Control Specification
Si12-619A
100
Function and Control
3.2
Frequency Control
Outline
Frequency that corresponds to each room’s capacity will be determined according to the
difference in the temperature of each room and the temperature that is set by the remote
controller.
The function is explained as follows.
1. How to determine frequency.
2. Frequency command from an indoor unit. (The difference between a room temperature and
the temperature set by the remote controller.)
3. Frequency command from an indoor unit. (The ranked capacity of the operating room).
4. Frequency initial setting.
5. PI control.
Detail
How to Determine Frequency
The compressor’s frequency will finally be determined by taking the following steps.
For Heat Pump Model
1. Determine command frequency
Command frequency will be determined in the following order of priority.
1.1 Limiting frequency by drooping function
Input current, discharge pipes, low Hz high pressure limit, peak cutting, freeze-up protection,
dew prevention, fin thermistor temperature.
1.2 Limiting defrost control time
1.3 Forced cooling / heating
1.4 Indoor frequency command
2. Determine upper limit frequency
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipes, Low Hz high pressure, peak cutting,
freeze-up protection, defrost.
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Four way valve operating compensation, draft prevention, pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
For Cooling Only Model
1. Determine command frequency
Command frequency will be determined in the following order of priority.
1.1 Limiting frequency by drooping function
Input current, discharge pipes, freeze-up protection, dew prevention, fin thermistor
temperature.
1.2 Indoor frequency command
Command frequency
Limit frequency
Skip control
Each upper limit function
Compressor protection function
Each lower limit function
Four-way valve operating compensation, etc. (*)
Initial frequency
PI control
Defrost control (*)
Each drooping function
Input current control, etc.
Upper limit frequency
FMAX
Lower limit frequency
FMIN
Target frequency
Command frequency X repeats when frequency becomes lower
Frequency changes by PI control < repeats when frequency becomes lower
*; only for heat pump model
(R1375)
Содержание 3MKS50DVM
Страница 1: ...Si12 619A Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump D Series E Series ...
Страница 13: ...Introduction Si12 619A xii ...
Страница 89: ...Printed Circuit Board Connector Wiring Diagram Si12 619A 76 Printed Circuit Board Connector Wiring Diagram ...
Страница 131: ...Control Specification Si12 619A 118 Function and Control ...
Страница 146: ...Si12 619A Instruction Operation Manual 133 Duct Connected Type Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 213: ...Instruction Si12 619A 200 Operation Manual ...
Страница 283: ...Check Si12 619A 270 Service Diagnosis ...
Страница 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Страница 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Страница 399: ...Si12 619A vi Index ...