6
|
Application guidelines
Installer reference guide
55
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
P
i
t
DI
a
b
P
i
Power input
t
Time
DI
Digital input (power limitation level)
a
Power limitation active
b
Actual power input
Setup and configuration
▪
No additional equipment needed.
▪
Set the power consumption control settings in [9.9] via the user interface (see
206]):
-
Select continuous limitation mode
-
Select the type of limitation (power in kW or current in A)
-
Set the desired power limitation level
6.6.2 Power limitation activated by digital inputs
Power limitation is also useful in combination with an energy management system.
The power or current of the entire Daikin system is limited dynamically by digital
inputs (maximum four steps). Each power limitation level is set via the user
interface by limiting one of the following:
▪
Current (in A)
▪
Power input (in kW)
The energy management system (field supply) decides the activation of a certain
power limitation level.
Example:
To limit the maximum power of the entire house
(lighting, domestic appliances, space heating…).
a
b
c
A
C
D
1
2
3
4
5
A8P
a
b
A
B
D
c
C
1
2
3
4
5
A8P
1
2
1
Models with integrated backup heater
2
With external backup heater kit
A
Outdoor unit
B
External backup heater kit
C
DHW tank
D
Energy management system
a
Power limitation activation (4 digital inputs)
b
Backup heater
c
Booster heater
Содержание EBLA04E2V3