2/8
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
User settings
└─ Preset values
└─ Room temperature
7.4.1.1
R/W
[3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2
R/W
[3-07]~[3-06], step: A.3.2.4
19°C
7.4.1.3
R/W
[3-08]~[3-09], step: A.3.2.4
24°C
7.4.1.4
R/W
[3-08]~[3-09], step: A.3.2.4
26°C
└─ LWT main
7.4.2.1
[8-09]
R/W
[9-01]~[9-00], step: 1°C
45°C
7.4.2.2
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
40°C
7.4.2.3
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
7.4.2.4
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
7.4.2.5
R/W
-10~10°C, step: 1°C
0°C
7.4.2.6
R/W
-10~10°C, step: 1°C
-2°C
7.4.2.7
R/W
-10~10°C, step: 1°C
0°C
7.4.2.8
R/W
-10~10°C, step: 1°C
2°C
└─ Tank temperature
7.4.3.1
[6-0A]
R/W
30~[6-0E]⁰C, step: 1⁰C
55⁰C
7.4.3.2
[6-0B]
R/W
30~min(50, [6-0E])⁰C, step: 1⁰C
45⁰C
7.4.3.3
[6-0C]
R/W
30~min(50, [6-0E])⁰C, step: 1⁰C
45⁰C
└─ Quiet level
7.4.4
R/W
0: Level 1
1: Level 2
2: Level 3
└─ Electricity price
7.4.5.1
[C-0C]
[D-0C]
R/W
0,00~990/kWh
0/kWh
7.4.5.2
[C-0D]
[D-0D]
R/W
0,00~990/kWh
0/kWh
7.4.5.3
[C-0E]
[D-0E]
R/W
0,00~990/kWh
0/kWh
└─ Fuel price
7.4.6
R/W
0,00~990/kWh
0,00~290/MBtu
8,0/kWh
└─ Set weather dependent
└─ Main
└────────────────── Set weather-dependent heating
7.7.1.1
[1-00]
Set weather-dependent heating
Low ambient temp. for LWT main zone heating
WD curve.
R/W
-40~5°C, step: 1°C
-10°C
7.7.1.1
[1-01]
Set weather-dependent heating
High ambient temp. for LWT main zone heating
WD curve.
R/W
10~25°C, step: 1°C
15°C
7.7.1.1
[1-02]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~[9-00]°C, step: 1°C
45°C
7.7.1.1
[1-03]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
35°C
└────────────────── Set weather-dependent cooling
7.7.1.2
[1-06]
Set weather-dependent cooling
Low ambient temp. for LWT main zone cooling
WD curve.
R/W
10~25°C, step: 1°C
20°C
7.7.1.2
[1-07]
Set weather-dependent cooling
High ambient temp. for LWT main zone cooling
WD curve.
R/W
25~43°C, step: 1°C
35°C
7.7.1.2
[1-08]
Set weather-dependent cooling
Leaving water value for low ambient temp. for
LWT main zone cooling WD curve.
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
7.7.1.2
[1-09]
Set weather-dependent cooling
Leaving water value for high ambient temp. for
LWT main zone cooling WD curve.
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
└─ Additional
└────────────────── Set weather-dependent heating
7.7.2.1
[0-00]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
R/W
[9-05]~min(45, [9-06])°C, step: 1°C
35°C
7.7.2.1
[0-01]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
R/W
[9-05]~[9-06]°C, step: 1°C
45°C
7.7.2.1
[0-02]
Set weather-dependent heating
High ambient temp. for LWT add zone heating
WD curve.
R/W
10~25°C, step: 1°C
15°C
7.7.2.1
[0-03]
Set weather-dependent heating
Low ambient temp. for LWT add zone heating
WD curve.
R/W
-40~5°C , step: 1°C
-10°C
└────────────────── Set weather-dependent cooling
7.7.2.2
[0-04]
Set weather-dependent cooling
Leaving water value for high ambient temp. for
LWT add zone cooling WD curve.
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
7.7.2.2
[0-05]
Set weather-dependent cooling
Leaving water value for low ambient temp. for
LWT add zone cooling WD curve.
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
7.7.2.2
[0-06]
Set weather-dependent cooling
High ambient temp. for LWT add zone cooling
WD curve.
R/W
25~43°C, step: 1°C
35°C
7.7.2.2
[0-07]
Set weather-dependent cooling
Low ambient temp. for LWT add zone cooling
WD curve.
R/W
10~25°C , step: 1°C
20°C
Installer settings
└─ System layout
└─ Standard
A.2.1.1
[E-00]
R/O
0~5
2: Monobloc
A.2.1.2
[E-01]
R/O
0~1
1: 16
A.2.1.3
[E-02]
R/O
0: Type 1 (*1) (*3)
1: Type 2 (*2) (*4)
A.2.1.7
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
Unit type
Compressor type
Indoor software type
Unit control method
Comfort (cooling)
Eco (cooling)
High
Medium
Low
Reheat
Storage comfort
Storage eco
Comfort (heating)
Eco (heating)
Comfort (cooling)
Eco (cooling)
Comfort (heating)
Eco (heating)
Field settings table
Installer setting at variance with
default value
Comfort (heating)
Eco (heating)
Comfort (cooling)
Eco (cooling)
4P522033-1A - 2018.06
(*1) *B*CAV3/CAW1_
(*2) *D*CAV3/CAW1_
(*3) *B*CA3*_(*4) *D*CA3*
Содержание Altherma EBLQ011CAV3
Страница 140: ...ESIE18 04 2019 02 Copyright 2019 Daikin...