E8.5064 V1
System Manager
Installation Manual
Please observe the safety instructions and read through this manual carefully before commissioning the equipment.
Страница 1: ...E8 5064 V1 System Manager Installation Manual Please observe the safety instructions and read through this manual carefully before commissioning the equipment ...
Страница 2: ...rsons using it are at put at risk of fatal or serious injury electric shock Ensure the controller is de energized prior to performing any work on the controller Safety Please read and keep in a safe place Please read through these instructions care fully before installing or operating Following the installa tion pass the instructions on to the operator Warranty conditions If the system is not inst...
Страница 3: ...mity We the manufacturer declare the product E8 5064 is in conformity with the fundamental requirements of the follow ing directives and standards Directives 2004 108 EC 2006 95 EC Standards EN 60730 1 EN 60730 2 9 The manufacture is subject to the quality management system in accordance with DIN EN ISO 9001 Function The device contains a number of functions and must be set in accordance with use ...
Страница 4: ...ensor resistances FBR 14 DCF receiver 14 PC 14 Maximum delimiter 15 Telephone switch 15 Sensor values characteristic curve 16 Sensors 17 Outside sensor AF AFS S 17 Immersion sensor KF KFS H SPF SPFS F 17 Strap on sensor VF VFAS v 17 System bus 18 The heating system 18 Bus ID 18 Input of the basic setting 18 Operation in normal mode 18 Operating elements 18 Ç Operating mode selection 19 Effect of t...
Страница 5: ...ng temperature relay MF1 28 MF 1 HYST hysteresis relay MF1 28 F15 FUNCTION sensor function F15 31 BUS ID heating circuit number 31 5 K SENSORS 1 K SENSORS 31 Choice of installation 32 Schematic circuit diagrams hydraulic system 32 Installation 01 E8 4034 Cascade controller for modulating HS 32 Terminal assignment 33 Installation 02 E8 4834 Cascade controller for switching HS 34 Terminal assignment...
Страница 6: ...right hand side of the unit a Pull the mounting clamp at the low away from the con troller wall toothing b In this condition slide the mounting clamp down or up until the distance from the edge of the unit corre sponds to the thickness of the control panel wall Detent position 1 0 5 1 0 mm wall thickness Detent position 5 5 0 mm wall thickness c Press the mounting clamp against the controller wall...
Страница 7: ...be laid separately away from mains cables After connecting or modifying the connections of sensors and remote controls the controller must be briefly switched off mains switch fuse The function of the controller is reconfigured in accordance with the connected sensors the next time the controller is switched on Note for installation in connection with digital room device When installing a digital ...
Страница 8: ...Electrical Connection Installation 8 Connection diagram 230 V Relay switching capacity 2 2 A 250 V ...
Страница 9: ...II 1 2 F15 0 10V input light sensor Room sensor for heating circuit 2 III 2 3 F17 Pulse counter for output measurement IX 1 2 Data line CAN bus IX 3 4 Power supply CAN bus Mains II 1 Neutral conductor mains II 2 Power supply unit II 3 Power supply relay II 4 A1 Pump heating circuit 1 II 5 A1 Pump heating circuit 2 II 6 A3 Cylinder charging pump II 7 A4 Mixer motor heating circuit 2 on II 8 A5 Mixe...
Страница 10: ...L1 Power supply unit L1 Power supply to relay D 1 heating circuit pump HC 1 D 2 heating circuit pump HC 2 F Storage tank charging pump v Mixer open heating circuit 2 v Mixer closed heating circuit 2 H Burner stage 1 H Burner stage 1 H Burner stage 2 HS2 H Burner stage 2 HS2 v Mixer heating circuit 1 open Multifunction relay 1 v Mixer heating circuit 1 close Multifunction relay 2 Collector pump 2 S...
Страница 11: ... 1 room sensor Pin 3 Buf stor tank top sensor FBR heating circuit 1 set value Pin 4 Flow sensor heating circuit 2 ground Pin 5 Flow sensor heating circuit 2 Pin 6 Waste water sensor Pin 7 Waste water and boiler sensor ground Pin 8 Boiler sensor Pin 9 Outdoor sensor Pin 10 Outdoor sensor ground Pin 1 Flow sensor heating circuit 1 sensor multifunction 1 Pin 2 Service water low sensor sensor multifun...
Страница 12: ...Connector 9 IX H L Pin 1 FBR heating circuit 2 room sensor 0 10 V IN Light Pin 2 FBR heating circuit 2 ground Pin 3 FBR heating circuit 2 set value Pulse counter for output measurement CAN Bus Pin 1 H Data CAN Bus Pin 2 L Data CAN Bus Pin 3 ground Gnd CAN Bus Pin 4 12 V supply ...
Страница 13: ...ters Entry of the heating circuit parameters Room temperature control Automatic adaptation of the heat slope not Lago FB Remote control FBR2 Electrical connection HC1 Connector I 2 Ground and 3 or HC2 Connector III 1 3 Rotating switch for modifying room temperature setting Adjusting range 5 K Room control via the integrated room sensor Rotating switch for selecting operating mode i Standby OFF fro...
Страница 14: ...ontroller time is up dated as soon as the DCF transmits a valid time on the BUS If the time has not been corrected after max 10 min select a different place of installation for the DCF e g another wall not in proximity to TV devices monitors or dimmers PC All system specific parameters can be set and interrogated using the ComfortSoft parameterisation software The pa rameters can be saved displaye...
Страница 15: ...connection dia gram are used for installation As soon as a short circuit between terminal 3 of the FBR and ground FBR terminal 2 is detected the assigned heating circuit is switched to heating mode Additionally the hot water preparation is ac tivated only for controllers with hot water preparation When the short circuit is eliminated the controller once again heats on the basis of the set heating ...
Страница 16: ...422 120 C 194 1936 1460 5 kOhm NTC AF KF SPF VF 1 kOhm PTC AFS KFS SPFS VFAS The controller can be operated with 5 kOhm NTC stand ard or 1 kOhm PTC sensors The sensor type is selected in the start up level during start up The start up level is displayed when the operating cover is opened after the supply voltage has been switched on once only It can be reactivated again by briefly switching the su...
Страница 17: ...mersed pipe of the hot water cylinder tank generally on the front face of the tank Installation Slide the sensor as far as possible into the immersed pipe The immersed sleeve must be dry Connect electrically Strap on sensor VF VFAS v Order no VF 5 kΩ 3 m ø 6 0x50 99 679 073 Order no VFAS 1 kΩ 3 m ø 6 0x50 99 679 051 Scope of supply Flow sensor thermal compound retaining strap pressure cap Installa...
Страница 18: ...Heating circuit numbers 00 15 may not be assigned twice Heating circuit numbers 00 and 01 may not be used simultaneously The heating circuits are sequentially numbered starting with 01 Please only use heating circuit number 00 for re placement controllers if 00 was used in the replaced controller Pre settings Heating circuit 1 01 Heating circuit 2 02 After setting all the bus ID s the system must ...
Страница 19: ...R Summer mode Heating OFF HW according to HW program W Service automatic reset after 15 min Boiler regulates to boiler target temperature maximum boiler temperature When the boiler temperature has reached 65 C the consumers are regulated to their max imum flow temperature to dissipate heat cooling function The cooling function must be explicitly enabled in the consumer circuits by means of a set v...
Страница 20: ...efer to DISPLAY SEL parameter C DCF reception OK only if receiver is connected via eBUS D Bus icon if this icon does not appear check data line to connected CAN controllers check eBUS via DISPLAY level E Display of the active heating program for the first heating circuit here 6 00 to 08 00 hrs and 16 00 to 22 00 hrs F Status display H internal burner 1 relay ON D heating mode F hot water preparati...
Страница 21: ...djust value Ä B Programming key Select a value level Select a value level to change Save a new value C Change display LED ON The value in the display can be changed by actuating the shaft encoder A x F D Manual Automatic switch In Manual mode all the pumps and first burner stage are switched on The mixers are not changed accessed DISPLAY EMERGENCY OPERATION Limitation switch of with 5 K hysteresis...
Страница 22: ...es you to the display and indicator area The current area DISPLAY appears in the display for a short time 1 clock circuit After the clock circuit the display switches to the cur rent operating level SETUP This is displayed for a short time 1 clock circuit when you switch to a new area Ç Select the level in which the value to be adjusted or displayed can be found using the rotary knob Ä Press Prog ...
Страница 23: ...are protected by a code no damage malfunction possible Expert FA only for FA via BUS Summary of values transmitted by the automatic firing de vice Levels The settings in the different areas are sorted into operating levels INSTALLATION Hot water Heating circuit I Heating circuit II Solar MF Installation All display values and settings that relate to the heat gen erator or the entire system and can...
Страница 24: ...TUP 9 Move program switch to required operating mode e g au tomatic 1 see page 19 Installation selecting basic controller functions This set value can be used to pre set the other values of the start up level The following basic functions may be pre selected also see system description page 32 If the selection of set value INSTALLATION always displays no pre selection values retain their previousl...
Страница 25: ...ture only for HS 1 TYPE 01 02 or 03 Burner relays are controlled in parallel Cooler KF F8 must be connected 05 0 10 V Preset Modulation degree only for HS 1 TYPE 02 HS 2 TYPE secondary heat generator type HS A7 For HS1 with 2 stage burner not active 00 No secondary heat generator 01 Solid fuel boiler function see STORAGE HS2 02 no function in V1 03 no function in V1 04 Collector pump 05 Pump for H...
Страница 26: ...to connect a FBR for heating circuit 1 00 no buffer storage for heating operation 01 Buffer storage for heating operation F1 F3 Sensor switching in V1 no other function 02 Combination storage tank for heating and HW opera tion Sensor switching in V1 no other function HC FUNCTION heating circuit function selection If this parameter is modified the controller is restarted RESET briefly appears in th...
Страница 27: ...the return return flow temperature increase Mixer motor CLOSED heating circuit return is passed through When the mixer motor is open it must be ensured that there is circulation through the boiler boiler pump CAP STAGE boiler output for each stage Display of the HS number and the stage Selection with Prog button Input Adjustment of HS output Stage Boiler not available 0 Stage Boiler not active In ...
Страница 28: ...tarting from 20 only If a further sensor is required for a function this sensor must be con nected as F17 connector III Pin 2 3 The functions that may be selected for the MF relays 1 4 are described using MF relay 1 as an example RELAY FUNC 1 function selection relay MF1 T MF1 SETP switching temperature relay MF1 MF 1 HYST hysteresis relay MF1 00 No MF function 01 Header pump ON When heat is reque...
Страница 29: ...nutes Switching on takes place on the edge once only The set circulation program and the Circulation with hot water setting have an overriding function Switching on only takes place during enable periods 22 Solid fuel boiler integration e g in connection with 2 stage HS T MF1 or 1 4 Temperature of the solid fuel boiler T BUFFER B Temperature of buffer storage in the infeed area F1 ON T MF1 T BUFFE...
Страница 30: ...RN 1 T MF1 SETP MF 1 HYST The return flow temperature increase pump is switched on if the return flow temperature drops below the temperature setting limit T MF1 SETP It is switched off again when the return flow temperature exceeds the temperature set ting limit by the Hysteresis MF 1 HYST 25 Return flow temperature increase HS2 T RETURN 2 Return temperature of system ON T RETURN 2 T MF1 SETP OFF...
Страница 31: ... the 0 10 V output that applies Any changes such as those relating to external heating circuits hot water preparation or the frost protection function are ignored The operating mode switch also has no effect on the burner requirement only on the internal and external determination of requirement and distribution Heating circuit Sensors Designation Value range Default IV BUS ID 1 00 15 01 BUS ID 2 ...
Страница 32: ...diagrams hydraulic system Choic 32 Choice of installation Schematic circuit diagrams hydraulic system Installation 01 E8 4034 Cascade controller for modulating HS Alternatively Isolating circuit for hot water preparation ...
Страница 33: ...mp VIII 2 optional F14 Multifunction relay sensor 4 PT1000 but not if circulation time applies III 1 3 optional FBR2 FBR1 for heating circuit 2 IX 1 2 Data line CAN bus IX 3 4 Power supply CAN bus Mains II 1 Neutral conductor mains II 2 Power supply unit II 3 Power supply relay II 4 A1 Pump heating circuit 1 II 5 A1 Pump heating circuit 2 II 6 A3 Cylinder charging pump II 7 A4 Mixer motor heating ...
Страница 34: ...Schematic circuit diagrams hydraulic system Choic 34 Installation 02 E8 4834 Cascade controller for switching HS Alternatively Isolating circuit for hot water preparation ...
Страница 35: ...l F14 Multifunction relay sensor 4 PT1000 but not if circulation time applies III 1 3 optional FBR2 FBR1 for heating circuit 2 IX 1 2 Data line CAN bus IX 3 4 Power supply CAN bus Mains II 1 Neutral conductor mains II 2 Power supply unit II 3 Power supply relay II 4 A1 Pump heating circuit 1 II 5 A1 Pump heating circuit 2 II 6 A3 Cylinder charging pump II 7 A4 Mixer motor heating circuit 2 on II 8...
Страница 36: ...Schematic circuit diagrams hydraulic system Choic 36 Installation 03 E8 3611 0 10 V Controller ...
Страница 37: ...1000 but not if circulation time applies VIII 2 optional F14 Multifunction relay sensor 4 PT1000 III 1 3 optional FBR2 FBR1 for heating circuit 2 IX 1 2 Data line CAN bus IX 3 4 Power supply CAN bus Mains II 1 Neutral conductor mains II 2 Power supply unit II 3 Power supply relay II 4 A1 Pump heating circuit 1 II 5 A1 Pump heating circuit 2 II 6 A3 Cylinder charging pump II 7 A4 Mixer motor heatin...
Страница 38: ...Schematic circuit diagrams hydraulic system Choic 38 Installation 04 E8 0634 Standard controller with 2 stage HS ...
Страница 39: ...4 Multifunction relay sensor 4 PT1000 but not if circulation time applies III 1 3 optional FBR2 FBR1 for heating circuit 2 IX 1 2 Data line CAN bus IX 3 4 Power supply CAN bus Mains II 1 Neutral conductor mains II 2 Power supply unit II 3 Power supply relay II 4 A1 Pump heating circuit 1 II 5 A1 Pump heating circuit 2 II 6 A3 Cylinder charging pump II 7 A4 Mixer motor heating circuit 2 on II 8 A5 ...
Страница 40: ...Schematic circuit diagrams hydraulic system Choic 40 Installation 05 2HS controller 2 HS cascade switched via relay ...
Страница 41: ...ater tank lower III 1 3 optional FBR2 FBR1 for heating circuit 2 IX 1 2 Data line CAN bus IX 3 4 Power supply CAN bus Mains II 1 Neutral conductor mains II 2 Power supply unit II 3 Power supply relay II 4 A1 Pump heating circuit 1 II 5 A1 Pump heating circuit 2 II 6 A3 Cylinder charging pump II 7 A4 Mixer motor heating circuit 2 on II 8 A5 Mixer motor heating circuit 2 to II 9 10 A6 HS 1 VI 1 2 A7...
Страница 42: ... ID used The set bus ID is already in use by another device More than 1 Time Master in the sys tem E 200 Communication error HS1 E 201 Communication error HS2 E 202 Communication error HS3 E 203 Communication error HS4 E 204 Communication error HS5 E 205 Communication error HS6 E 206 Communication error HS7 E 207 Communication error HS8 Internal error E 81 EEPROM error The invalid value has been r...
Страница 43: ... unit Room temperature displayed and current room temperature setting blanked out see Display heating circuit In mixer motor expansion controllers with connection to Boiler controller Outside temperature and boiler tem perature display see Display Installation Control unit Room temperature displayed and current room temperature setting blanked out see Display heating circuit In case of communicati...
Страница 44: ...inimum boiler temperature and type of minimum delimiter Protect from corrosion Burner will not switch on Check boiler temperature setting The temperature set ting must be greater than the boiler temperature Check operating mode Standard F test B With solar check burner blocking ...
Страница 45: ...Dimensions 45 Dimensions ...
Страница 46: ... DIN IEC 61554 Recess 138 x 92 Power reserve of the timer at least 10 hours Permitted room temperature during operation 0 to 50 C Permitted room temperature during storage 20 to 60 C Permissible humidity non condensing 95 r H Sensor resistances Tolerance of the resistor Temperature tolerance Tolerance of the resistor Temperature tolerance Tolerance of the resistor NTC 5 k AF KF SPF VF 1 at 25 C 0 ...
Страница 47: ...designation for the heating boiler It may also be a buffer storage tank however Mixed heating circuit Mixer circuit In the mixed heating circuit a three way valve is used to add cooled water from the return flow to the hot flow water The flow temperature is thus reduced This is important for Underfloor heating systems for example because they must only be operated with low flow temperatures Heatin...
Страница 48: ...rom Elster GmbH We reserve the right to make technical modifications in the interests of progress Elster GmbH Geschäftssegment Comfort Controls Kuhlmannstraße 10 31785 Hameln www kromschroeder de EN 0415 6 6701 903 14 Printed in Germany Subject to modification Malfunctions due to improper operation or settings are not cov ered by the warranty ...