70
AGZ 025D through 190D
OMM 1166-1
will lockout the compressor and a power cycle or Modbus reset command will be required to clear the
lockout.
Code 3 – Short Cycling: The module will flash the red
Alert
LED three times indicating the
compressor is locked out due to short cycling. Once locked out the compressor, a power cycle or
Modbus reset command will be required to clear the lockout.
Code 4 – Scroll High Temperature; The module will flash the red
Alert
LED four times indicating the
over-temperature condition. A Code 4
Alert
will open the M2-M1 contacts.The
Alert
will reset after
30 minutes. Once the module has locked out the compressor, a power cycle or Modbus reset command
will be required to clear the lockout.
Code 5 – Reserved for Future Use
Code 6 – Missing Phase: The module will flash the red
Alert
LED six times indicating a missing
phase. The
Alert
will reset after 5 minutes and the module will lockout the compressor after 10
consecutive Code 6
Alerts
. Once locked out, a power cycle or Modbus reset is required.
Code 7 – Reverse Phase: The module will flash the red
Alert
LED seven times indicating a reverse
phase in two of the three compressor leads. The modules will lockout the compressor after one Code
7
Alert
. A power cycle or Modbus reset command will be required to clear the lockout.
Code 8 – Reserved For Future Use
Code 9 – Module Low Voltage; The module will flash the red
Alert
LED nine times indicating low
module voltage for more than 5 seconds. . The
Alert
will reset after 5 minutes and the M2-M1
contacts will close if the T2-T1 voltage is above the reset value.
NOTE
:If a compressor with CoreSense Communications fails in the field, the CoreSense module
should remain with the failed compressor so the manufacturer’s technicians can download the
CoreSense data to assist with determining the root cause of compressor failure.
Filter-Driers
Each refrigerant circuit is furnished with a full flow filter drier (AGZ 030D – 100D) or a replaceable
core type filter-drier (AGZ 140D – 180D). The core assembly of the replaceable core drier consists of
a filter core held tightly in the shell in a manner that allows full flow without bypass.
Pressure drop across the filter drier at full load conditions must not exceed 10 psig at full load. See
page for maximum pressure drop at other load points. Replace the filter drier if the pressure drop
exceeds maximum.
!
WARNING
Pump out refrigerant before removing end flange for replacement of core(s) to remove liquid
refrigerant and lower pressure to prevent accidental blow off of cover. EPA recovery
regulations apply to this procedure.
A condenser liquid line service valve is provided for isolating the charge in the condenser, but also
serves as the point from which the liquid line can be pumped out. With the line free of refrigerant, the
filter-drier core(s) can be easily replaced.
System Adjustment
To maintain peak performance at full load operation, the system superheat and liquid subcooling may
require adjustment. Read the following subsections closely to determine if adjustment is required.
Liquid Line Sight Glass
The color of the moisture indicator is an indication of the dryness of the system and is extremely
important when the system has been serviced. Immediately after the system has been opened for
service, the element may indicate a wet condition. It is recommended that the equipment operate for