2 Components
Service manual
67
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
2.17.1
Double fan outdoor unit – single phase
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed
order.
To check the HAP LED of the main PCB
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
.
1
Turn on the unit using the respective circuit breaker.
2
Locate the HAP LED on the main PCB.
a
a
HAP LED
Does the HAP LED blink in
regular intervals (1 second
ON/1 second OFF)?
Action
Yes
of the
PCB and continue with the next
procedure.
No
Remove the main PCB, see
.
To check if the correct spare part is installed
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed
spare part number corresponds with the spare part number
indicated in the webbank.
NOTICE
Also check that the correct spare part is installed for the
capacity adapter.
Is the correct spare part for the
main PCB installed?
Action
Yes
of the
main PCB and continue with the
next procedure.
No
Replace the main PCB,
.
To check the wiring of the main PCB
1
Check that all connectors are fully plugged‑in. All colour codes
MUST correspond.
2
Check that no connectors are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
"5.2 Wiring diagram" on page 101
Is the wiring on the main PCB
correct?
Action
Yes
of the
PCB and continue with the next
procedure.
No
Adjust the wiring of the main
PCB, see
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
Repair procedures
To remove the main PCB
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
.
1
Remove the switch box.
2
Press the 2 latches and lift the wire terminal mounting plate.
Содержание Altherma EBLQ011CAV3