Technical Data
46
Technical Data
Supply voltage to EN 60038
AC 230 V
10 %
Power consumption
Max. 8 W
Switching capacity of the relays
AC 250 V 2 (2) A
Maximum current on terminal L1'
10 A
Enclosure to EN 60529
IP40
Safety class II to EN 60730-1
Totally insulated
Switch panel installation in acc. with
DIN IEC 61554
Recess 138 x 92
Power reserve of the timer
at least 10 hours
Permitted room temperature
during operation
0 to 50 °C
Permitted room temperature
during storage
- 20 to 60 °C
Permissible humidity non condensing
95 % r.H.
Sensor resistances
Tolerance of the resistor
Temperature tolerance
Tolerance of the resistor
Temperature tolerance
Tolerance of the resistor
NTC 5 k
(AF, KF, SPF, VF)
+/- 1 % at 25 °C
+/- 0.2 K at 25 °C
PTC 1010
(AFS, KFS, SPFS, VFAS)
+/- 1 % at 25 °C
+/- 1.3 K at 25 °C
PT1000 sensor with 1 k
+/- 0,2 % at 0 °C