Remote controls
Installation
14
Installation location:
In reference/main living room of the heating circuit
(on an inside wall of the room).
Not in the vicinity of radiators or other heat dissipating
units.
Any, if the room sensor influence is switched off.
Installation:
Remove cap from underside of pedestal.
Secure the base at the installation location.
Connect the electrical connection cables.
Press the cap back on.
Sensor resistances FBR
DCF receiver
Electrical connection: Connector VII; Terminal 1, 2
The controller can evaluate a eBUS DCF receiver on the
eBUS FA-Terminals.
If the DCF receiver is connected, the controller time is up-
dated as soon as the DCF transmits a valid time on the
BUS.
If the time has not been corrected after max. 10 min, select
a different place of installation for the DCF (e.g. another
wall - not in proximity to TV devices, monitors or dimmers).
PC
All system-specific parameters can be set and interrogated
using the
C
omfort
S
oft
parameterisation software. The pa-
rameters can be saved, displayed graphically and evaluat-
ed on the PC at predefined intervals. T connect to a PC
you need the optical adapter or CoCo PC active, which al-
so supports the sending of error messages by SMS and
the remote interrogation of controller data.
Temperature FBR1
terminals 1-2
switch in posi-
tion
q
FBR2
terminals 1-2
Room sensor
+10 °C
680
Ω
9950
Ω
+15 °C
700
Ω
7855
Ω
+20 °C
720
Ω
6245
Ω
+25 °C
740
Ω
5000
Ω
+30 °C
760
Ω
4028
Ω