22
AGZ 025D through 190D
OMM 1166-1
Unit Mode Selection
The operating mode of the unit is determined by
setpoints and inputs to the chiller. The Available
Modes Set Point determines what modes of
operation can be used. This set point also
determines whether the unit is configured for
glycol use. The Control Source Set Point
determines where a command to change modes
will come from. A digital input switches between
cool mode and ice mode if they are available and
the control source is set to ‘local.’ The BAS mode
request switches between cool mode and ice mode
if they are both available and the control source is
set to ‘network.’
The Available Modes Set Point should only be
changeable when the unit switch is off. This is to
avoid changing modes of operation inadvertently
while the chiller is running.
Unit Mode is set according to the following table:
Control Source
Set Point
Mode
Input
BAS
Request
Available Modes
Set Point
Unit Mode
Cool
Cool
Cool w/Glycol
Cool
Local
Off
Cool/Ice w/Glycol
Cool
Local
On
Cool/Ice w/Glycol
Ice
Network
Cool
Cool/Ice w/Glycol
Cool
Network
Ice
Cool/Ice w/Glycol
Ice
Ice w/Glycol
Ice
Test
Test
Glycol Configuration
If the Available Modes Set Point is set to an option ‘w/Glycol’, then glycol operation should be enabled for
the unit. Glycol operation should only be disabled when the Available Modes Set Point is set to ‘Cool’.
Unit States
The unit will always be in one of three states:
Off – Unit is not enabled to run
Auto – Unit is enabled to run
Pumpdown – Unit is doing a normal shutdown
Transitions between these states are shown in the following diagram.
OFF
AUTO
PUMPDOWN
T
3
T 2
T
4
T
1
POWER
ON
Diagram explanation on following page.