11
|
Configuration
Installer reference guide
193
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
#
Code
Description
[9.2.1]
[E‑05]
(a)
[E‑06]
(a)
[E‑07]
(a)
▪
No DHW
No tank installed.
▪
EKHWS/E, small volume
Tank with booster heater installed at the side of
the tank, with a volume of 150 l or 180 l.
▪
EKHWS/E, big volume
Tank with booster heater installed at the side of
the tank, with a volume of 200 l, 250 l or 300 l.
▪
EKHWP/HYC
Tank with optional booster heater installed at
the top of the tank.
▪
3rd party, small coil
Third-party tank with a coil size larger than
1.05 m².
▪
3rd party, big coil
Third-party tank with a coil size larger than
1.80 m².
(a)
Use the menu structure instead of the overview settings. Menu structure setting [9.2.1]
replaces the following 3 overview settings:
•
[E-05]: Can the system prepare domestic hot water?
•
[E-06]: Is a domestic hot water tank installed in the system?
•
[E-07]: What kind of domestic hot water tank is installed?
In case of EKHWP, we recommend to use the following settings:
#
Code
Item
EKHWP
[9.2.1]
[E‑07]
Tank type
5:
EKHWP/HYC
N/A
[4-05]
Thermistor type
0: Automatic
[5.8]
[6-0E]
Maximum tank
temperature
≤70°C
In case of EKHWS*D* / EKHWSU*D*, we recommend to use the following settings:
#
Code
Item
EKHWS*D* / EKHWSU*D*
150/180
200/250/300
[9.2.1]
[E‑07]
Tank type
0:
EKHWS/E,
small volume
3:
EKHWS/E, big
volume
N/A
[4-05]
Thermistor type
0: Automatic
[5.8]
[6-0E]
Maximum tank
temperature
≤60°C
≤75°C
In case of a third-party tank, we recommend to use the following settings:
#
Code
Item
Third-party tank
Coil≥1.05 m²
Coil≥1.8 m²
[9.2.1]
[E‑07]
Tank type
7:
3rd party,
small coil
8:
3rd party,
big coil
N/A
[4-05]
Thermistor type
0: Automatic