4 Installation

Installation manual

5

EHYHBH05AAV3* + EHYHBH/X08AAV3*
Daikin Altherma hybrid heat pump – heat pump module
4P349587-1F – 2016.10

3.2.1

To check the water volume and flow rate

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum
13.5 litre, the internal water volume of the indoor unit NOT included.

INFORMATION

In  critical  processes,  or  in  rooms  with  a  high  heat  load,
extra water might be required.

NOTICE

When  circulation  in  each  space  heating  loop  is  controlled
by  remotely  controlled  valves,  it  is  important  that  the
minimum  water  volume  is  guaranteed,  even  if  all  of  the
valves are closed.

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum
13.5 litre, the internal water volume of the indoor unit NOT included.

INFORMATION

In  critical  processes,  or  in  rooms  with  a  high  heat  load,
extra water might be required.

NOTICE

When  circulation  in  each  space  heating  loop  is  controlled
by  remotely  controlled  valves,  it  is  important  that  the
minimum  water  volume  is  guaranteed,  even  if  all  of  the
valves are closed.

Minimum flow rate

Check  that  the  minimum  flow  rate  (required  during  defrost/backup
heater operation) in the installation is guaranteed in all conditions.

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating/operation).

See the installer reference guide for more information.

Minimum required flow rate

05 models

7 l/min

08 models

8 l/min

See  the  recommended  procedure  as  described  in 

"6.2  Checklist

during commissioning" on page 20

.

3.3

Preparing electrical wiring

3.3.1

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Outdoor unit and indoor unit power supply

1

Power supply for
outdoor unit

2+GND

(a)

2

Power supply and
interconnection cable to
indoor unit

3+GND

(g)

3

Power supply gas
boiler

2+GND

(c)

Item

Description

Wires

Maximum

running

current

4

Preferential kWh rate
power supply (voltage
free contact)

2

(e)

5

Normal kWh rate power
supply

2

6.3 A

User interface

6

User interface

2

(f)

Optional equipment

7

3‑way valve

3

100 mA

(b)

8

Domestic hot water
tank thermistor

2

(d)

9

Power supply for drain
pan heater

2

(b)

10

Room thermostat/heat
pump convector

3 or 4

100 mA

(b)

11

Outdoor ambient
temperature sensor

2

(b)

12

Indoor ambient
temperature sensor

2

(b)

Field supplied components

13

Shut-off valve

2

100 mA

(b)

14

Electricity meter

2

(b)

15

Domestic hot water
pump

2

(b)

16

Alarm output

2

(b)

17

Changeover to external
heat source control

2

(b)

18

Space cool/heat
operation control

2

(b)

19

Power consumption
digital inputs

2 (per input
signal)

(b)

20

Gas meter

2

(b)

21

Safety thermostat

2

(e)

(a)

Refer to name plate on outdoor unit.

(b)

Minimum cable section 0.75 mm².

(c)

Use the cable supplied with the boiler.

(d)

The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.

(e)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

(f)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
user interface connection.

(g)

Cable section 1.5 mm

2

; maximum length: 50 m.

NOTICE

More  technical  specifications  of  the  different  connections
are indicated on the inside of the indoor unit.

4

Installation

4.1

Opening the units

4.1.1

To open the switch box cover of the
indoor unit

1

Remove the side panel at the right side of the indoor unit. The
side panel is fixed at the bottom with 1 screw.

Содержание EHYHBH05AA

Страница 1: ...Installation manual Daikin Altherma hybrid heat pump heat pump module English Installation manual Daikin Altherma hybrid heat pump heat pump module EHYHBH05AA EHYHBH08AA EHYHBX08AA ...

Страница 2: ...jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następującyc...

Страница 3: ...1 Indoor unit 12 5 1 1 Overview Configuration 12 5 1 2 Basic configuration 15 5 1 3 Menu structure Overview installer settings 19 6 Commissioning 20 6 1 Checklist before commissioning 20 6 2 Checklist during commissioning 20 6 2 1 To check the minimum flow rate 20 6 2 2 To perform an air purge 21 6 2 3 To perform a test run 21 6 2 4 To perform an actuator test run 21 6 2 5 To perform an underfloor...

Страница 4: ...e located in the upper part of the box The connection pieces for the gas boiler are attached to the water piping 1 Remove the accessories as described in 2 1 1 To unpack the indoor unit on page 4 a b c d e f g a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Quick installation guide f Connection pieces for gas boiler g Boile...

Страница 5: ...3 Preparing electrical wiring 3 3 1 Overview of electrical connections for external and internal actuators Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 GND g 3 Power supply gas boiler 2 GND c Item Description Wires Maximum running current 4 Preferential kWh ...

Страница 6: ... and lower screw on the side panel of the switch box 7 Remove the switch box from the unit 8 Hook the switch box to the side of the unit with the hooks foreseen on the switch box 6 6 7 8 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Put the installation pattern see box on the wall and follow the steps as shown below 2 1 3 2 Fix the wall bracket to the wall with 2 M8 bolts 2 3 Lif...

Страница 7: ...s Shut off valves are field supplied They allow service to the unit without draining the whole system Foresee a drain fill point to drain or fill the space heating circuit NOTICE Do NOT install valves to shut down the entire emitter system radiators floor heating loops fan coil units instantly if this can result in an immediate short circuit of the water flow between the outlet and the inlet of th...

Страница 8: ...f the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation When the drain pan is installed make sure to insulate the water piping up to the drain pan to avoid condensation In case of EHYHBX 0 0 mm a a Drain pan kit 4 5 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables 4 5 1 To c...

Страница 9: ...3 1 2 3 a Legend see illustration below In case of preferential kWh rate power supply 30 31 S1S X2M X1M 1 3 4 2 3 X5M L N L N c 1 2 3 1 2 3 b a a Interconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cable with cable ties to the cable tie mountings INFORMATION If the system is connected to a preferential kWh rate power supply a separat...

Страница 10: ...rdered separately mandatory option 4A From the rear b a PCB 1 4B From the left a PCB b 1 4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 5 4 To connect the shut off valve 1 Connect the valve control cable to the appropriate termi...

Страница 11: ...llustration below 35 34 X2M X1M X5M 1 M M2P 2 Fix the cable with cable ties to the cable tie mountings 4 5 8 To connect the alarm output 1 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 28 Y1 X2M X1M A4P A8P X5M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 5 9 To connect the space cooling heatin...

Страница 12: ... 5 Configuration 5 1 Indoor unit 5 1 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed NOTICE The explanation about the configuration in this chapter gives you ONLY basic explanations For more detailed explanation and background information see the installer reference guide Why If you do NOT configure the system correctly it ...

Страница 13: ...ser permission level to End user 1 Press for more than 4 seconds Result The user permission level switches to End user The user interface will return to the default home screen To modify an overview setting Example Modify 1 01 from 15 to 20 1 Go to A 8 Installer settings Overview settings 2 Go to the corresponding screen of the first part of the setting by using the and button INFORMATION An addit...

Страница 14: ...utes It is recommended to change installer settings or the configuration of the unit on the main user interface If not it can take up to 5 minutes before these changes are visible in the menu structure 8 Your system is now set to be operated by the 2 user interfaces To copy the language set from the first to the second user interface See To copy the system settings from the first to the second use...

Страница 15: ...e A 2 2 2 E 06 Domestic hot water production 0 Type 1 by boiler 1 Type 2 by tank Note For Switzerland setting MUST be 1 A 2 2 3 E 07 Domestic hot water tank 4 Type 5 EKHWP 6 Type 7 Third party tank Range 0 6 Code Description A 2 2 A D 02 Domestic hot water pump not applicable for Switzerland In case of E 06 0 0 No default NOT installed 1 Secondary rtrn Installed for instant hot water In case of E ...

Страница 16: ...tional demand PCB is installed 0 No 1 Pwr consmp ctrl Energy metering Code Description A 2 2 8 D 08 Optional external kWh meter 1 0 No NOT installed 1 Installed 0 1 pulse kWh 2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pulse kWh 5 Installed 1000 pulse kWh A 2 2 C D 0A Optional gas meter 0 No NOT installed 1 Installed 1 pulse m 2 Installed 10 pulse m 3 Installed 100 pulse m Sav...

Страница 17: ...r temperature main Ta Outdoor temperature INFORMATION In order to optimise comfort as well as running costs it is recommended to choose weather dependent setpoint operation Set the settings carefully they have significant influence on heat pump as well as boiler operation Too high leaving water temperature can result in constant boiler operation Leaving water temperature Additional zone Code Descr...

Страница 18: ...1 7 9 0B Emitter type Reaction time of the system 0 Quick Example Small water volume and fan coils 1 Slow Example Large water volume floor heating loops Depending on the system water volume and the heat emitters type the heat up or cool down of a space can take longer This setting can compensate for a slow or a quick heating cooling system by adjusting the unit capacity during the heat up cool dow...

Страница 19: ...t type Compressor type Indoor software type Forced off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW operation DHW tank DHW tank type Contact type add Digital I O PCB Demand PCB External kWh meter DHW pump External sensor Leaving water Main Additional Room thermostat Room temp range Room temp offset Ext room sensor off...

Страница 20: ... connection between the gas boiler and the indoor unit The shut off valves are properly installed and fully open field supply The stop valves gas and liquid on the outdoor unit are fully open The air purge valve is open at least 2 turns The pressure relief valve purges water when opened The gas boiler is switched ON Setting is correctly set on the gas boiler 0 for EHYHBH05 EHYHBH08 1 for EHYHBX08 ...

Страница 21: ...e leaving water temperature control and the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually press select OK and press Possible actuator test runs Pump test INF...

Страница 22: ...find the complete documentation on the url as earlier described in this manual Explain the user how to properly operate the system and what to do in case of problems Show the user what to do in relation to maintaining the unit Explain the user about energy saving tips as described in the operation manual 8 Technical data A subset of the latest technical data is available on the regional Daikin web...

Страница 23: ...ain leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump c...

Страница 24: ...s Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical and gas meter Electrical and gas meter English Translation Ext thermistor option External thermistor option For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V D...

Страница 25: ... add X2M 1a 2a 4 main X2M 1 2 4 Only for KRP1AHTA communication 2 core communication 2 core Power limitation demand input 4 Power limitation demand input 3 Power limitation demand input 2 Power limitation demand input 1 X2 2 4 earth unit power supply 230 V earth Gas boiler 3 core Gas boiler part Heat pump part 4 core In case user interface is relocated In case of signal cable keep minimum distance...

Страница 26: ......

Страница 27: ......

Страница 28: ...4P349587 1F 2016 10 Copyright 2013 Daikin ...

Отзывы: