3 Third party components
Service manual
98
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
To install the air purge valves on the highest
points of the water circuit
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Install air purge valves on all highest points of the installation
outside the unit.
2
Purge the air out of the water circuit, see
.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
with the next procedure.
To remove the external heat source from the water
circuit
1
Remove the external heat source from the installation outside
the unit.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To install a by-pass in the water circuit
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Install a by‑pass in the water circuit outside the installation as
shown below.
b
c
a
a
By‑pass
b
Underfloor heating circuit
c
Radiators circuit
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To replace the leaking domestic hot water tap from
in water circuit
1
Replace the leaking domestic hot water tap in the water circuit
with a correct one.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To repair the leak in the water circuit
1
Repair the leak in the water circuit.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To adjust the main water supply of the installation
1
Adjust the main water supply of the installation to be within the
expected range (>1 bar).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
3.4
Manuafacturer components
3.4.1
Checking procedures
To check the correct operation / setting of the third
party component
1
See the specific dealer manual to check for the correct
installation, operation or setting of your component.
Does the component function
correctly?
Action
Yes
Return to the troubleshooting of
the specific error and continue
with the next procedure.
No
Adjust the specific component,
see
.
3.4.2
Repair procedures
To adjust the third party component
1
See the specific dealer manual to adjust your component.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
3.5
External factors
3.5.1
Checking procedures
To check the outdoor temperature
1
The outdoor unit is designed to operate within a temperature
range of –25°C and 35°C. If the outdoor temperature is outside
this range, the outdoor unit may stop operating.
Is the outdoor temperature
within the operating range?
Action
Yes
Return to the troubleshooting of
the specific error and continue
with the next procedure.
No
Wait for the outdoor temperature
to return within the operating
range.