Si12-619A
Troubleshooting
Service Diagnosis
257
5.27
Low-voltage Detection
or
Over-voltage Detection
Remote
Controller
Display
U2
Outdoor Unit LED
Display
A
5
1
4
2
1
3
1
4
4
Method of
Malfunction
Detection
An abnormal voltage rise or drop is detected by checking the detection circuit or DC voltage
detection circuit.
Malfunction
Decision
Conditions
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer, or
the voltage being detected by the DC voltage detection circuit is judged to be below 150 V
for 0.1 second.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 60 minutes (normal)
Supposed
Causes
Supply voltage not as specified
Over-voltage detector or DC voltage detection circuit defective
PAM control part(s) defective
Troubleshooting
Check the supply voltage.
Correct the power supply.
Check for such factors for a
long term.
∗
Try to get restarted a
couple of times.
Replace the SPM or PM1.
(Replace the outdoor unit
PCB.)
(R2854)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Supply voltage as
specified?
NO
YES
Turn on the
power again.
System restarted?
NO
Repeat a
couple of times.
YES
(Precaution before turning on the power again)
Make sure the power has been off for
at least 30 seconds.
Disturbance factors
∗
Noise
∗
Power supply distortion
Содержание 3MKS50DVM
Страница 1: ...Si12 619A Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump D Series E Series ...
Страница 13: ...Introduction Si12 619A xii ...
Страница 89: ...Printed Circuit Board Connector Wiring Diagram Si12 619A 76 Printed Circuit Board Connector Wiring Diagram ...
Страница 131: ...Control Specification Si12 619A 118 Function and Control ...
Страница 146: ...Si12 619A Instruction Operation Manual 133 Duct Connected Type Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 213: ...Instruction Si12 619A 200 Operation Manual ...
Страница 283: ...Check Si12 619A 270 Service Diagnosis ...
Страница 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Страница 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Страница 399: ...Si12 619A vi Index ...