EKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW54465-1C
Installation manual
28
The configuration of pattern A is done by field settings:
1
Select the appropriate pattern: [7-02]=0
2
Turn on multiple set point 1: [7-03]=0
➞
[7-03]=1
Turn on multiple set point 2: [7-04]=0
➞
[7-04]=1
3
Enter the temperature multiple set point 1: [A-03] (see below)
Enter the temperature multiple set point 2: [A-04] (see below)
Configuration example:
Multiple set point control according to pattern B
The basic setup of multiple set point pattern B is the same as a
normal classic design, so again no domestic water heating and
space heating is possible simultaneously.
Multiple set point pattern B is focussed on space heating operation
and allows using multiple water set points in combination with the
remote controller or external room thermostat.
The configuration of pattern B allows space heating set points and
the domestic hot water set point.
The request signals for space heating can be implemented in 2
different ways (installer choice):
■
thermo ON/OFF signal (from external room thermostat)
■
status signal (active/not active) from the corresponding
temperature reducing device
Space 0, not using a temperature reducing device (
), always
needs to be linked with the highest water temperature set point and
can be controlled by the remote controller room thermostat function
or by the external room thermostat. Settings for space 0 can be made
on the remote controller (same as during normal operation
(1)
).
Indoor unit
DHW
Domestic hot water tank
Temperature reducing device
Space 1
Space 1
Space 2
Space 2
Set
point
Field
setting
Thermo status
Domestic
hot water
70°C
(a)
(a) The water temperature needed to reach this set point of course is higher
than 70°C.
[b-03]
OFF
ON
OFF
OFF
OFF
Space 1
65°C
[A-03]
OFF
ON/OFF
ON
ON
OFF
Space 2
35°C
[A-04]
OFF
ON/OFF
ON
OFF
ON
Resulting heat pump water
OFF
>70°C
65°C
65°C
35°C
NOTE
■
If the system is configured according to pattern A,
nor the remote controller room thermostat
function (default OFF if multiple set point is
selected) nor the external room thermostat (as
replacement of the remote controller room
thermostat function) may be used.
■
The remote controller water temperature value is
ignored when pattern A is active.
■
It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high
water temperatures towards floor heating loops,
etc.).
■
It is the installers responsibility to make sure the
water circuit is well balanced (e.g. when a
domestic hot water request occurs, there will be
sufficient flow towards other appliances as well,
etc.)
■
Daikin does not offer any temperature reducing
device (
). This system only provides the
possibility to use multiple set points.
■
It is advised to only use the automatic storage
functionality for domestic water heating when
applying pattern A (with a high set point
temperature).
TRD
Space 1
DHW
TRD
Space 2
TRD
Space 1
DHW
TRD
Space 2
Indoor unit
DHW
Domestic hot water tank
Temperature reducing device
Space 0
Space 0
Space 1
Space 1
Space 2
Space 2
A
Classic room thermostat control with remote controller room
thermostat function and external room thermostat
(1) When using the automatic weather dependent function for setting of space 0, you
have to make sure that the lowest possible temperature of the space 0 floating
set point (including the possible negative shift value) is higher than the
temperature set point of spaces 1 and 2.
This means that field setting [3-03] of space 0 needs to be higher than
temperature set point of spaces 1 and 2.
TRD
Space 1
DHW
TRD
Space 2
Space 0
TRD
Space 1
TRD
Space 2
M
DHW
Space 0
M
A
A