EKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW54465-1C
Installation manual
30
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
Remote control setup
00
User permission level
2
2~3
1
—
01
Room temperature compensation value
0
–5~5
0.5
°C
02
Not applicable. Do not change the default value.
1 (ON)
0/1
—
—
03
Status: space heating schedule timer mode
1 (ON)
0/1
—
—
1
Automatic storage timing for domestic water heating
00
Status: night time storage
1 (ON)
0/1
—
—
01
Night time storage start time
1:00
0:00~23:00
1:00
hour
02
Status: day time storage
0 (OFF)
0/1
—
—
03
Day time storage start time
15:00
0:00~23:00
1:00
hour
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
01
Setback operation start time
23:00
0:00~23:00
1:00
hour
02
Setback operation stop time
5:00
0:00~23:00
1:00
hour
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_Ti)
70
25~80
1
°C
03
Set point at high ambient temperature (Hi_Ti)
45
25~80
1
°C
4
Disinfection function
00
Status: disinfection operation
1 (ON)
0/1
—
—
01
Disinfection operation day selection
Fri
Mon~Sun
—
—
02
Disinfection operation start time
23:00
0:00~23:00
1:00
hour
5
Automatic setback and disinfection set point
00
Set point: disinfection operation temperature
70
60~75
5
°C
01
Disinfection operation time duration
10
5~60
5
min
02
Leaving water setback temperature
5
0~10
1
°C
03
Room setback temperature
18
17~23
1
°C
6
Option setup
00
Domestic hot water tank installed
0 (OFF)
0/1
—
—
01
Optional room thermostat installed
0 (OFF)
0/1
—
—
02
Not applicable. Do not change the default value.
0 (OFF)
0/1
—
—
03
Not applicable. Do not change the default value.
0 (OFF)
0/1
—
—
04
Benefit kWh power supply mode
0 0/2
1
—
7
Option setup
00
Optional bottom plate heater installed
0 (OFF)
0/1
—
—
01
Not applicable. Do not change the default value.
0 (OFF)
0/1
—
—
02
Multiple set point pattern
0 (A)
0/1
—
—
03
Multiple set point 1
0 (OFF)
0/1
—
—
04
Multiple set point 2
0 (OFF)
0/1
—
—
8
Option setup
00
Remote controller temperature control
1 (ON)
0/1
—
—
01
Status: automatic restart function
1 (ON)
0/1
—
—
02
Emergency mode
0 (OFF)
0/1
—
—
03
Status: low noise level
1
1~3
1
—
04
Status: freeze up prevention
0 0~2
1
—
Содержание EKHBRD-AY1
Страница 43: ...V1 Y1 NOTES 5 5...
Страница 44: ...4PW54465 1C Copyright Daikin...