Application 1....................................................................................... 2
Application 2....................................................................................... 3
Application 3....................................................................................... 3
Application 4....................................................................................... 4
Application 5....................................................................................... 5

Accessories ..................................................................................... 6

Accessories supplied with this unit ............................................. 6

Overview of the indoor unit............................................................ 6

Main components ....................................................................... 6
Switch box main components ..................................................... 7
Functional diagram ..................................................................... 7

Installation of the indoor unit......................................................... 8

Selecting an installation location................................................. 8
Dimensions and service space ................................................... 8
Inspecting and handling the unit ................................................. 8
Installing the indoor unit .............................................................. 8

Piping connection work................................................................ 10

Refrigerant piping work............................................................. 10
Water piping work ..................................................................... 11

Checking the water circuit ................................................................ 11
Checking the water volume and expansion vessel pre-pressure ..... 11
Setting the pre-pressure of the expansion vessel ............................ 12
Connecting the water circuit ............................................................. 12

Precautions when connecting field piping and
regarding insulation .................................................................. 13

Charging water .............................................................................. 13

Method for adding water ........................................................... 13

Electrical wiring work ................................................................... 13

Precautions on electrical wiring work........................................ 13
Internal wiring - Parts table ....................................................... 14
System overview of field wiring................................................. 14

Connection of the indoor unit power supply and
communication cable(s).................................................................... 15
Installation of the remote controller .................................................. 15
Connection to a benefit kWh rate power supply ............................... 16

Start-up and configuration ........................................................... 17

Pre-operation checks ................................................................ 17
Field settings............................................................................. 18

Procedure ......................................................................................... 18
Detailed description.......................................................................... 19
Simultaneous demand of space heating and
domestic water heating .................................................................... 24
Multiple set point control................................................................... 27
Field settings table............................................................................ 30

Final check and test run ............................................................... 32

Final check................................................................................ 32
Test run ..................................................................................... 32

Temperature read-out mode ............................................................. 32
Procedure for space heating ............................................................ 32
Procedure for domestic water heating.............................................. 32

Maintenance and service.............................................................. 33

Maintenance activities .............................................................. 33

Troubleshooting ............................................................................ 33

General guidelines .................................................................... 33
Opening the unit ....................................................................... 33
General symptoms.................................................................... 34
Error codes ............................................................................... 35

Unit specifications ........................................................................ 36

Technical specifications ............................................................ 36
Electrical specifications............................................................. 36

Annex ............................................................................................. 37

The English text is the original instruction. Other languages are
translations of the original instructions.

I

NTRODUCTION

General information

Thank you for purchasing this unit.

The unit is the indoor part of the air to water ERSQ or ERRQ heat
pump. The unit is designed for floor standing indoor installation and
used for heating applications. The unit can be combined with space
heating radiators (field supply) and with an EKHTS* domestic hot
water tank (option).

A remote controller with room thermostat functionality is standard
supplied with this unit to control your installation.

Domestic hot water tank (option)

An optional EKHTS* domestic hot water tank can be connected to
the indoor unit. The domestic hot water tank is available in two
different water capacities: 200 and 260 litre.

Refer to the domestic hot water tank installation manual for further
details.

Remote controller (option)

An optional secondary EKRUAHTA remote controller (with room
thermostat functionality) can be connected to the indoor unit.
Purpose is to provide the possibility to install the standard remote
controller near the unit (for service reasons), and install another
remote controller in another place (e.g. living room) to operate your
installation.

Refer to the 

"Installation of the remote controller" on page 15

  for

further details.

EKHBRD011AAV1

EKHBRD011AAY1

EKHBRD014AAV1

EKHBRD014AAY1

EKHBRD016AAV1

EKHBRD016AAY1

Indoor unit for air to water heat pump system

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL
BE CARRIED OUT BY A LICENSED TECHNICIAN.

BE SURE TO WEAR ADEQUATE PERSONEL PROTEC-
TION EQUIPMENT (PROTECTION GLOVES, SAFETY
GLASSES, ...) WHEN PERFORMING INSTALLATION,
MAINTENANCE OR SERVICE TO THE UNIT.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT
TEMPERATURES RANGING 5°C~30°C.

NOTE

An EKHBRD indoor unit can only be connected to an
ERSQ or ERRQ outdoor unit.

Содержание EKHBRD-AY1

Страница 1: ...INSTALLATION MANUAL EKHBRD011AAV1 EKHBRD014AAV1 EKHBRD016AAV1 EKHBRD011AAY1 EKHBRD014AAY1 EKHBRD016AAY1 Indoor unit for air to water heat pump system...

Страница 2: ...15 15 4 38 60 74 694 465 381 120 611 62 16 14 15 13 13 15 132 80 447 180 100 11 12 11 12 8 6 2 1 9 10 10 9 9 9 7 3 5 13 13 PS LV HV HV LV PS LV HV PS LV LV LV 1x 1x 1x 2x 1x 1x 1x 1x 1 2 3 4 6 2x 7 2x...

Страница 3: ...des 04 overeenkomstig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt...

Страница 4: ...ou for purchasing this unit The unit is the indoor part of the air to water ERSQ or ERRQ heat pump The unit is designed for floor standing indoor installation and used for heating applications The uni...

Страница 5: ...w are for illustration purposes only Application 1 Space heating and domestic hot water heating with a single remote controller installed in the living room The remote controller gives immediate feedb...

Страница 6: ...mer operation 1 Outdoor unit 10 Collector field supply 2 Indoor unit 11 Radiator field supply 3 Refrigerant heat exchanger 12 Electronic expansion valve 13 By pass valve field supply 4 Water heat exch...

Страница 7: ...er distribution is in this case the responsibility of the installer Pattern B The domestic hot water tank is installed in a separate circuit with a 3 way valve of the temperature reducing device s Thi...

Страница 8: ...rmostat C Auxiliary contact normal closed th Heating only room thermostat K1A Auxiliary relay for activation of EKHBRD unit field supply K2A Auxiliary relay for activation of boiler field supply NOTE...

Страница 9: ...from the water to prevent damage to the pump or blockage of the evaporator The water filter must be cleaned on a regular base See Maintenance activities on page 33 12 Expansion vessel 12 l 13 Manomete...

Страница 10: ...ry 20 Interface relay K1A 21 Wiring bridges 22 Fuse F1 only Y1 23 Fuse F2 only Y1 Functional diagram 8 18 12 20 13 2 3 1 19 5 10 14 11 17 16 15 21 6 9 7 15 15 8 18 12 20 13 2 3 1 19 10 7 14 11 17 16 2...

Страница 11: ...e carrier claims agent Bring the unit as close as possible to its final installation position in its original package in order to prevent damage during transport Unpack the indoor unit completely acco...

Страница 12: ...ter on page 13 Perform the electrical wiring work as described in the chapter Electrical wiring work on page 13 To make the casing completely sealed plug the knockout holes with putty or insulation ma...

Страница 13: ...instructions mentioned on the top plate of the unit In case of right connection only 2 pipes are required In case of left connection the 4 pipes are required Guidelines for flare connection Flares sh...

Страница 14: ...ains possible Take care that the components installed in the field piping can withstand the water pressure and temperature Always use materials which are compatible with the water used in the system a...

Страница 15: ...this must be done is explained in the chapter Opening the unit on page 33 Connecting the water circuit Water connections must be made The location of the water inlet connection and the water outlet c...

Страница 16: ...ations Be sure to install the required fuses as mentioned on the electrical wiring diagram The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the ins...

Страница 17: ...R2 A4P Resistance R1L Reactor R1L R3L Reactor R1H EKRTR Humidity sensor optional R1T EKRTW R Ambient sensor optional R2T EKHTS Domestic hot water tank thermistor optional R2T EKRTETS External sensor...

Страница 18: ...er supply switch S1S a 2 2 100 mA c 9 LV Multiple set point signal 1 a 2 2 100 mA c 10 LV Multiple set point signal 2 a 2 2 100 mA c 11 LV Heater kit signal a Refer to the installation manual of the h...

Страница 19: ...lectricity during certain periods of time The indoor unit is designed to receive an input signal by which the unit switches into forced off mode At that moment the unit compressors will not operate Po...

Страница 20: ...ck the switch box and the inside of the unit on loose connections or damaged electrical components 5 Installation Check that the unit is properly installed to avoid abnormal noises and vibrations when...

Страница 21: ...the Field settings table on page 30 In this list we provided for 2 columns to register the date and value of altered field settings at variance with the default value A detailed description of each fi...

Страница 22: ...emperature set points When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer Permission level 2 level 3 Operation ON OFF Operable Ope...

Страница 23: ...at the next scheduled ON function The last programmed command overrules the preceding programmed command and will remain active until the next programmed command occurs Example imagine the actual time...

Страница 24: ...temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 4 Disinfec...

Страница 25: ...ol on page 27 8 Option setup 8 00 Remote controller temperature control When using the remote control delivered with the unit 2 types of temperature control are possible Default 8 00 1 which means tha...

Страница 26: ...hot water to the domestic hot water tank if the reheat minimum value is reached The domestic water heating will continue until the reheat maximum temperature is reached In this way always a minimum of...

Страница 27: ...o 1 to enable the vacuum mode E 04 Pump only operation When commissioning and installing the unit it is very important to get all air out of the water circuit Through this field setting the pump can b...

Страница 28: ...tic hot water tank temperature D Leaving water thermo on request F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b 03 H D...

Страница 29: ...oom temperature thermo on request E Remote controller room temperature F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b...

Страница 30: ...estic hot water tank coil is open The heat pump will deliver water with a higher temperature which is needed for production of the domestic hot water At that time the lower temperature appliances have...

Страница 31: ...nt of course is higher than 70 C b 03 OFF ON OFF OFF OFF Space 1 65 C A 03 OFF ON OFF ON ON OFF Space 2 35 C A 04 OFF ON OFF ON OFF ON Resulting heat pump water OFF 70 C 65 C 65 C 35 C NOTE If the sys...

Страница 32: ...ng Thermo status Space 0 65 C Remote controller OFF ON OFF OFF OFF Space 1 45 C A 03 OFF ON OFF ON ON OFF Space 2 35 C A 04 OFF ON OFF OFF ON ON Resulting heat pump water OFF 65 C 45 C 45 C 35 C NOTE...

Страница 33: ...ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selec...

Страница 34: ...tatus weather dependent domestic water heating 1 ON 0 1 03 Set point storage temperature 70 45 75 1 C C Leaving water temperature limits 00 Set point leaving water maximum temperature 80 37 80 1 C 01...

Страница 35: ...ws when no action is performed the user interface will return to normal mode after 10 seconds or by pressing the z button once To test the space heating operation push the y button to start the test r...

Страница 36: ...ice was activated stop the unit and find out why the safety device was activated before resetting it Under no circumstances safety devices may be bridged or changed to a value other than the factory s...

Страница 37: ...on the manometer that there is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Make sure that the expansion vessel is not broken The water volume in the...

Страница 38: ...roller thermostat thermistor error Contact your local dealer E1 Compressor PCB error Contact your local dealer E3 High pressure error S1PH Check wiring connections on outdoor unit and indoor unit Make...

Страница 39: ...8 inch 15 9 5 8 inch 15 9 5 8 inch 15 9 5 8 inch 15 9 5 8 inch 15 9 5 8 inch Expansion vessel volume l 12 12 12 12 12 12 maximum working pressure MWP bar 4 4 4 4 4 4 Pump type DC motor DC motor DC mo...

Страница 40: ...t 7 02 1 and 7 03 1 or and 7 04 1 6 01 1 page 22 What type of appliance do you have No Blank display Push the b button n You selected permission level 3 on remote controller 0 00 3 page 19 You selecte...

Страница 41: ...tion function will operate depending on settings request w icon will start blinking with 0 5 second intervals Domestic hot water production will start immediately w icon will start blinking with 1 sec...