Installation level
Input of the basic setting
24
Installation level
Installation level
All the values in this level must be entered in sequence
without interruption
Ä
Open level,
Ç
adjust value,
Ä
save value and activate
next value
GERMAN Set
language
TIME
Set current time:
1. Minute =>
Ä
=> 2. Hour
YEAR
Set current date
MONTH
Set current date
DAY
Set current date
See following pages for continuation
Commissioning procedure
1. Please read this guide carefully before commissioning
2. Fit controller, make electrical connections and switch on
boiler and supply voltage
3. Wait until standard display appears on controller
4. Open hinged operating cover
When the hinged operating flap is opened for the first time after
switching on, the "SETUP" is shown on the display.
5.
Ä
Start SETUP
6.
Ç
Set 1. value
7.
Ä
Save value and next value ...
8. Close hinged operating flap (end of SETUP)
9. Move program switch to required operating mode, e.g. au-
tomatic 1 (see page 19)
Installation (selecting basic controller functions)
This set value can be used to pre/set the other values of the
start-up level. The following basic functions may be pre-
selected (also see system description page 32).
If the selection of set value INSTALLATION always displays “-
---“ = no pre-selection => values retain their previously defined
status (values on delivery: E8.0634 2-stage burner; Hot water
preparation two mixed heating circuits).
01 = E8.4034 => Cascade controller for modulating HS
02 = E8.4834 => Cascade controller for switching HS
03 = E8.3611 => 0 - 10 V Controller
04 = E8.0634 => Standard controller with 2-stage HS
05 = 2HS controller => 2 HS cascade switched via relay
06 = E8.6644 => (no function in V1)
Installation level
Designation Value
range
Default
IV
INSTALLATION
----, 01 - 06
----
BUS-ID HS
----, 01 - 08
----
HS 1 TYPE
00 - 06
01
HS1 BUS
00 - 05
00
HS 2 TYPE
00 - 05
00
STORAGE HS2
00 - 03
00
BUFFER
00, 01, 02
00
HC FUNCTION
D
1
00, 01, 03
00
HC FUNCTION
D
2
00 - 04
00
CAP/STAGE
00 - 9950 kW
00 kW
See following pages for continuation