2 Components
Service manual
86
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
Does the measured resistance
of the thermistor match with
the temperature determined
resistance?
Then
Yes
Thermistor is OK. Return to the
troubleshooting of the specific
error and continue with the next
procedure.
No
Replace the specific thermistor,
see
Repair procedures
To remove the thermistor
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Locate the thermistor that needs to be removed.
2
Cut the tie straps that fix the insulation and the thermistor wire.
c
b
a
a
f
d
e
a
Tie strap
b
Insulation
c
Thermistor wire
d
Clip
e
Thermistor
f
Thermistor holder
3
Cut and remove the insulation.
4
Pull the clip that fixes the thermistor.
5
Remove the thermistor from the thermistor holder.
6
Disconnect the thermistor connector from the appropriate PCB
and remove the thermistor.
7
To install the thermistor, see
"Repair procedures" on page 86
To install the thermistor
1
Pull the clip and install the thermistor in the specific thermistor
holder. Make sure the clip is in the correct position (blocking the
thermistor).
c
a
b
e
d
f
f
a
Clip
b
Thermistor
c
Thermistor holder
d
Insulation
e
Thermistor wire
f
Tie strap
2
Install the insulation around the thermistor.
3
Fix the insulation and the thermistor wire using new tie straps.
4
Connect the thermistor connector to the appropriate PCB.
WARNING
When reconnecting a connector to the PCB, do NOT apply
force, as this may damage the connector or connector pins
of the PCB.
Содержание Altherma EBLQ011CAV3
Страница 140: ...ESIE18 04 2019 02 Copyright 2019 Daikin...