background image

EKHBRD011~Y1

Indoor unit for air to water heat pump system

4PW54465-1C

Installation manual

8

I

NSTALLATION

 

OF

 

THE

 

INDOOR

 

UNIT

Selecting an installation location

The unit is to be placed in an indoor location that meets the following
requirements:

The installation location is frost-free.

The space around the unit is adequate for servicing. 

(See

figure 2)

.

The space around the unit allows for sufficient air circulation.

There is a provision for pressure relief valve blow-off.

There is no danger of fire due to leakage of inflammable gas.

The equipment is not intended for use in a potentially explosive
atmosphere.

All piping lengths and distances have been taken into
consideration.

Do not install the unit in places often used as workplace.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.

Do not install the unit in places with high humidity (e.g.
bathroom) (maximum humidity (RH)=85%).

If the sound is measured under actual installation conditions, the
measured value will be higher than the sound pressure level
mentioned in the 

"Unit specifications" on page 36

  due to

environmental noise and sound reflections. Choose the
installation location carefully and do not install in a sound
sensitive environment (e.g. living room, bedroom, ...).

Take care that in the event of a water leak, water can not cause
any damage to the installation space and surroundings.

The foundation must be strong enough to support the weight of
the unit (or unit and optional domestic hot water tank completely
filled with water in case the optional domestic hot water tank is
mounted on top of the unit).

The floor is flat to prevent vibrations and noise generation and to
have sufficient stability especially when the optional domestic
hot water tank is mounted on top of the unit.

Do not place any objects or equipment on top of the unit (top
plate).

Do not climb, sit or stand on top of the unit.

Be sure that sufficient precautions are taken, in accordance with
relevant local and national regulations, in case of refrigerant
leakage.

Dimensions and service space

Unit of measurement: mm

Dimensions of the unit, see 

figure 4

Required service space, see 

figure 2

Inspecting and handling the unit

At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent.

Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during
transport.

Unpack the indoor unit completely according to the instructions
mentioned on the unpacking instructions sheet.

Check if all indoor unit accessories (see 

"Accessories" on

page 6

) are enclosed.

Installing the indoor unit

For connecting piping and electrical cables, knockout holes are
provided at the back of the unit.

To punch a knockout hole, hit on it with a hammer.

When passing electrical wiring or piping through the
knockout holes, remove any burrs from the knockout holes.

NOTE

Make sure to provide for adequate measures in
order to prevent that the indoor unit should be
used as a shelter by small animals.

Small animals making contact with electrical parts
can cause malfunctions, smoke or fire. Please
instruct the customer to keep the area around the
unit clean.

Requirement 

Value

Maximum allowable refrigerant piping length between 
outdoor unit and indoor unit

50 m

Minimum required refrigerant piping length between 
outdoor unit and indoor unit

3 m

Maximum allowable height difference between 
outdoor unit and indoor unit

30 m

Maximum allowable distance between the domestic 
hot water tank and the indoor unit (only for 
installations with domestic hot water tank).

10 m

NOTE

If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water
tank installation manual.

1

Gas pipe connection

10

Water filter

2

Liquid pipe connection

11

Water inlet connection

3

Service port

12

Water outlet connection

4

Manometer

13

Electrical wiring knock out 
holes

5

Pressure relief valve

6

Flexible hose blow off 
valve

14

Refrigerant piping knock 
out holes

7

Drain valve water circuit

15

Water piping knock out 
holes

8

Air purge valve

9

Shut-off valve

16

Levelling feet

A

Space required for switch box removal

B

Left installation (top view)

C

Right installation (top view)

D

Space required for wiring (in case of right installation)

NOTE

For installation of the outdoor unit, refer to the
installation manual of the outdoor unit.

Knockout holes are foreseen at both sides of the
unit. Pay attention to knock out the correct holes
depending on your installation location.

Refrigerant piping and water piping must go
through different knockout holes.

The electrical wiring must always enter the unit
through the 2 upper knockout holes at the left
side of the unit (see 

figure 4

). 

Do NOT use the 2 lower knockout holes.

Содержание EKHBRD-AY1

Страница 1: ...INSTALLATION MANUAL EKHBRD011AAV1 EKHBRD014AAV1 EKHBRD016AAV1 EKHBRD011AAY1 EKHBRD014AAY1 EKHBRD016AAY1 Indoor unit for air to water heat pump system...

Страница 2: ...15 15 4 38 60 74 694 465 381 120 611 62 16 14 15 13 13 15 132 80 447 180 100 11 12 11 12 8 6 2 1 9 10 10 9 9 9 7 3 5 13 13 PS LV HV HV LV PS LV HV PS LV LV LV 1x 1x 1x 2x 1x 1x 1x 1x 1 2 3 4 6 2x 7 2x...

Страница 3: ...des 04 overeenkomstig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt...

Страница 4: ...ou for purchasing this unit The unit is the indoor part of the air to water ERSQ or ERRQ heat pump The unit is designed for floor standing indoor installation and used for heating applications The uni...

Страница 5: ...w are for illustration purposes only Application 1 Space heating and domestic hot water heating with a single remote controller installed in the living room The remote controller gives immediate feedb...

Страница 6: ...mer operation 1 Outdoor unit 10 Collector field supply 2 Indoor unit 11 Radiator field supply 3 Refrigerant heat exchanger 12 Electronic expansion valve 13 By pass valve field supply 4 Water heat exch...

Страница 7: ...er distribution is in this case the responsibility of the installer Pattern B The domestic hot water tank is installed in a separate circuit with a 3 way valve of the temperature reducing device s Thi...

Страница 8: ...rmostat C Auxiliary contact normal closed th Heating only room thermostat K1A Auxiliary relay for activation of EKHBRD unit field supply K2A Auxiliary relay for activation of boiler field supply NOTE...

Страница 9: ...from the water to prevent damage to the pump or blockage of the evaporator The water filter must be cleaned on a regular base See Maintenance activities on page 33 12 Expansion vessel 12 l 13 Manomete...

Страница 10: ...ry 20 Interface relay K1A 21 Wiring bridges 22 Fuse F1 only Y1 23 Fuse F2 only Y1 Functional diagram 8 18 12 20 13 2 3 1 19 5 10 14 11 17 16 15 21 6 9 7 15 15 8 18 12 20 13 2 3 1 19 10 7 14 11 17 16 2...

Страница 11: ...e carrier claims agent Bring the unit as close as possible to its final installation position in its original package in order to prevent damage during transport Unpack the indoor unit completely acco...

Страница 12: ...ter on page 13 Perform the electrical wiring work as described in the chapter Electrical wiring work on page 13 To make the casing completely sealed plug the knockout holes with putty or insulation ma...

Страница 13: ...instructions mentioned on the top plate of the unit In case of right connection only 2 pipes are required In case of left connection the 4 pipes are required Guidelines for flare connection Flares sh...

Страница 14: ...ains possible Take care that the components installed in the field piping can withstand the water pressure and temperature Always use materials which are compatible with the water used in the system a...

Страница 15: ...this must be done is explained in the chapter Opening the unit on page 33 Connecting the water circuit Water connections must be made The location of the water inlet connection and the water outlet c...

Страница 16: ...ations Be sure to install the required fuses as mentioned on the electrical wiring diagram The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the ins...

Страница 17: ...R2 A4P Resistance R1L Reactor R1L R3L Reactor R1H EKRTR Humidity sensor optional R1T EKRTW R Ambient sensor optional R2T EKHTS Domestic hot water tank thermistor optional R2T EKRTETS External sensor...

Страница 18: ...er supply switch S1S a 2 2 100 mA c 9 LV Multiple set point signal 1 a 2 2 100 mA c 10 LV Multiple set point signal 2 a 2 2 100 mA c 11 LV Heater kit signal a Refer to the installation manual of the h...

Страница 19: ...lectricity during certain periods of time The indoor unit is designed to receive an input signal by which the unit switches into forced off mode At that moment the unit compressors will not operate Po...

Страница 20: ...ck the switch box and the inside of the unit on loose connections or damaged electrical components 5 Installation Check that the unit is properly installed to avoid abnormal noises and vibrations when...

Страница 21: ...the Field settings table on page 30 In this list we provided for 2 columns to register the date and value of altered field settings at variance with the default value A detailed description of each fi...

Страница 22: ...emperature set points When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer Permission level 2 level 3 Operation ON OFF Operable Ope...

Страница 23: ...at the next scheduled ON function The last programmed command overrules the preceding programmed command and will remain active until the next programmed command occurs Example imagine the actual time...

Страница 24: ...temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 4 Disinfec...

Страница 25: ...ol on page 27 8 Option setup 8 00 Remote controller temperature control When using the remote control delivered with the unit 2 types of temperature control are possible Default 8 00 1 which means tha...

Страница 26: ...hot water to the domestic hot water tank if the reheat minimum value is reached The domestic water heating will continue until the reheat maximum temperature is reached In this way always a minimum of...

Страница 27: ...o 1 to enable the vacuum mode E 04 Pump only operation When commissioning and installing the unit it is very important to get all air out of the water circuit Through this field setting the pump can b...

Страница 28: ...tic hot water tank temperature D Leaving water thermo on request F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b 03 H D...

Страница 29: ...oom temperature thermo on request E Remote controller room temperature F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature maximum possible storage temperature b...

Страница 30: ...estic hot water tank coil is open The heat pump will deliver water with a higher temperature which is needed for production of the domestic hot water At that time the lower temperature appliances have...

Страница 31: ...nt of course is higher than 70 C b 03 OFF ON OFF OFF OFF Space 1 65 C A 03 OFF ON OFF ON ON OFF Space 2 35 C A 04 OFF ON OFF ON OFF ON Resulting heat pump water OFF 70 C 65 C 65 C 35 C NOTE If the sys...

Страница 32: ...ng Thermo status Space 0 65 C Remote controller OFF ON OFF OFF OFF Space 1 45 C A 03 OFF ON OFF ON ON OFF Space 2 35 C A 04 OFF ON OFF OFF ON ON Resulting heat pump water OFF 65 C 45 C 45 C 35 C NOTE...

Страница 33: ...ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selec...

Страница 34: ...tatus weather dependent domestic water heating 1 ON 0 1 03 Set point storage temperature 70 45 75 1 C C Leaving water temperature limits 00 Set point leaving water maximum temperature 80 37 80 1 C 01...

Страница 35: ...ws when no action is performed the user interface will return to normal mode after 10 seconds or by pressing the z button once To test the space heating operation push the y button to start the test r...

Страница 36: ...ice was activated stop the unit and find out why the safety device was activated before resetting it Under no circumstances safety devices may be bridged or changed to a value other than the factory s...

Страница 37: ...on the manometer that there is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Make sure that the expansion vessel is not broken The water volume in the...

Страница 38: ...roller thermostat thermistor error Contact your local dealer E1 Compressor PCB error Contact your local dealer E3 High pressure error S1PH Check wiring connections on outdoor unit and indoor unit Make...

Страница 39: ...8 inch 15 9 5 8 inch 15 9 5 8 inch 15 9 5 8 inch 15 9 5 8 inch 15 9 5 8 inch Expansion vessel volume l 12 12 12 12 12 12 maximum working pressure MWP bar 4 4 4 4 4 4 Pump type DC motor DC motor DC mo...

Страница 40: ...t 7 02 1 and 7 03 1 or and 7 04 1 6 01 1 page 22 What type of appliance do you have No Blank display Push the b button n You selected permission level 3 on remote controller 0 00 3 page 19 You selecte...

Страница 41: ...tion function will operate depending on settings request w icon will start blinking with 0 5 second intervals Domestic hot water production will start immediately w icon will start blinking with 1 sec...

Страница 42: ...nue in domestic hot water External room thermostat contol Yes Yes Yes 2 No Operation will switch to space heating Operation will switch to space heating Timer d 02 15 minutes passed sicne 2 No Space h...

Страница 43: ...V1 Y1 NOTES 5 5...

Страница 44: ...4PW54465 1C Copyright Daikin...

Отзывы: