Application guidelines

Installer reference guide

40

EBLA04~E23V3 + EDLA04~E23V3

Daikin Altherma 3 M

4P685228-1A – 2022.05

Benefits

Comfort.

-

The smart room thermostat functionality can decrease or increase the desired
leaving  water  temperature  based  on  the  actual  room  temperature
(modulation).

-

The  combination  of  the  two  heat  emitter  systems  provides  the  excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of
the heat pump convectors.

Efficiency.

-

Depending  on  the  demand,  the  outdoor  unit  supplies  different  leaving  water
temperature matching the design temperature of the different heat emitters.

-

Underfloor heating has the best performance with the heat pump system.

6.3 Setting up an auxiliary heat source for space heating

INFORMATION

Bivalent is only possible in case of 1 leaving water temperature zone with:

room thermostat control, OR

external room thermostat control.

Space heating can be done by:

-

The outdoor unit

-

An auxiliary boiler (field supply) connected to the system

When  there  is  a  heating  request,  the  outdoor  unit  or  the  auxiliary  boiler  starts
operating  depending  on  the  outdoor  temperature  (status  of  the  changeover  to
external  heat  source).  When  the  permission  is  given  to  the  auxiliary  boiler,  the
space heating by the outdoor unit is turned OFF.

Bivalent operation is only possible if

-

Space heating is turned ON, and

-

DHW tank operation is turned OFF.

Domestic  hot  water  is  always  produced  by  the  DHW  tank  connected  to  the
outdoor unit.

INFORMATION

During heating operation of the heat pump, the heat pump operates to achieve
the  desired  temperature  set  via  the  user  interface.  When  weather-dependent
operation  is  active,  the  water  temperature  is  determined  automatically
depending on the outdoor temperature.

During  heating  operation  of  the  auxiliary  boiler,  the  auxiliary  boiler  operates  to
achieve the desired water temperature set via the auxiliary boiler controller.

Setup

Integrate the auxiliary boiler as follows:

Содержание EBLA04E2V3

Страница 1: ...er reference guide Daikin Altherma 3 M EBLA04E2V3 EBLA06E2V3 EBLA08E2V3 EBLA04E23V3 EBLA06E23V3 EBLA08E23V3 EDLA04E2V3 EDLA06E2V3 EDLA08E2V3 EDLA04E23V3 EDLA06E23V3 EDLA08E23V3 https daikintechnicaldatahub eu ...

Страница 2: ... Setting up the domestic hot water tank 43 6 4 1 System layout Standalone DHW tank 43 6 4 2 Selecting the volume and desired temperature for the DHW tank 43 6 4 3 Setup and configuration DHW tank 45 6 4 4 DHW pump for instant hot water 45 6 4 5 DHW pump for disinfection 46 6 4 6 DHW pump for tank preheating 47 6 5 Setting up the energy metering 48 6 5 1 Produced heat 48 6 5 2 Consumed energy 48 6 ...

Страница 3: ...upply 99 9 2 4 External backup heater kit 100 9 2 5 To connect the user interface 107 9 2 6 To connect the shut off valve 110 9 2 7 To connect the electricity meters 111 9 2 8 To connect the domestic hot water pump 112 9 2 9 To connect the alarm output 112 9 2 10 To connect the space cooling heating ON OFF output 113 9 2 11 To connect the changeover to external heat source 114 9 2 12 To connect th...

Страница 4: ...ng 238 15 1 Overview Troubleshooting 238 15 2 Precautions when troubleshooting 238 15 3 Solving problems based on symptoms 239 15 3 1 Symptom The unit is NOT heating or cooling as expected 239 15 3 2 Symptom Hot water does NOT reach the desired temperature 239 15 3 3 Symptom The compressor does NOT start space heating or domestic water heating 240 15 3 4 Symptom The system is making gurgling noise...

Страница 5: ...ion good practices reference data Format Digital files on https www daikin eu Use the search function to find your model Addendum book for optional equipment Additional info about how to install optional equipment Format Paper in the box of the outdoor unit Digital files on https www daikin eu Use the search function to find your model Latest revisions of the supplied documentation may be availabl...

Страница 6: ...OS and Android devices using the QR codes below Registration to the Stand By Me platform is required to access the app App Store Google Play 1 1 Meaning of warnings and symbols DANGER Indicates a situation that results in death or serious injury DANGER RISK OF ELECTROCUTION Indicates a situation that could result in electrocution DANGER RISK OF BURNING SCALDING Indicates a situation that could res...

Страница 7: ...e 1 3 Table title means Table 3 in chapter 1 1 2 Installer reference guide at a glance Chapter Description About the documentation What documentation exists for the installer General safety precautions Safety instructions that you must read before installing Specific installer safety instructions About the box How to handle the box unpack the units and remove their accessories About the units and ...

Страница 8: ...o and know to commission the system after it is configured Hand over to the user What to give and explain to the user Maintenance and service How to maintain and service the units Troubleshooting What to do in case of problems Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms Field settings table Table to be filled in by the installer an...

Страница 9: ...erant WARNING Improper installation or attachment of equipment or accessories could result in electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optional equipment and spare parts made or approved by Daikin WARNING Make sure installation testing and applied materials comply with applicable legislation on top of the instructions described in the Daikin d...

Страница 10: ...n of the unit Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmospheres In places where there is machinery that emits electromagnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment In places where there is a risk of fi...

Страница 11: ...o NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been connected make sure there is no gas leak Use nitrogen to perform a gas leak detection NOTICE To avoid compressor breakdown do NOT charge more than the specified amount of refrigerant When the refrigerant system is to be opened refrigerant MUST be treated according to...

Страница 12: ...lation manual or installer reference guide of your application for more information NOTICE Make sure water quality complies with EU directive 2020 2184 2 1 5 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical parts Disconnect the power supply for more than 10 minutes and measure the voltage at t...

Страница 13: ...of the earth leakage protector CAUTION When connecting the power supply connect the earth cable first before making the current carrying connections When disconnecting the power supply disconnect the current carrying cables first before separating the earth connection The length of the conductors between the power supply stress relief and the terminal block itself MUST be as such that the current ...

Страница 14: ...nts box is connected securely Make sure all covers are closed before starting up the unit NOTICE ONLY applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of reversed phase after a momentary black out and the power goes ON and OFF while the product is operating attach a reversed phase protection circuit locally Running the p...

Страница 15: ...ant does NOT contain an odour WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater WARNING Make sure installation servicing maintenance and repair comply with instructions from Daikin and with applicable legislation and are...

Страница 16: ...plug the system galvanized pipes are NOT used in glycol systems since the presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor Electrical installation see 9 Electrical installation 486 DANGER RISK OF ELECTROCUTION WARNING Electrical wiring connection method MUST be in accordance with the instructions from This manual See 9 Electrical installation 486 The...

Страница 17: ...eference guide 17 EBLA04 08E2V3 E23V3 EDLA04 08E2V3 E23V3 Daikin Altherma 3 M 4P685228 1A 2022 05 Commissioning see 12 Commissioning 4224 WARNING Commissioning method MUST be in accordance with the instructions from this manual See 12 Commissioning 4224 ...

Страница 18: ... as close as possible to its final installation position to prevent damage during transport Prepare in advance the path along which you want to bring the unit to its final installation position In this chapter 4 1 Outdoor unit 18 4 1 1 To unpack the outdoor unit 18 4 1 2 To remove the accessories from the outdoor unit 18 4 1 Outdoor unit 4 1 1 To unpack the outdoor unit 1 Cut straps and remove the...

Страница 19: ...rs b General safety precautions c Operation manual d Installation manual e Addendum book for optional equipment f Energy label g WLAN cartridge h User interface front plate rear plate screws and wall plugs i Unit mounting plate j Vibration dampers k Cable tie l Bolts nuts washers and spring washers 2 After opening the unit see 7 3 2 To open the outdoor unit 468 remove the accessory inside the unit...

Страница 20: ...oor unit 21 5 2 2 Possible combinations of outdoor unit and domestic hot water tank 25 5 1 Identification 5 1 1 Identification label Outdoor unit Location Model identification Example E B L A 06 E2 3 V3 Code Explanation E Monobloc outdoor heat pump B B Reversible heating cooling D Heating only L Low water temperature ambient zone 2 see operation range A Refrigerant R32 06 Capacity class E2 Model s...

Страница 21: ...ment Remote sensor for wireless thermostat EKRTETSB You can use the remote indoor temperature sensor EKRTETSB only in combination with the wireless thermostat EKRTRB For installation instructions see the installation manual of the room thermostat and the addendum book for optional equipment Digital I O PCB EKRP1HBAA The digital I O PCB is required to provide following signals Alarm output Space he...

Страница 22: ...te outdoor sensor PC cable EKPCCAB4 The PC cable makes a connection between the hydro PCB A1P of the outdoor unit and a PC It gives the possibility to update the hydro software and EEPROM For installation instructions see Installation manual of the PC cable 11 1 2 To connect the PC cable to the switch box 4126 Heat pump convector FWX For providing space heating cooling it is possible to use the fo...

Страница 23: ...llation manual of the connection kit Connection kit for third party tank with built in thermostat EKHY3PART2 Kit for the connection of a third party tank with built in thermostat to the system The kit converts a thermostat demand from the tank to a domestic hot water request for the outdoor unit Domestic hot water tank For providing domestic hot water a domestic hot water tank can be connected to ...

Страница 24: ...ntrol For installation instructions see the installation and operation manual of the Human Comfort Interface HCI as room thermostat and the addendum book for optional equipment Domestic hot water tank thermistor EKTESE1 EKTESE2 To increase the maximum distance between the domestic hot water tank and the outdoor unit a 30 m thermistor can be connected For stainless steel tanks EKTESE1 can be connec...

Страница 25: ...ies with the minimum requirements see Third party tank requirements 425 Third party tank requirements In case of a third party tank the tank shall adhere to the following requirements The heat exchanger coil of the tank is 1 05 m and 3 7 m The tank thermistor must be located above the heat exchanger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performanc...

Страница 26: ...3 Power supply layouts with power meters 49 6 6 Setting up the power consumption control 54 6 6 1 Permanent power limitation 54 6 6 2 Power limitation activated by digital inputs 55 6 6 3 Power limitation process 56 6 6 4 BBR16 power limitation 57 6 7 Setting up an external temperature sensor 58 6 1 Overview Application guidelines The purpose of the application guidelines is to give a glance of th...

Страница 27: ...ermo OFF 6 2 Setting up the space heating cooling system The heat pump system supplies leaving water to heat emitters in one or more rooms Because the system offers a wide flexibility to control the temperature in each room you need to answer the following questions first How many rooms are heated or cooled by the heat pump system Which heat emitter types are used in each room and what is their de...

Страница 28: ...room thermostat Configuration Setting Value Unit temperature control 2 9 Code C 07 2 Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface Number of water temperature zones 4 4 Code 7 02 0 Single zone Main Benefits Highest comfort and efficiency The smart room thermostat functionality can decrease or increase the desired leaving water t...

Страница 29: ...e wireless external room thermostat optional equipment EKRTRB Configuration Setting Value Unit temperature control 2 9 Code C 07 1 External room thermostat Unit operation is decided by the external thermostat Number of water temperature zones 4 4 Code 7 02 0 Single zone Main External room thermostat for the main zone 2 A Code C 05 1 1 contact When the used external room thermostat or heat pump con...

Страница 30: ...e heat pump convectors The installation manual of the heat pump convector options The addendum book for optional equipment The space heating cooling demand signal is sent to one digital input on the outdoor unit X2M 35 and X2M 30 The space operation mode is sent to the heat pump convectors by one digital output on the outdoor unit X2M 4 and X2M 3 Configuration Setting Value Unit temperature contro...

Страница 31: ...or to the external backup heater kit if there is one A shut off valve field supply is installed before the underfloor heating to prevent condensation on the floor during cooling operation The desired room temperature is set via the controller of the heat pump convectors There are different controllers and setups possible for the heat pump convectors For more information see The installation manual...

Страница 32: ...T zone If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same you do NOT need a mixing valve station cost effective Example If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters Underfloor heating or radiators Thermostatic valves If you are heating up rooms with underfloor hea...

Страница 33: ...ature of the dedicated Human Comfort Interface Number of water temperature zones 4 4 Code 7 02 0 Single zone Main Benefits Easy Same installation as for one room but with thermostatic valves Underfloor heating or radiators Multiple external room thermostats Setup M1 M2 C B b c b a A A Main leaving water temperature zone B Room 1 C Room 2 a User interface delivered as accessory b External room ther...

Страница 34: ...7 02 0 Single zone Main Benefits Compared with underfloor heating or radiators for one room Comfort You can set the desired room temperature including schedules for each room via the room thermostats Heat pump convectors Multiple rooms Setup b a b B C A A Main leaving water temperature zone B Room 1 C Room 2 a User interface delivered as accessory b Heat pump convectors controllers For more inform...

Страница 35: ...ecided by the external thermostat Number of water temperature zones 4 4 Code 7 02 0 Single zone Main Benefits Compared with heat pump convectors for one room Comfort You can set the desired room temperature including schedules for each room via the remote controller of the heat pump convectors Combination Underfloor heating Heat pump convectors Multiple rooms Setup c B C A M1 b a M1 A Main leaving...

Страница 36: ...erface connected to the outdoor unit decides the space operation mode Mind that the operation mode on each external room thermostat and controller of the heat pump convectors must be set to match the outdoor unit INFORMATION To increase comfort and performance we recommend to install the valve kit option EKVKHPC on each heat pump convector Configuration Setting Value Unit temperature control 2 9 C...

Страница 37: ...tional zone Heat pump convectors In heating 45 C In cooling 12 C a In cooling mode you can allow the underfloor heating main zone to provide refreshment no real cooling or NOT allow it See setup below Setup Three bizone kit system variations are possible 1 System without hydraulic separator D d B C a a f A E b c g e 2 System with hydraulic separator for main zone B C a a f A E D b c g d e h 3 Syst...

Страница 38: ...e in relation to the required capacity of both water temperature zones A bypass valve must be installed to make water recirculation possible when all shut off valves are closed To guarantee reliable operation provide a minimum water flow as described in table To check the water volume and flow rate in 8 1 Preparing water piping 471 For the additional zone The heat pump convectors are directly conn...

Страница 39: ...4 Code 7 02 1 Dual zone Main additional In case of heat pump convectors External room thermostat for the additional zone 3 A Code C 06 1 1 contact When the used external room thermostat or heat pump convector can only send a thermo ON OFF condition No separation between heating or cooling demand Bizone kit installed 9 P 1 Code E 0B 2 Yes A bizone kit is installed in order to add an additional temp...

Страница 40: ...external room thermostat control Space heating can be done by The outdoor unit An auxiliary boiler field supply connected to the system When there is a heating request the outdoor unit or the auxiliary boiler starts operating depending on the outdoor temperature status of the changeover to external heat source When the permission is given to the auxiliary boiler the space heating by the outdoor un...

Страница 41: ...um 60 C Install an aquastat valve in the return water flow of the heat pump Set the aquastat valve to close above 60 C and to open below 60 C Install non return valves An expansion vessel is already pre mounted in the outdoor unit But for bivalent operation also make sure that there is an expansion vessel in the auxiliary boiler loop Otherwise when bivalent operation is running and if the Aquastat...

Страница 42: ... leaving water temperature zone see 6 2 Setting up the space heating cooling system 427 The auxiliary contact can be An outdoor temperature thermostat An electricity tariff contact A manually operated contact Setup Connect the following field wiring L N H Com A K2A K1A X2M BTI K2A K1A Outdoor Auto Boiler 35 30 X Y Outdoor BTI Boiler thermostat input A Auxiliary contact normally closed H Heating de...

Страница 43: ...he volume and desired temperature for the DHW tank consists of 1 Determining the DHW consumption equivalent hot water volume at 40 C 2 Determining the volume and desired temperature for the DHW tank Determining the DHW consumption Answer the following questions and calculate the DHW consumption equivalent hot water volume at 40 C using typical water volumes Question Typical water volume How many s...

Страница 44: ...tabook of the storage tank Energy saving tips If the DHW consumption differs from day to day you can program a weekly schedule with different desired DHW tank temperatures for each day The lower the desired DHW tank temperature the more cost effective By selecting a larger DHW tank you can lower the desired DHW tank temperature The heat pump itself can produce domestic hot water of maximum 55 C lo...

Страница 45: ...of the heat pump Electrical booster heater For more information about Optimising the energy consumption for producing domestic hot water see 11 Configuration 4123 Connecting the electrical wiring of the standalone DHW tank to the outdoor unit see the installation manual of the DHW tank and the addendum book for optional equipment Connecting the water piping of the standalone DHW tank to the outdoo...

Страница 46: ...allation are field supply and the responsibility of the installer For the electrical wiring see 9 2 8 To connect the domestic hot water pump 4112 For more information about connecting the recirculation connection see the installation manual of the domestic hot water tank Configuration For more information see 11 Configuration 4123 You can program a schedule to control the DHW pump via the user int...

Страница 47: ... element as shown above If applicable legislation requires disinfection of the water piping until the tapping point you can connect a DHW pump and heater element if needed as shown above Configuration The outdoor unit can control DHW pump operation For more information see 11 Configuration 4123 6 4 6 DHW pump for tank preheating INFORMATION Restriction Only applicable in case of stainless steel ta...

Страница 48: ...roduced heat are calibrated automatically INFORMATION If glycol is present in the system E 0D 1 then the produced heat will NOT be calculated nor will it be displayed on the user interface The produced heat is calculated internally based on The leaving and entering water temperature The flow rate The power consumption of the booster heater if applicable in the domestic hot water tank Setup and con...

Страница 49: ...ethod because of higher accuracy Requires external power meters Setup and configuration When using electrical power meters set the number of pulses kWh for each power meter via the user interface INFORMATION When measuring the electrical power consumption make sure ALL power input of the system is covered by the electrical power meters 6 5 3 Power supply layouts with power meters 1 power meter You...

Страница 50: ...se power meter in other cases 2 Measures a Compressor module Connection X5M 3 4 Power meter type Single phase power meter according to the power supply of the outdoor unit a In the software the power consumption data of both meters is added so you do NOT have to set which meter covers which power consumption Exceptional cases You can also use a second power meter if The power range of one meter is...

Страница 51: ...le phase power meter 580 1 50 0 0 f e d g A B c c c a b X5M 5 6 Outdoor unit 1N external backup heater kit 1N or 3N b b Single or three phase power meter depending on external backup heater kit e d g 580 1 50 0 0 A B c c a a c c f f C C b b X5M 5 6 450896 005 3N A Outdoor unit B DHW tank C External backup heater kit a Electrical cabinet Normal kWh rate power supply b Power meter c Overcurrent fuse...

Страница 52: ... meter f e d g A B c c c a b X5M 5 6 580 1 50 0 0 S1S X5M 9 10 Outdoor unit 1N external backup heater kit 1N or 3N b b Single or three phase power meter depending on external backup heater kit e d g A B c c a a c c f f C C b b X5M 5 6 580 1 50 0 0 S1S X5M 9 10 450896 005 3N A Outdoor unit B DHW tank C External backup heater kit a Electrical cabinet Preferential kWh rate power supply b Power meter ...

Страница 53: ...M 3 4 c X5M 9 10 S1S Outdoor unit 1N external backup heater kit 1N or 3N b1 b1 Single or three phase power meter depending on external backup heater kit b2 Single phase power meter e d g 580 1 50 0 0 A B c c a1 a1 c c f f C C b1 b1 X5M 5 6 580 1 50 0 0 a2 b2 X5M 3 4 c X5M 9 10 S1S 450896 005 3N A Outdoor unit B DHW tank C External backup heater kit a1 Electrical cabinet Normal kWh rate power suppl...

Страница 54: ...ble in Swedish language Allows you to comply with BBR16 regulations Swedish energy regulations Limitation of power in kW Can be combined with the other kW power consumption controls If you do so the unit uses the most restrictive control NOTICE It is possible to install a field fuse with lower than recommended rating over the heat pump For this you must modify field setting 2 0E according to the m...

Страница 55: ...Power limitation is also useful in combination with an energy management system The power or current of the entire Daikin system is limited dynamically by digital inputs maximum four steps Each power limitation level is set via the user interface by limiting one of the following Current in A Power input in kW The energy management system field supply decides the activation of a certain power limit...

Страница 56: ... power consumption control settings in 9 9 via the user interface for the description of all settings see Power consumption control 4206 Select limitation by digital inputs Select the type of limitation power in kW or current in A Set the desired power limitation level corresponding to each digital input INFORMATION In case more than 1 digital input is closed at the same time the digital input pri...

Страница 57: ...nsumed energy A Outdoor unit B Booster heater C Backup heater a Limited outdoor unit operation b Full outdoor unit operation c Booster heater turned ON d Backup heater step 1 turned ON e Backup heater step 2 turned ON 6 6 4 BBR16 power limitation INFORMATION Restriction BBR16 settings are only visible when the language of the user interface is set to Swedish NOTICE 2 weeks to change After you acti...

Страница 58: ...as room thermostat measures the indoor ambient temperature Therefore the Human Comfort Interface must be installed on a location Where the average temperature in the room can be detected That is NOT exposed to direct sunlight That is NOT near a heat source That is NOT affected by outside air or air draught because of for example door opening closing If this is NOT possible we recommend to connect ...

Страница 59: ...n 4214 the outdoor unit is turned down to reduce standby energy losses As a result the outdoor ambient temperature is NOT read out If the desired leaving water temperature is weather dependent the full time outdoor temperature measurement is important This is another reason to install the optional outdoor ambient temperature sensor INFORMATION The external outdoor ambient sensor data either averag...

Страница 60: ...e units 68 7 3 2 To open the outdoor unit 68 7 3 3 To rotate the switch box 69 7 3 4 To close the outdoor unit 70 7 1 Preparing the installation site Choose an installation location with sufficient space to transport the unit in and out of the site Do NOT install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit MUS...

Страница 61: ...osed to wind It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind c b b a a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in the following places Sound sensitive areas e g near a bedroom so that the operation noise will cause no trouble Note If the sound is measured under actual installation conditions...

Страница 62: ...nd b Building c Outdoor unit d Windbreaker The outdoor unit is designed for outdoor installation only and for the following ambient temperatures Cooling mode 10 43 C Heating mode 25 25 C DHW production 25 35 C Mind the measurement guidelines Maximum height difference between domestic hot water tank and outdoor unit 5 m Maximum distance between outdoor unit and domestic hot water tank 10 m 25 m a b...

Страница 63: ...any Hungary Latvia Lithuania Norway Poland Romania Serbia Slovakia Sweden 1 Remove the screws holding the suction grille 2 Remove the suction grille and dispose of it 3 Reattach the screws to the unit 4 1 3 2 a a Suction grille Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up d c c a b a Snow cover or shed b Pedestal c Prevailing wind directio...

Страница 64: ... over 5 Protecting the unit against snow and wind by installing a snow cover and baffle plates See 7 1 Preparing the installation site 460 7 2 2 Precautions when mounting the outdoor unit INFORMATION Also read the precautions and requirements in the following chapters 2 General safety precautions 49 7 1 Preparing the installation site 460 7 2 3 To provide the installation structure Check the stren...

Страница 65: ... feet In this case you can use the bolts nuts washers and spring washers delivered with the unit as accessories 0 mm 7 2 4 To install the outdoor unit CAUTION To avoid injury do NOT touch the air inlet or aluminium fins of the unit CAUTION Do NOT remove the protective cardboard before the unit is installed properly 1 Carry the unit using the slings attached to the unit Pull up both sides of the sl...

Страница 66: ...aikin Altherma 3 M 4P685228 1A 2022 05 2 2 2 While handling the unit Keep both sides of the sling level Keep your back straight 110 kg 3 Install the outdoor unit as follows 1 Put the unit into position 2 Remove the slings by pulling 1 side of the sling 3 Fix the unit 2 3 2 1 a a a Air outlet ...

Страница 67: ...o drain waste water away from the unit Avoid drain water flowing over the footpath so that it does NOT become slippery in case of ambient freezing temperatures If you install the unit on a frame install a waterproof plate within 150 mm of the bottom side of the unit in order to prevent water from getting into the unit and to avoid drain water dripping see the following figure INFORMATION If necess...

Страница 68: ...over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint field supply 4 Attach the ends of the cables 5 Tighten the cables 7 3 Opening and closing the unit 7 3 1 About opening the units At certain times you have to open the unit Example When connecting the electrical wiring When maintaining or servicing the unit DANGER RI...

Страница 69: ...During the installation you will need access to the inside of the outdoor unit To have easier front access rotate the switch box out of the unit as follows Prerequisite The front plate has been removed 1 Push down the clip of the switch box holder 1 2 Rotate the switch box out of the unit 2 3 Rotate the switch box back until it engages properly in the switch box holder ...

Страница 70: ...EBLA04 08E2V3 E23V3 EDLA04 08E2V3 E23V3 Daikin Altherma 3 M 4P685228 1A 2022 05 3 4 7 3 4 To close the outdoor unit NOTICE Speed nut Make sure the speed nut for the top screw is correctly attached to the service cover 2 2 2 5 1 3 55 N m a a Speed nut ...

Страница 71: ...en diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to excessive corrosion Connecting piping Legislation Make all piping connections in accordance with the applicable legislation and the instructions in the Installation chapter respecting the water inlet and outlet Connecting piping Force Do NOT use excessive force when connecting the piping Deformation of the...

Страница 72: ...flow You can find the minimum required water flow for unit operation in the following table In all cases this flow needs to be guaranteed When the flow is lower the unit will stop operation and display error 7H If operation is Then the minimum required flow rate is Cooling 10 l min Heating 6 l min BUH operation 12 l min Heating defrost 12 l min DHW 25 l min Field supply components Water and glycol...

Страница 73: ...Separating circuits When using a 3 way valve in the water circuit make sure that the domestic hot water circuit and the floor heating circuit are fully separated Valve Change over time When using a 2 way valve or a 3 way valve in the water circuit the maximum change over time of the valve must be 60 seconds Filter It is strongly recommended to install an additional filter on the heating water circ...

Страница 74: ...estic hot water tank c d a b a Recirculation connection b Hot water connection c Shower d Recirculation pump 8 1 2 Formula to calculate the expansion vessel pre pressure The pre pressure Pg of the vessel depends on the installation height difference H Pg 0 3 H 10 bar 8 1 3 To check the water volume and flow rate The outdoor unit has an expansion vessel of 7 litre with a factory set pre pressure of...

Страница 75: ...re is 15 C 50 l INFORMATION In critical processes or in rooms with a high heat load extra water might be required NOTICE Never use less water than the minimum water volume It may cause the unit to malfunction NOTICE When circulation in each space heating cooling loop is controlled by remotely controlled valves it is important that the minimum water volume is guaranteed even if all of the valves ar...

Страница 76: ...wing Decrease the pre pressure according to the required installation height difference The pre pressure should decrease by 0 1 bar for each metre below 7 m Check if the water volume does NOT exceed the maximum allowed water volume 7 m Do the following Increase the pre pressure according to the required installation height difference The pre pressure should increase by 0 1 bar for each metre above...

Страница 77: ...ops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation See the recommended procedure as described in 12 4 Checklist during commissioning 4226 8 1 4 Changing the pre pressure of the expansion vessel NOTICE ONLY a li...

Страница 78: ...the highest point in the water circuit The total water volume in the water circuit is 250 l Actions Because the total water volume 250 l is more than the default water volume 185 l the pre pressure must be decreased The required pre pressure is Pg 0 3 H 10 bar 0 3 0 10 bar 0 3 bar The corresponding maximum water volume at 0 3 bar is 270 l See the graph in Maximum water volume 476 Because 250 l is ...

Страница 79: ...tion manual of the tank For instructions regarding the external backup heater kit see The installation manual of the backup heater kit To connect the backup heater kit 4100 this topic partially supersedes the installation manual of the backup heater 8 2 2 Precautions when connecting the water piping INFORMATION Also read the precautions and requirements in the following chapters 2 General safety p...

Страница 80: ...ice purposes it is recommended to also install a shut off valve and drain point to the water OUT connection This shut off valve and drain point are field supplied NOTICE Install air purge valves at all local high points NOTICE In case an optional domestic hot water tank is installed A pressure relief valve field supply with an opening pressure of maximum 10 bar 1 MPa must be installed on the domes...

Страница 81: ... of water WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system Therefore it i...

Страница 82: ...ll prevent the piping from bursting but NOT the liquid inside the piping from freezing Protection against freezing the glycol will prevent the liquid inside the piping from freezing NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table above with the specifications provided by the glycol manufacturer If necessary meet the requ...

Страница 83: ...ptional field supply c Normally closed valves recommended field supply Part Description a An automatic air intake for air supply should be installed at the highest point For example an automatic air purge b Protection for the field piping Install the freeze protection valves At all lowest points of the field piping In the coldest part of the field piping away from heat sources Vertically to allow ...

Страница 84: ...C at least 2 C higher than the maximum opening temperature of the freeze protection valve If lower freeze protection valves can open during cooling operation 8 2 5 To fill the water circuit To fill the water circuit use a field supply filling kit Make sure you comply with the applicable legislation NOTICE The unit contains an automatic air purge valve Make sure it is open All automatic air purge v...

Страница 85: ...he minimum insulation thickness can be determined using the Hydronic Piping Calculation tool The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator which can be reached via https professional standbyme daikin eu Please contact your dealer if you have no access to Heating Solutions Navigator This recommendation ensures good operation of the unit however local regulations ma...

Страница 86: ...tic hot water pump 112 9 2 9 To connect the alarm output 112 9 2 10 To connect the space cooling heating ON OFF output 113 9 2 11 To connect the changeover to external heat source 114 9 2 12 To connect the power consumption digital inputs 115 9 2 13 To connect the safety thermostat normally closed contact 116 9 2 14 To connect a Smart Grid 117 9 2 15 To connect the WLAN cartridge delivered as acce...

Страница 87: ...or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents CAUTION Do NOT push or place redundant cable length in the unit NOTICE The distance between the high voltage and low voltage cables should be at lea...

Страница 88: ...preferential kWh rate power supply Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorised to bill clients at benefit rates E g time of use rates seasonal rates Wärmepumpentarif in Germany and Austria This equipment allows for connection to such preferential kWh rate power supply delivery systems Consult with the elec...

Страница 89: ...eparate normal kWh rate power supply Normal kWh rate power supply With integrated backup heater e d c f A B b b b a 580 1 50 0 0 With external backup heater kit d c f A B b b a b e C 580 1 50 0 0 A Outdoor unit B DHW tank C External backup heater kit a Electrical cabinet Normal kWh rate power supply b Overcurrent fuse c Compressor module d Hydro module e Backup heater f Booster heater Preferential...

Страница 90: ...ntegrated backup heater e d c f A B b b b a1 580 1 50 0 0 a2 b X5M 9 10 S1S 580 1 50 0 0 With external backup heater kit d c f A B b b a1 b e C 580 1 50 0 0 a2 b X5M 9 10 S1S 580 1 50 0 0 A Outdoor unit B DHW tank C External backup heater kit a1 Electrical cabinet Normal kWh rate power supply a2 Electrical cabinet Preferential kWh rate power supply b Overcurrent fuse c Compressor module d Hydro mo...

Страница 91: ...9 2 9 To connect the alarm output 4112 Space cooling heating operation control See 9 2 10 To connect the space cooling heating ON OFF output 4113 Changeover to external heat source control See 9 2 11 To connect the changeover to external heat source 4114 Power consumption digital inputs See 9 2 12 To connect the power consumption digital inputs 4115 Safety thermostat See 9 2 13 To connect the safe...

Страница 92: ...ipment In case of wired room thermostat with multi zoning base unit see Installation manual of the wired room thermostat digital or analogue multi zoning base unit Addendum book for optional equipment In this case You need to connect the wired room thermostat digital or analogue to the multi zoning base unit You need to connect the multi zoning base unit to the outdoor unit For cooling heating ope...

Страница 93: ...allation manual of the heat pump convector options Addendum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Ext thermostat type For the additional zone 3 A Ext thermostat type 3 9 read only Control Remote outdoor sensor See Installation manual of the remote outdoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 1 Externa...

Страница 94: ...nk Domestic hot water tank thermistor See Installation manual of the domestic hot water tank Addendum book for optional equipment Wires 2 The thermistor and connection wire 12 m are delivered with the domestic hot water tank A thermistor 30 m is optionally available 9 2 Domestic hot water in case of DHW tank Power supply for booster heater from outdoor unit to thermal protector of booster heater S...

Страница 95: ...d EKHWSU D a1 Contactor a2 Terminal block b Connection kit for third party tank with built in thermostat EKHY3PART2 c Flow switch EKFLSW2 d Demand PCB A8P EKRP1AHTA e Digital I O PCB A4P EKRP1HBAA f Smart grid relay kit EKRELSG 9 2 1 To connect the electrical wiring to the outdoor unit 1 Open the service cover See 7 3 2 To open the outdoor unit 4 68 If necessary rotate the switch box See 7 3 3 To ...

Страница 96: ...d fix the cables with cable ties 9 2 2 To connect the main power supply This topic describes 2 possible ways to connect the main power supply In case of normal kWh rate power supply In case of preferential kWh rate power supply In case of normal kWh rate power supply Normal kWh rate power supply Wires 1N GND Maximum running current Refer to name plate on unit 1 Access the electrical connections Se...

Страница 97: ...Preferential kWh rate power supply contact Wires 2 0 75 1 25 mm Maximum length 50 m Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA 9 8 Benefit kWh power supply 1 Access the electrical connections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the pr...

Страница 98: ... required in the following cases if the preferential kWh rate power supply is interrupted when active OR if no power consumption of the hydro module of the outdoor unit is allowed at the preferential kWh rate power supply when active 5 M 2 X 6 M 2 X L N 1N 50 Hz 230 V AC 6 3 A 180 6 5 X2M 4 Connect the preferential power supply contact X5M 10 S1S X5M 9 910 X5M 180 5 In case of a separate normal kW...

Страница 99: ... External backup heater kit 4100 Backup heater type Power supply Wires 3V 1N 230 V 2 GND 9 3 Backup heater WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed ALWAYS connect the backup heater power supply and the earth cable Connect the power supply of the...

Страница 100: ...thout integrated backup heater you can install the external backup heater kit EKLBUHCB6W1 If you do so then under certain conditions you also need to install a bypass valve kit EKMBHBP1 See To connect the backup heater kit 4100 Bypass valve kit necessity 4105 To connect the bypass valve kit 4106 To connect the backup heater kit The installation of the external backup heater kit is described in the...

Страница 101: ... 400 V 8 6 A 9 kW 3N 400 V 13 A a This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the pub...

Страница 102: ...X14M 3 Fix the cable with cable ties to the cable tie mountings During connection of the backup heater miswiring is possible To detect possible miswiring it is highly recommended to measure the resistance value of the heater elements Depending on the capacity and power supply following resistance values see table below should be measured ALWAYS measure the resistance on the contactor clamps K1M K2...

Страница 103: ...14 1 3 5 13 2 4 6 14 Ω Ω To connect the backup heater kit to the outdoor unit The wiring between the backup heater kit and the outdoor unit is as follows 1 2 3 4 5 6 7 8 9 10 X3M X15M 1 2 1 2 X5M X15M EKLBUHCB6W A B HV LV A Outdoor unit B Backup heater kit HV High voltage connections backup heater thermal protector backup heater connection LV Low voltage connection backup heater thermistor NOTICE ...

Страница 104: ...2 X15M F1B LV HV 2 On the outdoor unit connect the HV cable to the appropriate terminals as shown in the illustration below HV X3M 1 X3M 2 X3M 3 X3M 4 X3M 5 6 7 8 9 10 X15M EKLBUHCB6W 180 X3M 1 2 3 4 5 X3M 3 On the outdoor unit connect the LV cable to the appropriate terminals as shown in the illustration below LV 1 M 5 X 2 M 5 X 1 2 X15M EKLBUHCB6W ...

Страница 105: ...led the installation of valve kit EKMBHBP1 is required if condensation is expected inside the backup heater 7 10 13 16 19 22 25 28 31 7 10 13 16 19 22 25 28 31 20 23 26 29 32 A C A C B C DB A Leaving water evaporator temperature B Dry bulb temperature Relative humidity 40 Relative humidity 60 Relative humidity 80 Example Given are an ambient temperature of 25 C and a relative humidity of 40 If the...

Страница 106: ...he instruction sheet delivered with the bypass valve kit Wires 3 0 75 mm The components of the bypass valve kit are as follows You only need B and D A B C D 1 Integrate components B and D as follows in the system B D FHL1 FHL2 FHL3 EKMBHBP1 B D Cu A 18 C 0 25 m 0 5 m 0 1 m 0 2 m Alpex A 5 C 2 On the outdoor unit connect B to the appropriate terminals as shown in the illustration below X2M 4 X2M 3 ...

Страница 107: ...necting the user interface cable to it if necessary Opening the user interface after it is installed Connecting the user interface cable to the outdoor unit Wires 4 0 75 1 25 mm Maximum length 200 m 2 9 Control 1 6 Room sensor offset 1 Access the electrical connections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the user interface cable to the outdoor unit Fix the ...

Страница 108: ...interface and connecting the user interface cable to it You need the following user interface accessories delivered on top of the unit a b c d 2 2 a Front plate b Rear plate c Screws d Wall plugs 1 Mount the rear plate to the wall Use the 2 screws and wall plugs Use any of the 6 holes The holes are compatible with standard electrical box extenders of 60 mm a b 60 mm a Holes ...

Страница 109: ...able in the part of the casing where the casing is thinner A a b c d B X1B B A a Top side b Left side c Bottom side d Right side 3 Mount the front plate Align the positioning pins and push the front plate onto the rear plate until it moves into place with a click The connector pins are automatically inserted correctly a b a a Positioning pins b Connector pins Opening the user interface after it is...

Страница 110: ...nd a combination of underfloor heating and heat pump convectors install a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied by PCB 1 Access the electrical connections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the valve control cable to the app...

Страница 111: ...lied by PCB 9 A Energy metering INFORMATION In case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Access the electrical connections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the electricity meters cable to the appropriate terminals as shown in...

Страница 112: ...To connect the electrical wiring to the outdoor unit 495 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below X2M 2 X2M 1 M2P M 1 180 2 1 X2M 3 Fix the cable with cable ties to the cable tie mountings 9 2 9 To connect the alarm output Wires 2 1 0 75 mm Maximum load 0 3 A 250 V AC 9 D Alarm output 1 Access the electrical connections See 9 2 1 T...

Страница 113: ...WARNING Stripped wire Make sure that stripped wire cannot make contact with possible water on the bottom plate 3 Fix the cable with cable ties to the cable tie mountings 9 2 10 To connect the space cooling heating ON OFF output INFORMATION Cooling is only applicable in case of reversible models Wires 2 1 0 75 mm Maximum load 0 3 A 250 V AC 1 Access the electrical connections See 9 2 1 To connect t...

Страница 114: ...A is required WARNING Stripped wire Make sure that stripped wire cannot make contact with possible water on the bottom plate 3 Fix the cable with cable ties to the cable tie mountings 9 2 11 To connect the changeover to external heat source INFORMATION Bivalent is only possible in case of 1 leaving water temperature zone with room thermostat control OR external room thermostat control Wires 2 0 75...

Страница 115: ... 3 Fix the cable with cable ties to the cable tie mountings 9 2 12 To connect the power consumption digital inputs Wires 2 per input signal 0 75 mm Power limitation digital inputs 12 V DC 12 mA detection voltage supplied by PCB 9 9 Power consumption control 1 Access the electrical connections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the power consumption digital...

Страница 116: ... contact Wires 2 0 75 mm Maximum length 50 m Safety thermostat contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum applicable load of 15 V DC 10 mA 1 Access the electrical connections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the safety thermostat normally closed cable to the appropriate terminals as shown in the il...

Страница 117: ... Smart Grid This topic describes 2 possible ways to connect the outdoor unit to a Smart Grid In case of low voltage Smart Grid contacts In case of high voltage Smart Grid contacts This requires the installation of the Smart Grid relay kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forc...

Страница 118: ...ections See 9 2 1 To connect the electrical wiring to the outdoor unit 495 2 Connect the wiring as follows X5M 4 X5M 3 X5M 10 X5M 9 X5M 6 X5M 5 1 2 S4S S10S S11S 180 X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter 0 5 mm Wires high voltage Smart Grid contacts 1 mm 9 8 4 3 Benefit kWh power su...

Страница 119: ... factory mounted If you also connect a safety thermostat Q4L replace the jumper with the safety thermostat wires S4S Smart Grid pulse meter optional 1 Install the components of the Smart Grid relay kit as follows a b c d e K1A K2A X10M 2 4 K1A Relay for Smart Grid contact 1 K2A Relay for Smart Grid contact 2 X10M Terminal block a Screws for X10M b Screws for K1A and K2A c Sticker to put on the hig...

Страница 120: ...M 2 X10M 3 X10M 4 L L N N 1 2 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 180 1 2 3 4 X10M 4 Fix the cables with cable ties to the cable tie mountings If necessary bundle excessive cable length with a cable tie 9 2 15 To connect the WLAN cartridge delivered as accessory D Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the i...

Страница 121: ...9 Electrical installation Installer reference guide 121 EBLA04 08E2V3 E23V3 EDLA04 08E2V3 E23V3 Daikin Altherma 3 M 4P685228 1A 2022 05 ...

Страница 122: ...esistance over the poles can drop but if it is at least 1 MΩ then the unit will not break down Use a 500 V mega tester when measuring insulation Do NOT use a mega tester for low voltage circuits 1 Measure the insulation resistance over the poles If Then 1 MΩ Insulation resistance is OK This procedure is finished 1 MΩ Insulation resistance is not OK Go to the next step 2 Turn ON the power and leave...

Страница 123: ...her dependent curve 145 11 5 1 What is a weather dependent curve 145 11 5 2 2 points curve 145 11 5 3 Slope offset curve 146 11 5 4 Using weather dependent curves 148 11 6 Settings menu 150 11 6 1 Malfunctioning 150 11 6 2 Room 150 11 6 3 Main zone 155 11 6 4 Additional zone 164 11 6 5 Space heating cooling 168 11 6 6 Tank 178 11 6 7 User settings 186 11 6 8 Information 190 11 6 9 Installer settin...

Страница 124: ...cessing settings Legend for tables You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home...

Страница 125: ...verview setting Example Modify 1 01 from 15 to 20 Most settings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user permission level to Installer See To change the user permission level 4124 2 Go to 9 I Installer settings Overview field settings 3 Turn the left...

Страница 126: ... home screen INFORMATION When you change the overview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applied 11 1 2 To connect the PC cable to the switch box Prerequisite The EKPCCAB4 kit is required 1 Connect the USB connector of the cable to your PC 2 Conne...

Страница 127: ...e configuration here All the settings can also be adjusted in the settings menu use the breadcrumbs For the setting Refer to Language 7 1 Time date 7 2 Hours Minutes Year Month Day Daylight savings time Format System Indoor unit type read only 11 6 9 Installer settings 4191 Backup heater type 9 3 1 Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 11 6 5 Space heating cooling 4168 Glycol ...

Страница 128: ...ble Schedule 2 1 WD curve type 2 E Additional zone only if 4 4 1 Emitter type 3 7 11 6 4 Additional zone 4164 Control read only 3 9 Setpoint mode 3 4 Heating WD curve 3 5 if applicable Cooling WD curve 3 6 if applicable Schedule 3 1 WD curve type 3 C read only Tank if applicable Heat up mode 5 6 11 6 6 Tank 4178 Comfort setpoint 5 2 Eco setpoint 5 3 Reheat setpoint 5 4 Hysteresis 5 9 and 5 A 11 3 ...

Страница 129: ...t curve c4 Screen with schedule 11 3 2 Home screen Press the button to go back to the home screen You see an overview of the unit configuration and the room and setpoint temperatures Only symbols applicable for your configuration are visible on the home screen 6 26 Feb 2020 22 19 55 21 35 j e2 l k1 k2 k3 45 d e1 g3 g2 g1 f i2 i3 i4 i1 a2 a1 e3 b c 1 6 h2 bar h1 Possible actions on this screen Go t...

Страница 130: ...cy Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is currently being used for space heating e3 Smart energy is currently being used for domestic hot water f Space operation mode Cooling Heating g Outdoor quiet mode g1 6 Measured outdoor temperature ...

Страница 131: ...r type Underfloor heating Fancoil unit Radiator i3 21 Measured room temperature a i4 35 Leaving water temperature setpoint a j Holiday mode Holiday mode active k Additional zone k1 Installed room thermostat type Unit operation is decided by the external room thermostat wired or wireless No room thermostat installed or set Unit operation is decided based on the leaving water temperature regardless ...

Страница 132: ...dicated Human Comfort Interface BRC1HHDA used as room thermostat is controlling the outdoor unit Set the room temperature 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temperature zones Shows the applicable symbol for your additional zone emitter...

Страница 133: ...D Wireless gateway Restriction Only displayed if a wireless LAN WLAN is installed Contains settings needed when configuring the ONECTA app 11 3 4 Menu screen Example 7 1 Language Time date Holiday Possible actions on this screen Go through the list Enter the submenu setting 11 3 5 Setpoint screen The setpoint screen is displayed for screens describing system components that need a setpoint value E...

Страница 134: ...by the unit a2 Restricted by the installer Maximum temperature limit b1 Fixed by the unit b2 Restricted by the installer Current temperature c Measured by the unit Desired temperature d Turn the right dial to increase decrease Submenu e Turn or press the left dial to go to the submenu 11 3 6 Detailed screen with values Example a b c a b c 7 2 1 Time date Hours 11 30 Minutes a Settings b Values c S...

Страница 135: ...e if the DHW tank mode is Schedule reheat Electricity prices under 7 5 User settings Electricity price Restriction Only applicable if Bivalent is enabled by the installer 7 5 1 High You can use these preset values in 7 5 4 Schedule weekly schedule screen for the energy prices See 11 4 4 Setting the energy prices 4143 7 5 2 Medium 7 5 3 Low Additional to the user defined preset values the system al...

Страница 136: ... schedule 2 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 3 Select Select Delete Rename Select 4 Select the schedule that you currently want to use Possible schedules The table contains the following information Schedule Control This column shows you where you can consult the currently selected schedule for the specific control If needed you can Select another ...

Страница 137: ... leaving water temperature for the main zone in cooling mode Predefined schedules 1 Activation screen 2 1 Schedule Possible actions In case of weather dependent Shift temperatures within range Otherwise Temperatures within range 3 2 Additional zone Heating schedule Schedule for when the system is allowed to heat up the additional zone in heating mode Predefined schedules 1 Activation screen 3 1 Sc...

Страница 138: ...also takes the user defined preset value 5 4 Reheat setpoint into account 7 4 2 User settings Quiet Schedule Schedule for when the unit has to use which quiet mode level Predefined schedules 1 Activation screen 7 4 1 Activation only available to installers Possible actions You can use the following system defined preset values Off Quiet More quiet Most quiet See About quiet mode 4187 7 5 4 User se...

Страница 139: ... if room thermostat control is active If leaving water temperature control is active you can program the main zone schedule instead 1 Go to the schedule 2 optional Clear the content of the whole week schedule or the content of a selected day schedule 3 Program the schedule for Monday 4 Copy the schedule to the other weekdays 5 Program the schedule for Saturday and copy it to Sunday 6 Give the sche...

Страница 140: ...defined 1 2 Select Edit Delete Edit Copy 3 Use the left dial to select an entry and edit the entry with the right dial You can program up to 6 actions each day On the bar a high temperature has a darker colour than a low temperature 0 6 00 8 30 17 30 20 C 18 C 22 00 18 C 21 C 12 24 Mon Note To clear an action set its time as the time of the previous action 4 Confirm the changes Result The schedule...

Страница 141: ...r defined 1 2 Select Copy Delete Edit Copy Result Next to the copied day C is displayed 3 Select Tuesday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 4 Select Paste Delete Edit Copy Paste Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C 5 Repeat this action for all other weekdays Mon Sat Wed Fri Thu Tue Sun User defined 1 C To program the schedule for Saturday and copy it to Sunday 1 Select Sat...

Страница 142: ...me of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Rename Delete Rename Select 3 optional To delete the current schedule name browse through the character list until is displayed then press to remove the previous character Repeat for each character of the schedule name 4 To name the current schedule browse through the character list and confirm the selected character Th...

Страница 143: ... the gas price 1 Go to 7 6 User settings Gas price 2 Select the correct gas price 3 Confirm the changes INFORMATION Price value ranging from 0 00 990 valuta kWh with 2 significant values To set the electricity price 1 Go to 7 5 1 7 5 2 7 5 3 User settings Electricity price High Medium Low 2 Select the correct electricity price 3 Confirm the changes 4 Repeat this for all three electricity prices IN...

Страница 144: ...the value for the gas price with the following formula Actual gas price Incentive kWh 0 9 For the procedure to set the gas price see To set the gas price 4143 To set the electricity price in case of an incentive per kWh renewable energy Calculate the value for the electricity price with following formula Actual electricity price Incentive kWh For the procedure to set the electricity price see To s...

Страница 145: ...To be able to compensate for differences in temperature the unit relies on its weather dependent curve This curve defines how much the temperature of the tank or leaving water must be at different outdoor temperatures Because the slope of the curve depends on local circumstances such as climate and the insulation of the building the curve can be adjusted by an installer or user Types of weather de...

Страница 146: ...rm changes and proceed 11 5 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature...

Страница 147: ...at X1 is unequally higher than the preferred temperature at X2 When offset is changed the new preferred temperature at X1 is equally higher as the preferred temperature at X2 c Slope d Offset e Selected weather dependent zone Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X1 X2 Examples of outdoor ambient temperature Y1 Y2 Y3 Y4 Examples of desired tan...

Страница 148: ...t mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent Tank 5 B Tank Setpoint mode Restriction Only available to installers Weather dependent To change the ty...

Страница 149: ...aximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fi...

Страница 150: ...ion User profile Main zone 0 Malfunctioning 11 6 2 Room Overview The following items are listed in the submenu 1 Room Main zone Malfunctioning Operation Additional zone 1 Room Setpoint screen 1 1 Schedule 1 2 Heating schedule 1 3 Cooling schedule 1 4 Antifrost 1 5 Setpoint range 1 6 Room sensor offset 1 7 Room sensor offset 1 9 Room comfort setpoint Setpoint screen Control the room temperature of ...

Страница 151: ...e case when 2 9 Control External room thermostat and C 2 Space heating cooling Off or if 2 9 Control Leaving water In the above cases Antifrost will heat the space heating water to a reduced setpoint when the outdoor temperature is lower than 6 C Main zone unit control method 2 9 Description Leaving water temperature control C 07 0 Room frost protection is NOT guaranteed External room thermostat c...

Страница 152: ...room antifrost 2 06 is activated limited frost protection by the unit is possible If Then Space heating cooling Off and Outdoor ambient temperature drops below 6 C The unit will supply leaving water to the heat emitters to heat up the room again and the temperature setpoint of the leaving water will be lowered Space heating cooling On and Operation mode Heating The unit will supply leaving water t...

Страница 153: ... Space heating cooling On and Operation mode Heating and The external room thermostat is Thermo OFF and Outdoor temperature drops below 6 C The unit will supply leaving water to the heat emitters to heat up the room again and the temperature setpoint of the leaving water will be lowered Space heating cooling On and Operation mode Cooling There is no room frost protection Room thermostat control C ...

Страница 154: ... 1 3 07 Heating minimum 1 5 2 3 06 Heating maximum 1 5 3 3 09 Cooling minimum 1 5 4 3 08 Cooling maximum Room sensor offset Only applicable in room thermostat control To calibrate the external room temperature sensor give an offset to the value of the room thermistor as measured by the Human Comfort Interface BRC1HHDA used as room thermostat or by the external room sensor The setting can be used t...

Страница 155: ...bmenu 2 Main zone Additional zone Room Malfunctioning Space heating cooling 2 Main zone Setpoint screen 2 1 Schedule 2 2 Heating schedule 2 3 Cooling schedule 2 4 Setpoint mode 2 5 Heating WD curve 2 6 Cooling WD curve 2 7 Emitter type 2 8 Setpoint range 2 9 Control 2 A Ext thermostat type 2 B Delta T 2 C Modulation 2 E WD curve type Setpoint screen Control the leaving water temperature for the ma...

Страница 156: ...does not depend on the outdoor ambient temperature In WD heating fixed cooling mode the desired leaving water temperature depends on the outdoor ambient temperature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Description 2 4 N A Setpoint mode Fixed WD heati...

Страница 157: ... main zone Ta Outdoor temperature 1 00 Low outdoor ambient temperature 40 C 5 C 1 01 High outdoor ambient temperature 10 C 25 C 1 02 Desired leaving water temperature when the outdoor temperature equals or drops below the low ambient temperature 9 01 C 9 00 C Note This value should be higher than 1 03 as for low outdoor temperatures warmer water is required 1 03 Desired leaving water temperature w...

Страница 158: ... be higher than 1 09 as for low outdoor temperatures less cold water is required 1 09 Desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature 9 03 C 9 02 C Note This value should be lower than 1 08 as for high outdoor temperatures colder water is required Emitter type Heating up or cooling down the main zone can take longer This depends on ...

Страница 159: ...that in heating the zone with the lowest water temperature is configured as the main zone and the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towards a low temperature emitter underfloor heating To avoid this Install an aquastat thermostatic valve to avoid...

Страница 160: ...n and selection of the heat emitters The desired leaving water temperature is the result of several settings preset values shift values weather dependent curves modulation As a result too high or too low leaving water temperatures could occur which lead to overtemperatures or capacity shortage By limiting the leaving water temperature range to adequate values depending on the heat emitter such sit...

Страница 161: ... used the external room thermostat will control the room frost protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 External room thermostat type for the main zone 1 1 contact The used external room thermostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand The room thermostat is con...

Страница 162: ...en leaving water temperature setpoint and inlet temperature at startup INFORMATION If the main zone or the additional zone has a heating demand and this zone is equipped with radiators then the target delta T that the unit will use in heating operation will be 8 C fixed If the zones are not equipped with radiators then in heating the unit will give priority to the target delta T for the additional...

Страница 163: ...Yes enabled Note The desired leaving water temperature can only be read out on the user interface 2 C 2 8 06 Max modulation 0 C 10 C This is the temperature value by which the desired leaving water temperature is increased or decreased INFORMATION When leaving water temperature modulation is enabled the weather dependent curve needs to be set to a higher position than 8 06 plus the minimum leaving...

Страница 164: ...pe 3 8 Setpoint range 3 9 Control 3 A Ext thermostat type 3 B Delta T 3 C WD curve type Setpoint screen Control the leaving water temperature for the additional zone via setpoint screen 3 Additional zone See 11 3 5 Setpoint screen 4133 Schedule Indicates if the desired leaving water temperature is according to a schedule See 11 6 3 Main zone 4155 Code Description 3 1 N A Schedule No Yes Heating sc...

Страница 165: ...ve 4145 and 11 5 3 Slope offset curve 4146 Both curve types require 4 field settings to be configured according to the figure below 0 00 0 01 Ta Tt 0 03 0 02 Tt Target leaving water temperature additional zone Ta Outdoor temperature 0 03 Low outdoor ambient temperature 40 C 5 C 0 02 High outdoor ambient temperature 10 C 25 C 0 01 Desired leaving water temperature when the outdoor temperature equal...

Страница 166: ...ature 10 C 25 C 0 06 High outdoor ambient temperature 25 C 43 C 0 05 Desired leaving water temperature when the outdoor temperature equals or drops below the low ambient temperature 9 07 C 9 08 C Note This value should be higher than 0 04 as for low outdoor temperatures less cold water is required 0 04 Desired leaving water temperature when the outdoor temperature equals or rises above the high am...

Страница 167: ... the highest leaving water temperature in heating operation and the lowest leaving water temperature in cooling operation 3 8 1 9 05 Heating minimum 15 C 37 C 3 8 2 9 06 Heating maximum 2 0D 2 emitter type additional zone radiator 37 C 60 C Else 37 C 55 C 3 8 3 9 07 Cooling minimum 5 C 18 C 3 8 4 9 08 Cooling maximum 18 C 22 C Control The control type for the additional zone is read only It is det...

Страница 168: ... heat emitters in heating mode If 2 0D 2 this is fixed to 8 C Else 3 C 10 C 3 B 2 1 0E Delta T cooling A minimum temperature difference is required for the good operation of heat emitters in cooling mode 3 C 10 C WD curve type There are 2 methods to define the weather dependent curves 2 points see 11 5 2 2 points curve 4145 Slope Offset see 11 5 3 Slope offset curve 4146 In 2 E WD curve type you c...

Страница 169: ...del is installed 1 Go to 4 Space heating cooling 2 Check if 4 1 Operation mode is listed and editable If so a heating cooling heat pump model is installed To tell the system which space operation to use you can You can Location Check which space operation mode is currently used Home screen Set the space operation mode permanently Main menu Restrict automatic changeover according to a monthly sched...

Страница 170: ...3 For each month select an option Reversible Not restricted Heating only Restricted Cooling only Restricted 4 Confirm the changes Example Changeover restrictions When Restriction During cold season Example October November December January February and March Heating only During warm season Example June July and August Cooling only In between Example April May and September Reversible The unit dete...

Страница 171: ...he measured indoor temperature Besides the desired heating cooling room temperature the installer sets a hysteresis value e g when in heating this value is related to the desired cooling temperature and an offset value e g when in heating this value is related to the desired heating temperature Example A unit is configured as following Desired room temperature in heating mode 22 C Desired room tem...

Страница 172: ...nsures that the active desired room temperature is always reached In heating mode the space operation only changes when the room temperature rises above the desired heating temperature added by the offset value Range 1 C 10 C Number of zones The system can supply leaving water to up to 2 water temperature zones During configuration the number of water zones must be set INFORMATION Mixing station I...

Страница 173: ...ortant that in heating the zone with the lowest water temperature is configured as the main zone and the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towards a low temperature emitter underfloor heating To avoid this Install an aquastat thermostatic valve t...

Страница 174: ...a b c d b c a Space heating cooling control b Off c On d Pump operation 4 5 F 0D 1 Sample The pump is ON when there is heating or cooling demand as the leaving water temperature has not yet reached the desired temperature yet When thermo OFF condition occurs the pump runs every 3 minutes to check the water temperature and demand heating or cooling if necessary Remark Sample is ONLY available in le...

Страница 175: ...h type of unit is used Code Description 4 6 E 02 Unit type 0 Reversible 1 Heating only Pump limitation Pump speed limitation 9 0D defines the maximum pump speed In normal conditions the default setting should NOT be modified The pump speed limitation will be overruled when the flow rate is in the range of the minimum flow error 7H In most cases instead of using 9 0D you can prevent flow noises by ...

Страница 176: ... capacity With this limitation range delta T is possible and the comfort is guaranteed During sampling operation the pump runs for a short time to measure the water temperatures which indicate if operation is required or not 5 90 pump speed during sampling 6 80 pump speed during sampling 7 70 pump speed during sampling 8 60 pump speed during sampling The maximum values depend on the unit type 9 0D...

Страница 177: ...ice or snow e g in cold region countries In heating operation the desired leaving water temperature is locally increased around an outdoor temperature of 0 C This compensation can be selected when using an absolute or a weather dependent desired temperature see illustration below Tt TA R L 0 C Tt TA R L 0 C a b a Absolute desired LWT b Weather dependent desired LWT Code Description 4 A D 03 Increa...

Страница 178: ...s Space heating cooling Additional zone Information 5 Tank Setpoint screen 5 1 Powerful operation 5 2 Comfort setpoint 5 3 Eco setpoint 5 4 Reheat setpoint 5 5 Schedule 5 6 Heat up mode 5 7 Disinfection 5 8 Maximum 5 9 Hysteresis 5 A Hysteresis 5 B Setpoint mode 5 C WD curve 5 D Margin 5 E WD curve type Tank setpoint screen You can set the domestic hot water temperature using the setpoint screen F...

Страница 179: ... one place The tank will heat up until the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfo...

Страница 180: ...heduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the operation manual for more details INFORMATION Risk of space heating capacity shortage for domestic hot water tank without internal booster heater In case of frequent domestic hot water operation frequent and long space heating cooling interruption will h...

Страница 181: ...that the domestic hot water temperature at the hot water tap will be equal to the value selected in field setting 2 03 after a disinfection operation When the high domestic hot water temperature can be a potential risk for human injuries a mixing valve field supply shall be installed at the hot water outlet connection of the domestic hot water tank This mixing valve shall secure that the hot water...

Страница 182: ...commended to program the start up of the disinfection function at least 4 hours later than the last expected large hot water tapping This start up can be set by installer settings disinfection function When the Schedule only mode is selected it is recommended to program an Eco action 3 hours before the scheduled start up of the disinfection function to preheat the tank INFORMATION Disinfection fun...

Страница 183: ...erature Code Description 5 A 6 08 Reheat hysteresis 2 C 20 C Setpoint mode Code Description 5 B N A Setpoint mode Fixed Weather dependent WD curve When weather dependent operation is active the desired tank temperature is determined automatically depending on the averaged outdoor temperature low outdoor temperatures will result in higher desired tank temperatures as the cold water tap is colder an...

Страница 184: ...red tank temperature Ta The averaged outdoor ambient temperature 0 0E low outdoor ambient temperature 40 C 5 C 0 0D high outdoor ambient temperature 10 C 25 C 0 0C desired tank temperature when the outdoor temperature equals or drops below the low ambient temperature 45 C 6 0E C 0 0B desired tank temperature when the outdoor temperature equals or rises above the high ambient temperature 35 C 6 0E ...

Страница 185: ...imum heat pump temperature 6 01 THP MAX 6 01 t 6 00 HP 5 10 20 30 40 43 45 TU THP OFF THP MAX TDHW THP ON 50 HP Heat pump If heating up time by the heat pump takes too long auxiliary heating by the backup heater can take place THP MAX Maximum heat pump temperature at sensor in domestic hot water tank THP OFF Heat pump OFF temperature THP MAX 6 01 THP ON Heat pump ON temperature THP OFF 6 00 TDHW D...

Страница 186: ...abled and clock format is set to 24 hours These settings can be changed during initial configuration or via the menu structure 7 2 User settings Time date Holiday About holiday mode During your holiday you can use the holiday mode to deviate from your normal schedules without having to change them While holiday mode is active space heating cooling operation and domestic hot water operation will be...

Страница 187: ...mode You can use quiet mode to decrease the sound of the outdoor unit However this also decreases the heating cooling capacity of the system There are multiple quiet mode levels The installer can Completely deactivate quiet mode Manually activate a quiet mode level Enable the user to program a quiet mode schedule If enabled by the installer the user can program a quiet mode schedule INFORMATION If...

Страница 188: ...4 2 Schedule For more information about scheduling see 11 4 3 Schedule screen Example 4139 Electricity prices and gas price Only applicable in combination with the bivalent function See also Bivalent 4211 Code Description 7 5 1 N A Electricity price High 7 5 2 N A Electricity price Medium 7 5 3 N A Electricity price Low 7 6 N A Gas price INFORMATION Electricity price can only be set when bivalent ...

Страница 189: ...nt About energy prices in case of an incentive per kWh renewable energy An incentive can be taken into account when setting the energy prices Although the running cost can increase the total operation cost taking into account the reimbursement will be optimized NOTICE Make sure to modify the setting of the energy prices at the end of the incentive period To set the gas price in case of an incentiv...

Страница 190: ... 8 Information Overview The following items are listed in the submenu 8 Information Installer settings User settings Tank Commissioning 8 Information 8 1 Energy data 8 2 Malfunction history 8 3 Dealer information 8 4 Sensors 8 5 Actuators 8 6 Operation modes 8 7 About 8 8 Connection status 8 9 Running hours 8 A Reset Dealer information The installer can fill in his contact number here Code Descrip...

Страница 191: ...ry 8 3 Dealer information Contact helpdesk number 8 4 Sensors Room temperature outside temperature leaving water temperature 8 5 Actuators Status mode of each actuator Example Unit pump ON OFF 8 6 Operation modes Current operation mode Example Defrost oil return mode 8 7 About Version information about the system 8 8 Connection status Information about the connection status of the unit the room th...

Страница 192: ...H Forced defrost 9 I Overview field settings 9 N Export MMI settings 9 P Bizone kit Configuration wizard After first power ON of the system the user interface will guide you using the configuration wizard This way you can set the most important initial settings This way the unit will be able to run properly Afterwards more detailed settings can be done via the menu structure if required To restart...

Страница 193: ... Menu structure setting 9 2 1 replaces the following 3 overview settings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of domestic hot water tank is installed In case of EKHWP we recommend to use the following settings Code Item EKHWP 9 2 1 E 07 Tank type 5 EKHWP HYC N A 4 05 Thermistor type 0 Automatic 5 8 6 0E Maximum tank...

Страница 194: ...t runs when the domestic hot water tank is being preheated No further settings are needed 4 Circulation and disinfection Combination of 2 and 3 It runs when the disinfection function of the domestic hot water tank is running or when the domestic hot water tank is being preheated No further settings are needed See also 6 4 4 DHW pump for instant hot water 445 6 4 5 DHW pump for disinfection 446 6 4...

Страница 195: ...1ph or 400V 3ph Code Description 9 3 2 5 0D 0 230V 1ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup heater with 2 steps If 2 steps the capacity of the second step depends on this setting It can also be chosen to have a higher capacity of the second step in emergency For a 3V model this is fixed to Re...

Страница 196: ...or temperature below which operation of the backup heater or external backup heat source in case of a bivalent system is allowed Range 15 C 35 C INFORMATION Applicable if 5 00 1 Above 10 C ambient temperature the heat pump will operate until 55 C Configuring a higher setpoint with an ambient temperature that is higher than the set equilibrium temperature will prevent the backup heater from assisti...

Страница 197: ...k schedule For more information see 11 4 3 Schedule screen Example 4139 Example Only allow the booster heater to operate during the night BSH eco timer Code Description 9 4 3 8 03 Booster heater delay timer Start up delay time for the booster heater when domestic hot water mode is active When domestic hot water mode is NOT active the delay time is 20 minutes The delay time starts from booster heat...

Страница 198: ...heater will not be allowed to operate when Ta 5 03 and 5 02 1 The domestic hot water temperature can be maximum the heat pump OFF temperature 9 4 4 4 03 1 Allowed Booster heater operation is allowed when required 9 4 4 4 03 2 Overlap The booster heater is allowed outside the operation range of the heat pump for domestic hot water operation Booster heater operation is only allowed if Ambient temper...

Страница 199: ...n the optional tank takes over the domestic hot water production When Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioning main menu screen and confirm whether the backup heater and or booster heater can take over the heat load or not Alternatively when Emergency is se...

Страница 200: ... heater to provide domestic hot water and space heating When this mode is activated Heat pump operation is NOT possible Cooling is NOT possible Code Description 9 5 2 7 06 Activation of the Compressor forced off mode 0 disabled 1 enabled Glycol filled system Glycol Filled system This setting gives the installer the possibility to indicate whether the system is filled with glycol or water This is i...

Страница 201: ... heater only Please do NOT change the default value Range 15 C 35 C 9 6 3 5 04 Offset BSH setpoint Setpoint correction for domestic hot water temperature setpoint correction for the desired domestic hot water temperature to be applied at low outdoor temperature when space heating priority is enabled The corrected higher setpoint will make sure that the total heat capacity of the water in the tank ...

Страница 202: ...tion Domestic hot water heating stops even when the target domestic hot water temperature is NOT reached The actual maximum running time also depends on setting 8 04 When Control Room thermostat This preset value is only taken into account if there is a request for space heating or cooling If there is NO request for space heating cooling the tank is heated until the setpoint has been reached When ...

Страница 203: ...ater pipe freeze prevention if glycol is used For more information on freeze protection by glycol see 8 2 4 To protect the water circuit against freezing 480 Benefit kWh power supply Code Description 9 8 2 D 00 Restriction Only applicable if 9 8 4 is NOT set to Smart grid Allow heater Which heaters are allowed to operate during preferential kWh rate power supply 0 No None 1 Only BSH Booster heater...

Страница 204: ...tart function 2 Closed The outdoor unit is connected to a preferential kWh rate power supply When the preferential kWh rate signal is sent by the electricity company the contact will close and the unit will go in forced off mode When the signal is released again the voltage free contact will open and the unit will restart operation Therefore always enable the auto restart function 3 Smart grid A S...

Страница 205: ...ricity meter 2 None Normally when a pulse meter is available the following happens The pulse meter measures the power produced by the photovoltaic panels The unit limits its power consumption during the Smart Grid s Recommended ON mode to only use the power provided by the photovoltaic panels However when the pulse meter is not available you can still limit the unit s power consumption using this ...

Страница 206: ...buffering the room will heat up or cool down to the comfort setpoint In case of tank buffering the tank will heat up to the maximum tank temperature The goal is to buffer the energy from the photovoltaic panels Therefore the capacity of the unit is limited to what the photovoltaic panels are providing If Smart Grid pulse meter is Then the limit is Available Decided by the unit based on the input o...

Страница 207: ...4 09 Type 0 Amp The limitation values are set in A 1 kW The limitation values are set in kW Limit when 9 9 1 Continuous and 9 9 2 Amp Code Description 9 9 3 5 05 Limit Only applicable in case of full time current limitation mode 0 A 50 A Limits when 9 9 1 Inputs and 9 9 2 Amp Code Description 9 9 4 5 05 Limit 1 0 A 50 A 9 9 5 5 06 Limit 2 0 A 50 A 9 9 6 5 07 Limit 3 0 A 50 A 9 9 7 5 08 Limit 4 0 A...

Страница 208: ... booster heater will be limited first before the backup heater is limited Note In case power consumption control is DISABLED for all models the setting 4 01 defines whether backup heater and booster heater can operate simultaneously or if the booster heater backup heater has priority over the backup heater booster heater In case power consumption control is ENABLED the setting 4 01 defines the pri...

Страница 209: ... pulse frequency output of each power meter in accordance with the power meter specifications It is possible to connect up to 2 power meters with different pulse frequencies If only 1 or no power meter is used select None to indicate the corresponding pulse input is NOT used Code Description 9 A 1 D 08 Electricity meter 1 0 None NOT installed 1 1 10kWh Installed 2 1 kWh Installed 3 10 kWh Installe...

Страница 210: ...s value has only meaning in room thermostat control Ext amb sensor offset ONLY applicable in case an external outdoor ambient sensor is connected and configured You can calibrate the external outdoor ambient temperature sensor It is possible to give an offset to the thermistor value This setting can be used to compensate for situations where the external outdoor ambient sensor cannot be installed ...

Страница 211: ...scription 9 C 1 C 02 Bivalent Indicates if the space heating is also performed by means of another heat source than the system 0 No Not installed 1 Yes Installed The auxiliary boiler gas boiler oil burner will operate in space heating when the outdoor ambient temperature is low During bivalent operation the heat pump will run in domestic hot water operation when tank heat up is required or is turn...

Страница 212: ...gnal for the auxiliary boiler is Drops below Tcalc Stops Active Rises above Tcalc 3 C Starts Inactive INFORMATION The permission signal for the auxiliary boiler is located on the EKRP1HBAA digital I O PCB When it is activated the contact X1 X2 is closed and open when it is deactivated See illustration below for the schematic location of this contact YC Y1 Y2 Y3 Y4 X1 X2 X3 X4 OFF ON X2M SS1 X1M Co...

Страница 213: ...3 Electricity and gas prices INFORMATION To set electricity and gas price values do NOT use overview settings Set them in the menu structure instead 7 5 1 7 5 2 7 5 3 and 7 6 For more information on how to set the energy prices see the operation manual and the user reference guide INFORMATION Solar panels If solar panels are used set the electricity price value very low to promote the use of the h...

Страница 214: ...upply failure the auto restart function reapplies the user interface settings at the time of the power failure Therefore it is recommended to always enable the function If the preferential kWh rate power supply is of the type that power supply is interrupted always enable the auto restart function Continuous hydro module control can be guaranteed independent of the preferential kWh rate power supp...

Страница 215: ...fter his work is done he can enable the protective functions by setting 9 G Disable protections No Code Description 9 G N A Disable protections 0 No 1 Yes Forced defrost Forced defrost Manually start a defrost operation Code Description 9 H N A Do you want to start a defrost operation Back OK NOTICE Forced defrost start up You can only start forced defrost when the heating operation has been runni...

Страница 216: ...ected storage device Back OK To export MMI settings 1 Insert a USB memory stick in the user interface 2 On the user interface go to 9 N Export MMI settings 3 Select OK 4 Remove the USB memory stick Bizone kit Bizone kit installed Code Description 9 P 1 E 0B Bizone kit installed 0 No The system only has a main zone 1 N A 2 Yes A bizone kit is installed in order to add an additional temperature zone...

Страница 217: ...c separator with direct pump d c b a a Indoor unit b Mixing station c Hydraulic separator d Direct pump Additional zone pump fixed PWM The speed of the additional zone pump can be fixed with this setting Code Description 9 P 3 7 0A Add zone pump fixed PWM Fixed pump speed for additional direct zone 20 95 default 95 Main zone pump fixed PWM The speed of the main zone pump can be fixed with this set...

Страница 218: ...25 11 6 10 Commissioning Overview The following items are listed in the submenu A Commissioning User profile Installer settings Information Operation A Commissioning A 1 Operation test run A 2 Actuator test run A 3 Air purge A 4 UFH screed dryout A 5 Pump down About commissioning See 12 Commissioning 4224 11 6 11 User profile B User profile See To change the user permission level 4124 B User profi...

Страница 219: ...ollowing items are listed in the submenu D Wireless gateway Malfunctioning Operation User profile Room D Wireless gateway D 1 Mode D 2 Reboot D 3 WPS D 4 Remove from cloud D 5 Home network connection D 6 Cloud connection About the WLAN cartridge The WLAN cartridge connects the system to the internet The user can then control the system via the ONECTA app This needs the following components b a c a...

Страница 220: ... D 1 N A Enable AP mode No Yes Reboot Reboot the WLAN cartridge Code Description D 2 N A Reboot the gateway Back OK WPS Connect the WLAN cartridge to the router Code Description D 3 N A WPS No Yes INFORMATION You can only use this function if it is supported by the software version of the WLAN and the software version of the ONECTA app Remove from cloud Remove the WLAN cartridge from the cloud Cod...

Страница 221: ...11 Configuration Installer reference guide 221 EBLA04 08E2V3 E23V3 EDLA04 08E2V3 E23V3 Daikin Altherma 3 M 4P685228 1A 2022 05 Code Description D 6 N A Cloud connection Not connected Connected ...

Страница 222: ...at Quiet Mode Schedule Level Restrictions 7 4 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 4 Space heating cooling Operation mode Operation mode schedule Room comfort setpoint 1 9 Room comfort setpoint Heating comfort setpoint Cooling comfort setpoint D Wireless gateway Mode Reboot WPS Remove from cloud Home network connection Cloud connection 2 Main zone Sche...

Страница 223: ...lent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installer settings Configuration wizard Domestic hot water Backup heater Booster heater Emergency Balancing Water pipe freeze prevention Benefit kWh power supply Power consumption control Energy meterin...

Страница 224: ...ed with protective functions such as room antifrost The unit automatically runs these functions when necessary During installation or service this behaviour is undesired Therefore the protective functions can be disabled At first power on The protective functions are disabled by default After 12 hours they will be automatically enabled Afterwards An installer can manually disable the protective fu...

Страница 225: ...during startup NOTICE ALWAYS operate the unit with thermistors and or pressure sensors switches If NOT burning of the compressor might be the result 12 3 Checklist before commissioning 1 After the installation of the unit check the items listed below 2 Close the unit 3 Power up the unit You read the complete installation instructions as described in the installer reference guide The outdoor unit i...

Страница 226: ...eck the water volume and flow rate in 8 1 Preparing water piping 471 if applicable The domestic hot water tank is filled completely 12 4 Checklist during commissioning The minimum flow rate is guaranteed in all conditions See To check the water volume and flow rate in 8 1 Preparing water piping 471 To perform an air purge To perform a test run To perform an actuator test run Underfloor screed dryo...

Страница 227: ...the position of the 3 way valve to Space or Tank Air purge must be performed for both space heating and tank domestic hot water circuits Automatic The unit automatically changes the pump speed and switches the position of the 3 way valve between the space heating and the domestic hot water circuit Typical workflow Purging the air from the system should consist of 1 Performing a manual air purge 2 ...

Страница 228: ...mission level 4124 2 Go to A 3 Commissioning Air purge 3 In the menu set Type Manual 4 Select Start air purge 5 Select OK to confirm Result The air purge starts It stops automatically when ready 6 During manual operation You can change the pump speed You must change the circuit To change these settings during the air purge open the menu and go to A 3 1 5 Settings Scroll to Circuit and set it to Sp...

Страница 229: ...to A 1 Commissioning Operation test run 3 Select a test from the list Example Heating 4 Select OK to confirm Result The test run starts It stops automatically when ready 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm INFORMATION If the outdoor temperature is outside the range of operation the unit may NOT operate or may NOT deliver the required capaci...

Страница 230: ...RMATION Make sure that all air is purged before executing the test run Also avoid disturbances in the water circuit during the test run Diverter valve test 3 way valve for switching between space heating and tank heating Bivalent signal test Alarm output test C H signal test DHW pump test 12 4 5 Underfloor heating screed dryout About underfloor heating screed dryout Purpose The underfloor heating ...

Страница 231: ... 1 Action step 1 2 Action step 2 Steps 1 Set the user permission level to Installer See To change the user permission level 4124 2 Go to A 4 2 Commissioning UFH screed dryout Program 3 Program the schedule To add a new step select the next empty line and change its value To delete a step and all steps below it decrease the duration to Scroll through the schedule Adjust the duration between 1 and 7...

Страница 232: ...d dryout schedule has been programmed See To program an underfloor heating screed dryout schedule 4231 Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the user permission level 4124 2 Go to A 4 Commissioning UFH screed dryout 3 Select Start UFH screed dryout 4 Select OK...

Страница 233: ...ryout To manually stop underfloor heating screed dryout 1 Go to A 4 3 Commissioning UFH screed dryout 2 Select Stop UFH screed dryout 3 Select OK to confirm Result The underfloor heating screed dryout is stopped Read out UFH screed dryout status When the program is stopped due to an error an operation switch off or a power failure you can read out the underfloor heating screed dryout status 1 Go t...

Страница 234: ...er setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what to do in case of problems Show the user what to do for the maintena...

Страница 235: ... performing maintenance at least once a year However applicable legislation might require shorter maintenance intervals In this chapter 14 1 Maintenance safety precautions 235 14 2 Yearly maintenance 235 14 2 1 Yearly maintenance outdoor unit overview 235 14 2 2 Yearly maintenance outdoor unit instructions 236 14 1 Maintenance safety precautions DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING ...

Страница 236: ...s correctly The water may be very hot Checkpoints are The water flow coming from the relief valve is high enough no blockage of the valve or in between piping is suspected Dirty water coming out of the relief valve open the valve until the discharged water does NOT contain dirt anymore flush the system It is recommended to do this maintenance more frequently Pressure relief valve of the domestic h...

Страница 237: ...orough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring Using an ohmmeter check if contactors K1M K2M K3M and K5M depending on your installation operate correctly All contacts of these contactors must be in open position when the power is turned OFF WARNING If the internal wiring is damaged it has to be replaced by the manufacturer its ...

Страница 238: ...problems based on error codes 245 15 4 1 To display the help text in case of a malfunction 245 15 4 2 Error codes of the unit 245 15 1 Overview Troubleshooting This chapter describes what you have to do in case of problems It contains information about Solving problems based on symptoms Solving problems based on error codes Before troubleshooting Carry out a thorough visual inspection of the unit ...

Страница 239: ...anually see To perform a manual air purge 4 228 or use the automatic air purge function see To perform an automatic air purge 4228 The water pressure is 1 bar The expansion vessel is NOT broken The resistance in the water circuit is NOT too high for the pump see the ESP curve If the problem persists after you have conducted all of the above checks contact your dealer In some cases it is normal tha...

Страница 240: ...at emitters As a result the water temperature will gradually rise Monitor the inlet water temperature and make sure it does NOT drop below 25 C If the problem persists after you have done all of the above checks contact your dealer The preferential kWh rate power supply settings and electrical connections do NOT match This should match with the connections as explained in 9 2 2 To connect the main...

Страница 241: ...We recommend to purge air with the air purge function of the unit to be performed by the installer If you purge air from the heat emitters or collectors mind the following WARNING Air purging heat emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that t...

Страница 242: ...is NOT broken The pre pressure setting of the expansion vessel is correct see 8 1 4 Changing the pre pressure of the expansion vessel 477 15 3 7 Symptom The pressure relief valve opens Possible causes Corrective action The expansion vessel is broken Replace the expansion vessel The water volume in the installation is too high Make sure that the water volume in the installation is below the maximum...

Страница 243: ...ns a backup heater The backup heater operation is not activated Check the following The backup heater operation mode is enabled Go to 9 3 8 Installer settings Backup heater Operation 4 00 The backup heater overcurrent circuit breaker is on If not turn it back on The thermal protector of the backup heater is NOT activated If it has check the following and then press the reset button in the switch b...

Страница 244: ...lief valve and the cold water inlet Replace the pressure relief valve 15 3 11 Symptom Tank disinfection function is NOT completed correctly AH error Possible causes Corrective action The disinfection function was interrupted by domestic hot water tapping Program the start up of the disinfection function when the coming 4 hours NO domestic hot water tapping is expected Large domestic hot water tapp...

Страница 245: ... malfunction the following will appear on the home screen depending on the severity Error Malfunction You can get a short and a long description of the malfunction as follows 1 Press the left dial to open the main menu and go to Malfunctioning Result A short description of the error and the error code is displayed on the screen 2 Press in the error screen Result A long description of the error is ...

Страница 246: ... 8H 01 Overheating mixed water circuit 8H 02 Overheating mixed water circuit thermostat 8H 03 Overheating water circuit thermostat A1 00 Zero cross detection problem A5 00 OU High pressure peak cut freeze protection problem AA 01 Backup heater overheated or BUH power cable not connected AC 00 Booster heater overheated AH 00 Tank disinfection function not completed correctly AJ 03 Too long DHW heat...

Страница 247: ...tch HPS H5 00 Malfunction of compressor overload protection H6 00 OU Malfunction of position detection sensor H8 00 OU Malfunction of compressor input CT system H9 00 OU Malfunction of outdoor air thermistor HC 00 Tank temperature sensor problem HC 01 Second tank temperature sensor problem HJ 10 Water pressure sensor abnormality J3 00 OU Malfunction of discharge pipe thermistor J6 00 OU Malfunctio...

Страница 248: ... voltage U3 00 Underfloor heating screed dryout function not completed correctly U4 00 Indoor outdoor unit communication problem U5 00 User interface communication problem U7 00 OU Transmission malfunction between main CPU INV CPU U8 02 Connection with room thermostat lost U8 03 No connection with room thermostat U8 04 Unknown USB device U8 05 File malfunction U8 06 MMI bizone kit communication pr...

Страница 249: ...peration If operation is Then the minimum required flow rate is Cooling 10 l min Heating 6 l min BUH operation 12 l min Heating defrost 12 l min DHW 25 l min INFORMATION If error 89 05 or 89 06 occurs check the minimum water volume during cooling INFORMATION Error AJ 03 is reset automatically from the moment there is a normal tank heat up INFORMATION If an U8 04 error occurs the error can be reset...

Страница 250: ... 08E2V3 E23V3 EDLA04 08E2V3 E23V3 Daikin Altherma 3 M 4P685228 1A 2022 05 INFORMATION A malfunctioning booster heater will have an impact on energy metering and power consumption control INFORMATION The user interface will display how to reset an error code ...

Страница 251: ...2 To pump down Example To protect the environment pump down when relocating the unit or when disposing of the unit DANGER RISK OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and there is a leak in the refrigerant circuit Do NOT use the unit s automatic pump down function with which you can collect all refrigerant from the system into the outdoor unit Possible conseq...

Страница 252: ...alve 3 Start the pump down operation via the user interface integrated in the indoor unit 1 Set the user permission level to Installer See To change the user permission level 4124 2 Go to A 5 Commissioning Pump down 3 Select Pump down 4 Select OK to confirm Result The pump down operation starts It stops automatically when done To stop the pump down operation manually 1 In the menu go to Stop pump ...

Страница 253: ...ical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required In this chapter 17 1 Piping diagram Outdoor unit 254 17 2 Wiring diagram Outdoor unit 256 17 3 ESP curve Outdoor unit 265 ...

Страница 254: ...n male 1 Thermistors hydro module b Drain valve water circuit R1T Outlet water heat exchanger c Expansion vessel R3T Refrigerant liquid side d Flow sensor R4T Inlet water e Plate heat exchanger f Backup heater Thermistors compressor module g Automatic air purge valve R1T Outdoor air h Safety valve R2T Air heat exchanger i Pump R3T Compressor discharge j Connection for optional flow switch k Liquid...

Страница 255: ...istors hydro module b Drain valve water circuit R1T Outlet water heat exchanger c Expansion vessel R3T Refrigerant liquid side d Flow sensor R4T Inlet water e Plate heat exchanger f Automatic air purge valve Thermistors compressor module g Safety valve R1T Outdoor air h Pump R2T Compressor discharge i Connection for optional flow switch R3T Compressor suction j Liquid stop valve k Filter Refrigera...

Страница 256: ...ranslation 1 Connection diagram 1 Connection diagram Outdoor Outdoor Hydro Hydro module 2 Notes 2 Notes Connection X1M Main terminal Earth wiring Field supply Option Wiring depending on model Switch box PCB Protective earth Field wire 3 Legend 3 Legend Optional Field supply A1P Hydro kit main PCB AL Connector C Capacitor DB Rectifier bridge DC Connector DP Connector E Connector F1U Fuse T 6 3 A 25...

Страница 257: ...r transistor IGBT R1T Thermistor air R2T Thermistor heat exchanger R3T Thermistor discharge RTH2 Resistor S Connector S1PH High pressure switch S2 80 Connector SA1 Surge arrestor SHM Terminal strip fixed plate U V W Connector V3 V4 V401 Varistor X A Connector X M Terminal strip Y1E Electronic expansion valve Y1S Solenoid valve 4 way valve Z C Noise filter ferrite core Z F Noise filter NOTES 1 When...

Страница 258: ... backup heater option For normal power supply standard For normal power supply standard For preferential kWh rate power supply outdoor For preferential kWh rate power supply outdoor Hydro SWB power supplied from compressor SWB Hydro switch box power supplied from compressor switch box Normal kWh rate power supply Normal kWh rate power supply SWB Switch box Use normal kWh rate power supply for hydr...

Страница 259: ...AN adapter A14P User interface PCB A15P Receiver PCB wireless ON OFF thermostat CN A4P Connector DS1 A8P DIP switch E P A9P Indication LED F1B Overcurrent fuse backup heater F2B Overcurrent fuse booster heater F1U F2U A4P Fuse 5 A 250 V for digital I O PCB K1A K2A High voltage Smart Grid relay K1M Contactor backup heater K3M Contactor booster heater K R A4P Relay on PCB M2P Domestic hot water pump...

Страница 260: ...P Selector switch TR1 Power supply transformer X4M Terminal strip booster heater power supply X8M Terminal strip power supply at client side X9M Terminal strip integrated backup heater power supply X10M Terminal strip Smart Grid power supply X X A X Y Connector X M Terminal strip Z C Noise filter ferrite core 5 Option PCBs 5 Option PCBs Alarm output Alarm output Changeover to ext heat source Chang...

Страница 261: ...w voltage Smart Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid For For Inrush Inrush current NO valve Normal open valve Only for LAN adapter Only for LAN adapter Optional for Optional for Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB Remote user...

Страница 262: ...ram For internal BUH option For models with integrated backup heater Hydro Hydro module Outdoor Outdoor SWB Hydro switch box 2 Notes 2 Notes X1M Terminal main X2M Terminal field wiring for AC X4M Terminal booster heater power supply X5M Terminal field wiring for DC X9M Terminal integrated backup heater power supply X10M Terminal Smart Grid Earth wiring Field supply 1 Several wiring possibilities O...

Страница 263: ...glish Translation K3M Contactor booster heater Q1DI Earth leakage circuit breaker TR1 Power supply transformer X4M Terminal strip booster heater power supply X6M Terminal strip power supply at client side X9M Terminal strip integrated backup heater power supply X10M Terminal high voltage Smart Grid X A Connector X M Terminal strip ...

Страница 264: ...al 2 core signal 2 core signal 2 core Flow switch signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS WLAN cartridge Optional part for EWA EWYA signal 2 core 3m included A14P P1 P2 user interface Only for remote user Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operat...

Страница 265: ... during Cooling operation E Minimum flow during Defrost and Backup heater operation With built in BUH 4D139365 0 40 80 60 20 30 70 50 10 A kPa B l min 0 5 10 15 20 25 30 35 40 C D E A External static pressure B Water flow rate C Minimum flow during normal operation D Minimum flow during Cooling operation E Minimum flow during Defrost and Backup heater operation Notes Selecting a flow outside the o...

Страница 266: ...roduct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories Labels m...

Страница 267: ... table Applicable indoor units EBLA04E23V3 EDLA04E23V3 EBLA06E23V3 EDLA06E23V3 EBLA08E23V3 EDLA08E23V3 EBLA04E2V3 EDLA04E2V3 EBLA06E2V3 EDLA06E2V3 EBLA08E2V3 EDLA08E2V3 Notes 1 EBLA 2 EDLA 3 23V3 4 2V3 4P685235 1 2022 03 ...

Страница 268: ... R O 2 0C 2 2 0C 2 37 70 step 1 C 65 C 2 0C 2 37 55 step 1 C 55 C 2 8 3 9 03 R W 5 18 C step 1 C 5 C 2 8 4 9 02 R W 18 22 C step 1 C 22 C Main zone 2 9 C 07 R W 0 Leaving water 1 External room thermostat 2 Room thermostat 2 A C 05 R W 1 1 contact 2 2 contacts Delta T 2 B 1 1 0B R W 2 0C 2 R O 2 0C 2 3 10 C step 1 C 2 0C 2 Radiator 5 C 2 0C 2 Radiator 10 C 2 B 2 1 0D R W 3 10 C step 1 C 5 C Cooling...

Страница 269: ...t 2 2 contacts Delta T 3 B 1 1 0C 2 0D 2 R W 2 0D 2 R O 2 0D 2 Radiator 3 10 C step 1 C 5 C 2 0D 2 Radiator 10 C 3 B 2 1 0E R W 3 10 C step 1 C 5 C Additional zone 3 C R O 0 2 points 1 Slope Offset Space heating cooling Operation range 4 3 1 4 02 R W 14 35 C step 1 C 22 C 4 3 2 F 01 R W 10 35 C step 1 C 20 C Space heating cooling 4 4 7 02 R W 0 Single zone 1 Dual zone 4 5 F 0D R W 0 Continuous 1 S...

Страница 270: ... C 80 C E 07 7 40 60 C step 1 C 60 C E 07 8 40 75 C step 1 C 75 C 5 9 6 00 R W 2 40 C step 1 C 8 C 5 A 6 08 R W 2 20 C step 1 C 10 C 5 B R W 0 Fixed 1 Weather dependent WD curve 5 C 0 0B R W 35 6 0E C step 1 C 55 C 5 C 0 0C R W Min 45 6 0E 6 0E C step 1 C 60 C 5 C 0 0D R W 10 25 C step 1 C 15 C 5 C 0 0E R W 40 5 C step 1 C 10 C Tank 5 D 6 01 R W 0 10 C step 1 C 2 C 5 E R O 0 2 points 1 Slope Offse...

Страница 271: ...ther dependent 9 1 5 4 R W 0 No 1 Yes 9 1 5 5 R W 0 2 points 1 Slope Offset 9 1 6 1 00 R W 40 5 C step 1 C 10 C 9 1 6 1 01 R W 10 25 C step 1 C 15 C 9 1 6 1 02 R W 9 01 9 00 step 1 C 2 0C 0 35 C 2 0C 1 45 C 2 0C 2 60 C 9 1 6 1 03 R W 9 01 min 45 9 00 C step 1 C 2 0C 0 25 C 2 0C 1 35 C 2 0C 2 40 C 9 1 7 1 06 R W 10 25 C step 1 C 20 C 9 1 7 1 07 R W 25 43 C step 1 C 35 C 9 1 7 1 08 R W 9 03 9 02 C s...

Страница 272: ...pump 1 Instant hot water 2 Disinfection 3 Circulation 4 Circulation and disinfection 9 2 4 D 07 R W 0 No 1 Yes DHW Back up heater 9 3 1 E 03 R O 3 R W 4 0 No heater 4 1 External heater 2 3V 3 9 3 2 5 0D R O 3 R W 4 0 230V 1 3 1 230V 3 2 400V 3 9 3 3 4 0A R W 0 1 1 1 1 2 2 1 2 3 1 2 1 1 2 in emergency 9 3 4 6 03 R W 0 10kW step 0 2kW 0kW 4 3kW 3 9 3 5 6 04 R W 4 R O 3 0 10kW step 0 2kW 0kW 3 9 3 6 ...

Страница 273: ...onsumption control 9 9 1 4 08 R W 0 No 1 Continuous 2 Inputs 3 Current Sensor 9 9 2 4 09 R W 0 Amp 1 kW 9 9 3 5 05 R W 0 50 A step 1 A 50 A 9 9 4 5 05 R W 0 50 A step 1 A 50 A 9 9 5 5 06 R W 0 50 A step 1 A 50 A 9 9 6 5 07 R W 0 50 A step 1 A 50 A 9 9 7 5 08 R W 0 50 A step 1 A 50 A 9 9 8 5 09 R W 0 20 kW step 0 5 kW 20 kW 9 9 9 5 09 R W 0 20 kW step 0 5 kW 20 kW 9 9 A 5 0A R W 0 20 kW step 0 5 kW...

Страница 274: ...1 C 55 C 9 I 0 0C R W Min 45 6 0E 6 0E C step 1 C 60 C 9 I 0 0D R W 10 25 C step 1 C 15 C 9 I 0 0E R W 40 5 C step 1 C 10 C 9 I 1 00 R W 40 5 C step 1 C 10 C 9 I 1 01 R W 10 25 C step 1 C 15 C 9 I 1 02 R W 9 01 9 00 step 1 C 2 0C 0 35 C 2 0C 1 45 C 2 0C 2 60 C Boiler efficiency Temperature Electricity meter 2 PV meter External sensor Ext amb sensor offset Averaging time Bivalent Hysteresis Alarm o...

Страница 275: ...5 C 9 I 3 09 R W 15 25 C step 0 5 1 C 15 C Leaving water value for high ambient temp for LWT main zone heating WD curve Weather dependent cooling of the main leaving water temperature zone Weather dependent cooling of the additional leaving water temperature zone Low ambient temp for LWT main zone cooling WD curve High ambient temp for LWT main zone cooling WD curve Leaving water value for low amb...

Страница 276: ... 9 I 6 09 0 9 I 6 0A R W 30 6 0E C step 1 C 60 C 9 I 6 0B R W 30 min 50 6 0E C step 1 C 45 C 9 I 6 0C R W 30 min 50 6 0E C step 1 C 45 C 9 I 6 0D R W 0 Reheat only 1 Schedule reheat 2 Schedule only What is the BUH operation mode Which electric heater has priority Below which outdoor temperature is heating allowed Operation permission of the booster heater Water pipe freeze prevention Emergency Whi...

Страница 277: ... C step 0 5 C 23 C Booster heater delay timer Additional running time for the maximum running time Domestic hot water booster heater hysteresis How many leaving water temperature zones are there Boiler efficiency HP forced OFF BBR16 activation BBR16 settings are only visible when the language of the user interface is set to Swedish Minimum running time for domestic hot water operation Additional z...

Страница 278: ... kWh 6 100 pulse kWh PV meter 7 1000 pulse kWh PV meter 9 I D 0A 2 9 I D 0B 2 9 I D 0C 0 9 I D 0D 0 9 I D 0E 0 9 I E 00 R O 0 5 2 Monobloc 9 I E 01 R O 0 9 I E 02 R W 1 R O 2 0 Reversible 1 1 Heating only 2 9 I E 03 R O 3 R W 4 0 No heater 4 1 External heater 2 3V 3 9 I E 04 R O 0 No 1 Yes 9 I E 05 R W 0 No 1 Yes 9 I E 06 1 Bivalent hysteresis temperature What is the thermo request contact type fo...

Страница 279: ...R W 0 Disabled 1 Enabled 9 I F 0A 0 9 I F 0B R W 0 9 I F 0C R W 1 9 I F 0D R W 0 Continuous 1 Sample 2 Request Bi zone kit settings 9 P 1 E 0B R W 0 not installed 1 2 Bizone kit installed 9 P 2 E 0C R W 0 Without hydraulic separator no direct pump 1 With hydraulic separator no direct pump 2 With hydraulic separator with direct pump 9 P 3 7 0A R W 20 95 step 5 95 9 P 4 7 0B R W 20 95 step 5 95 9 P ...

Страница 280: ...14 14 ...

Страница 281: ......

Страница 282: ......