PRODUCT DESIGN
23
v
V
X
DIRECT VENT TERMINAL CLEARANCES
1
In accordance with the current
CSA B149.1, Natural Gas and Propane Installation Code.
2
In accordance with the current
ANSI Z223.1/NFPA 54, National Fuel Gas Code.
†
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single fanily dwellings and serves
both dwellings.
‡
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*
For clearances not specified in
ANSI Z223.1/NFPA 54
or
CSA B149.1
, the following statement shall be included:
“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instruction.”
Canadian Installations
1
U.S. Installations
2
I=
Clearance to service
regulator vent outlet.
3 ft. (91 cm).
*
J=
Clearance to nonmechanical air
supply inlet to building or the
combustion air inlet to any other
appliance.
6 in. (15 cm) for appliances 10,000
Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30 kW).
6 in. (15 cm) for appliances 10,000
Btuh (3 kW), 9 in. (23 cm) for
appliances > 10,000 Btuh (3kW) and
50,000 Btuh (15 kW), 12 in. (30 cm) for
appliances > 50,000 Btuh (15 kW).
K= Clearance to a mechanical
air supply inlet.
6 ft. (1.83 m)
3 ft. (91 cm) above if within
10 ft. (3 m) horizontally.
L= Clearance above paved sidewalk or
paved driveway located on public
property.
7 ft. (2.13m) †
*
M= Clearance under veranda, porch,
deck or balcony.
12 in. (30 cm) ‡
*
Canadian Installations
1
U.S. Installations
2
A= Clearance above grade,
veranda, porch, deck or
balcony. (See 1.24.6-i(9)b.)
12 in. (30 cm)
12 in. (30 cm)
B= Clearance to window or
door that may be opened.
6 in. (15 cm) for appliances
10,000 Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3 kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30
kW).
6 in. (15 cm) for appliances
10,000 Btuh (3 kW), 9 in. (23 cm) for
appliances > 10,000 Btuh (3 kW) and
50,000 Btuh (15 kW), 12 in. (30 cm) for
appliances > 500,000 Btuh (15 kW).
C= Clearance to permanently
closed window.
*
*
D= Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal.
*
*
E= Clearance to unventilated soffit.
*
*
F= Clearance to outside corner.
*
*
G= Clearance to inside corner.
*
*
H= Clearance to each side of center
line extended above meter/regulator
assembly.
3 ft. (91 cm) within a height 15 ft.
(4.5 m) above the meter/regulator
assembly.
*
OTHER THAN DIRECT VENT TERMINAL CLEARANCES
1
In accordance with the current
CSA B149.1, Natural Gas and Propane Installation Code.
2
In accordance with the current
ANSI Z223.1/NFPA 54, National Fuel Gas Code.
†
A vent shall not terminate directly above a sidewalk or paveable driveway that is located between two single family dwellings and
serves both dwelling.
‡
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*
For clearances not specified in
ANSI Z223.1/NFPA 54
or
CSA B149.1
, the following statement shall be included:
“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instruction.”
Canadian Installations
1
U.S. Installations
2
I=
Clearance to sevice
regulator vent outlet.
3 ft. (91 cm).
*
J= Clearance to nonmechanical air
supply inlet to building or the
combustion air inlet to any other
appliance.
6 in. (15 cm) for appliances 10,000
Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30 kW).
4 ft. (1.2 m) below or to side of
opening; 1 ft. (300 m) above opening.
K= Clearance to a mechanical
air supply inlet.
6 ft. (1.83 m)
3 ft. (91 cm) above if within
10 ft. (3 m) horizontally.
L= Clearance above paved sidewalk or
paved driveway located on public
property.
7 ft. (2.13m) †
7 ft. (2.13m)
M= Clearance under veranda, porch,
deck or balcony.
12 in. (30 cm) ‡
*
Canadian Installations
1
U.S. Installations
2
A= Clearance above grade,
veranda, porch, deck or
balcony. (See 1.24.6-i(9)b.)
12 in. (30 cm)
12 in. (30 cm)
B= Clearance to window or
door that may be opened.
6 in. (15 cm) for appliances
10,000 Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3 kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30
kW).
4 ft. (1.2 m) below or to side of
opening; 1 ft. (300 m) above opening.
C= Clearance to permanently
closed window.
*
*
D= Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal.
*
*
E= Clearance to unventilated soffit.
*
*
F= Clearance to outside corner.
*
*
G= Clearance to inside corner.
*
*
H= Clearance to each side of center
line extended above meter/regulator
assembly.
3 ft. (91 cm) within a height 15 ft.
(4.5 m) above the meter/regulator
assembly.
*