Si12-619A
Control Specification
Function and Control
107
3.10
Defrost Control
Outline
Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its fixed value when finishing.
Detail
Conditions for Starting Defrost
Under the conditions that the system is in heating operation, 6 minutes after the compressor is
started and more than 38 minutes of accumulated time pass since the start of the operation or
ending the defrosting.
When the outdoor air temperature and the outdoor heat exchanger temperature meet the
following condition for 60 seconds, the defrost control starts.
A< –(19/256)×B+(45/64)×C
A: outdoor heat exchanger temperature
B: output frequency
C: outdoor air temperature
Conditions for Canceling Defrost
The target heat exchanger temperature as the canceling condition is selected in the range of
4°C
≤
Te
≤
12°C according to the air temperature as the following formula.
The target heat exchanger temperature = –(45/64)×(ambient tempe14
The defrost operation surely operates in 120 seconds after the start. (A
→
B)
After then the defrost operation stops at the following conditions.
1. When the heat exchanger temperature reaches the target heat exchanger temperature.
(B
→
C)
2. When 650 seconds have passed after the start even if the heat exchanger temperature does
not reaches the target heat exchanger temperature. (C)
A
B
C
(R7062)
2YC32 : 94Hz
2YC36 : 62Hz
2YC45 : 54Hz
2YC63 : 39Hz
2YC32 : 94Hz
2YC36 : 80Hz
2YC45 : 82Hz
2YC63 : 62Hz
pls
pls
pls
pls
pls
Содержание 3MKS50DVM
Страница 1: ...Si12 619A Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump D Series E Series ...
Страница 13: ...Introduction Si12 619A xii ...
Страница 89: ...Printed Circuit Board Connector Wiring Diagram Si12 619A 76 Printed Circuit Board Connector Wiring Diagram ...
Страница 131: ...Control Specification Si12 619A 118 Function and Control ...
Страница 146: ...Si12 619A Instruction Operation Manual 133 Duct Connected Type Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 213: ...Instruction Si12 619A 200 Operation Manual ...
Страница 283: ...Check Si12 619A 270 Service Diagnosis ...
Страница 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Страница 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Страница 399: ...Si12 619A vi Index ...