5 Configuration
Installation manual
17
EHYHBH05AAV3* + EHYHBH/X08AAV3*
Daikin Altherma hybrid heat pump – heat pump module
4P349587-1F – 2016.10
INFORMATION
▪ The primary energy factor can always be set, but is
only used in case the savings mode is set to
Ecological.
▪ To set electricity price values, do NOT use overview
settings. Set them in the menu structure instead
([7.4.5.1], [7.4.5.2], and [7.4.5.3]). For more information
on how to set the energy prices, see the operation
manual and the user reference guide.
Space heating/cooling control
Leaving water temperature: Main zone
#
Code
Description
[A.3.1.1.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1
(Weather
dep.):
Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
(WD/scheduled):
Weather-
dependent + scheduled (only for
leaving water temperature control)
[7.7.1.1]
[1‑00]
[1‑01]
[1‑02]
[1‑03]
Weather-dependent curve (heating):
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
[7.7.1.2]
[1‑06]
[1‑07]
[1‑08]
[1‑09]
Only for EHYHBX08. Weather-
dependent curve (cooling):
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
INFORMATION
In order to optimise comfort as well as running costs, it is
recommended to choose weather-dependent setpoint
operation. Set the settings carefully; they have significant
influence on heat pump as well as boiler operation. Too
high leaving water temperature can result in constant boiler
operation.
Leaving water temperature: Additional zone
#
Code
Description
[A.3.1.2.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1
(Weather
dep.):
Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
(WD/scheduled):
Weather-
dependent + scheduled (only for
leaving water temperature control)
[7.7.2.1]
[0‑00]
[0‑01]
[0‑02]
[0‑03]
Weather-dependent curve (heating):
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
[7.7.2.2]
[0‑04]
[0‑05]
[0‑06]
[0‑07]
Only for EHYHBX08. Weather-
dependent curve (cooling):
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
Pump control: Flow target
#
Code
Description
N/A
[8‑0B]
Target flow rate during heat pump
operation.
N/A
[8‑0C]
Target flow rate during hybrid
operation.
N/A
[8‑0D]
Target flow rate during boiler operation.
INFORMATION
Changing these settings can result in discomfort. Refer to
the installer reference guide for more information.