Example 3; Clear an Alarm,
from the Main Menu scroll down to the Alarms line. Note the arrow
indicating this line is a link. Press the wheel to jump to the next menu Alarms There are two lines here;
Alarm Active and Alarm Log. Alarms are cleared from the Active Alarm link. Press the wheel to jump
to the next screen. With the first line highlighted, press the wheel to enter edit mode. Rotate wheel
until AlmClr is set to On, then press wheel to clear the alarms.
Menus
Screens with titles and contents are shown in leftmost column of Table 13. An identifier for each
screen is also found in this column. Screen contents can include:
Data
Setpoints
Links to other screens
Note that some parameters or links may not be visible due to the unit configuration.
Link visibility as well as read and write access to parameters is defined for each password level:
R = readable/visible
R/W = readable/writeable
blank = not visible/accessible
Screen Navigational Links:
For each link on a screen, the linked screen is indicated in the rightmost column.
Example; the Enter Password screen links to screen U-2
For each screen, the screen(s) from which you can navigate to it is also shown on the same row as the
screen identifier.
Example: Enter Password in screen U-2 is linked from Screen U-1
For most circuit or compressor level parameters, there is a link to a screen that shows the values for all
circuits/compressors which is indicated in the 'Links to screen' column as *.
For many of the circuit level screens, only one screen will be shown in this document. The same set of
screens exists for each circuit and compressor. These screens are identified with 'Cx' and Cmpx'
identifiers. 'U' designates a unit related screen.
Table 13, Menu Screens
NOTE:
Bold entries indicate screens with links to other screens.
Screen U-1
Main Menu
No password
Operator
Links to screen
Enter Password
R
R
U-2
Quick Menu
R
U-3
View/Set Unit
R
U-4
View/Set Circuit
R
U-5
Unit Status
R
R
Active Setpoint
R
R
Evap Leaving Water Temp
R
R
Unit Capacity
R
R
Unit Mode
R
R
Time Until Restart
R
R
U-6
Alarms
R
R
U-7
Scheduled Maintenance
R
R
U-8
Review Operation
U-9
Manual Control
U-10
Commission Unit
U-11
About Chiller
R