3 Third party components
Service manual
97
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
2
Open the drain and fill valve.
3
If an automatic air purge valve was installed, make sure it is
open.
4
Collect the drained water in a bottle, … using the installed drain
hose.
5
Close the drain and fill valve.
6
Disconnect the water supply hose from the drain and fill valve.
7
To add water to the water circuit, see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To add water to the water circuit
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
.
1
Connect the water supply hose to the drain and fill valve.
2
Open the drain and fill valve.
3
If an automatic air purge valve was installed, make sure it is
open.
4
Fill the circuit with water until the manometer (field supply)
indicates a pressure of ±2.0 bar.
5
Purge as much air as possible from the water circuit, see
"3.3.2 Repair procedures" on page 96
6
Refill the circuit until the pressure is ±2.0 bar.
7
Repeat steps 5 and 6 until no more air is purged and there are
no more pressure drops.
8
Close the drain and fill valve.
9
Disconnect the water supply hose from the drain and fill valve.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To open the stop valves of the water circuit
1
The stop valves are located outside the unit. Open the valves
by placing them in line with the piping.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To open the air purge valves of the water circuit
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
.
1
Place the air purge valve, installed inside the unit, in the open
position by turning it clockwise.
INFORMATION
If a backup heater kit is installed, place the air purge valve
of the backup heater kit in the open position.
a
a
Air purge valve
2
Place all air purge valves, installed in the installation outside the
unit, in the open position.
3
Purge the air out of the water circuit, see
.
Is the problem solved?
Action
Yes
No further actions required.
No
and continue
with the next procedure.