Installation
Sensors
17
Sensors
Outside sensor AF (AFS)
S
Order no. AF, 5 k
Ω
: 99 679 030
Order no. AFS, 1 k
Ω
: 99 679 001
Scope of supply
Outside sensor, screw and dowel
Installation location:
Wherever possible, on a northerly or north-easterly
wall behind a heated room
Approx. 2.5 m above ground
Not above windows or ventilation shafts
Installation:
Pull cover off sensor.
Fasten sensor with enclosed screw
Connect
electrically
Immersion sensor KF (KFS)
H
/SPF (SPFS)
F
Order no. KF/SPF, 5 k
Ω
, 3 m, ø 6.0x50: 99 676 769
Order no. KFS/SPFS, 1 k
Ω
, 3 m, ø 6.0x50: 99 676 682
Installation location:
In the immersed pipe of the hot-water cylinder tank
(generally on the front face of the tank)
Installation:
Slide the sensor as far as possible into
the immersed pipe.
!
The immersed sleeve must be dry.
Connect
electrically
Strap-on sensor VF (VFAS)
v
Order no. VF, 5 k
Ω
, 3 m, ø 6.0x50: 99 679 073
Order no. VFAS, 1 k
Ω
, 3 m, ø 6.0x50: 99 679 051
Scope of supply
Flow sensor, thermal compound, retaining strap, pressure
cap
Installation location:
In the case of boiler control instead of the boiler sensor
KF as close as possible behind the boiler on the heat-
ing flow pipe
In the case of mixer operation
v
approx. 0.5 m behind
the circulation pump
Installation:
Thoroughly clean the flow pipe.
Apply heat conductive paste (A)!!
Secure sensor with stretch band.
Connect
electrically
!
Only sensor of one type may be used