Troubleshooting
Si12-619A
234
Service Diagnosis
5.18
High
Pressure Control in Cooling
Remote
Controller
Display
F6
Outdoor Unit LED
Display
A
5
1
4
2
1
3
4
4
4
Method of
Malfunction
Detection
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
Decision
Conditions
Activated when the temperature being sensed by the heat exchanger thermistor rises above
65°C.
The error is cleared when the temperature drops below 50°C.
Supposed
Causes
The installation space is not large enough.
Faulty outdoor unit fan
Faulty electronic expansion valve
Faulty outdoor unit heat exchanger thermistor
Faulty outdoor unit PCB
Faulty stop valve
Dirty heat exchanger
Содержание 3MKS50DVM
Страница 1: ...Si12 619A Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump D Series E Series ...
Страница 13: ...Introduction Si12 619A xii ...
Страница 89: ...Printed Circuit Board Connector Wiring Diagram Si12 619A 76 Printed Circuit Board Connector Wiring Diagram ...
Страница 131: ...Control Specification Si12 619A 118 Function and Control ...
Страница 146: ...Si12 619A Instruction Operation Manual 133 Duct Connected Type Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 213: ...Instruction Si12 619A 200 Operation Manual ...
Страница 283: ...Check Si12 619A 270 Service Diagnosis ...
Страница 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Страница 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Страница 399: ...Si12 619A vi Index ...