Problem Symptoms and Measures
Si12-619A
204
Service Diagnosis
2.
Problem Symptoms and Measures
Problem Symptom
Check Item
Details of Measure
Page
No.
to be
referred
None of the units operates. Check the power supply.
Check to make sure that the rated voltage is
supplied.
—
Check the type of the indoor units.
Check to make sure that the indoor unit type is
compatible with the outdoor unit.
—
Check the outdoor air temperature.
Heating operation cannot be used when the
outdoor air temperature is 15.5°C or higher
(only for heat pump model), and cooling
operation cannot be used when the outdoor air
temperature is below –10~10 °C (depending on
the model).
—
Diagnosis with indoor unit LED
indication
—
209
Diagnosis with outdoor unit LED
indication
—
210
Check the remote controller
addresses.
Check to make sure that address settings for
the remote controller and indoor unit are
correct.
—
Operation sometimes
stops.
Check the power supply.
A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor air temperature.
Heating operation cannot be used when the
outdoor air temperature is 15.5°C or higher
(only for heat pump model), and cooling
operation cannot be used when the outdoor air
temperature is below –10~10 °C (depending on
the model).
—
Diagnosis with indoor unit LED
indication
—
209
Diagnosis with outdoor unit LED
indication
—
210
Some indoor units do not
operate.
Check the type of the indoor units.
Check to make sure that the indoor unit type is
compatible with the outdoor unit.
—
Diagnosis with indoor unit LED
indication
—
209
Diagnosis with outdoor unit LED
indication
—
210
Equipment operates but
does not cool, or does not
heat (only for heat pump
model).
Check for wiring and piping errors in
the indoor and outdoor units
connection wires and pipes.
Conduct the wiring/piping error check described
on the product diagnosis nameplate.
—
Check for thermistor detection errors. Check to make sure that the main unit’s
thermistor has not dismounted from the pipe
holder.
—
Check for faulty operation of the
electronic expansion valve.
Set the units to cooling operation, and compare
the temperatures of the liquid side connection
pipes of the connection section among rooms to
check the opening and closing operation of the
electronic expansion valves of the individual
units.
—
Diagnosis with indoor unit LED
indication
—
209
Diagnosis with outdoor unit LED
indication
—
210
Diagnosis by service port pressure
and operating current
Check for insufficient gas.
266
Large operating noise and
vibrations
Check the output voltage of the
power transistor.
—
267
Check the power transistor.
—
—
Check the installation condition.
Check to make sure that the required spaces
for installation (specified in the Engineering
Data book, etc.) are provided.
—
Содержание 3MKS50DVM
Страница 1: ...Si12 619A Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump D Series E Series ...
Страница 13: ...Introduction Si12 619A xii ...
Страница 89: ...Printed Circuit Board Connector Wiring Diagram Si12 619A 76 Printed Circuit Board Connector Wiring Diagram ...
Страница 131: ...Control Specification Si12 619A 118 Function and Control ...
Страница 146: ...Si12 619A Instruction Operation Manual 133 Duct Connected Type Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 213: ...Instruction Si12 619A 200 Operation Manual ...
Страница 283: ...Check Si12 619A 270 Service Diagnosis ...
Страница 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Страница 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Страница 399: ...Si12 619A vi Index ...