Input of the basic setting
Changing set values
21
Changing set values
The operating flap must be opened first in order to change
or request set values.
=> Controller switches to Operation mode
a
Display indicating the current level
b
Holes to unlock the controller fixation.
Insert a thin screwdriver deep into the holes and
then lift up the controller.
Operating elements
Ç
A => Shaft encoder
Search for value/level or adjust value
Ä
B => Programming key
Select a value level
Select a value level to change
Save a new value
C => Change display
LED ON => The value in the display can be changed by
actuating the shaft encoder (A).
x
F
D => Manual-Automatic switch.
In Manual mode, all the pumps and first burner stage are
switched on. The mixers are not changed/accessed.
(“DISPLAY EMERGENCY OPERATION”).
Limitation (switch-of with 5 K hysteresis):
Burner => MAX T-MODULE (expert)
Heating circuit pumps => MAX T-FLOW (expert)
Cylinder charging pump => DHW-TEMP I (user)
E
Caution, overheating, e.g. with floor or wall heating! =>
Set mixer by hand!
E => PC connection via optical adapter