Planning the Installation

General System Layout

The vent system consists of the raised vent itself and a sin-

gle, Dacor approved, externally mounted blower (see page 

5 and 6 for examples).

 wARNING

Failure to install an approved blower and proper duct 

• 

work with the appliance will result in a back draft and/

or the insufficient venting of smoke and fumes.
To reduce the risk of personal injury caused by reach-

• 

ing over a hot appliance, cabinet storage space locat-

ed directly above the cooktop should be avoided.
Follow the instructions and diagrams for minimum 

• 

safe clearances and installation location in these 

instructions, the appliance installation instructions and 

the blower installation instructions. Failure to do so 

may result in a fire or safety hazard.

Install the raised vent, blower and cooktop so that they 

• 

can be removed if service is required.
Refer to the cooktop installation instructions for the 

• 

minimum cutout dimensions specific to the particular 

raised vent model being installed.
The raised vent is equipped with adjustable anchor 

• 

legs to accommodate various cabinet heights.
All contact surfaces between the raised vent and any 

• 

cabinets or walls must be solid and at right angles.

Electrical Specifications

 wARNING

The electric service for the raised vent should be installed 

only by a licensed electrician.

It is the owner’s responsibility to ensure that the electrical 

connection of this appliance is performed by a qualified 

electrician. The electrical installation, including minimum 

supply wire size and grounding, must be in accordance 

with the National Electric code ANSI/NFPA 70- 2002* (or 

latest revision) and local codes and ordinances.
*A copy of this standard may be obtained from: 
National Fire Protection Association  

1 Batterymarch Park 

Quincy, Massachusetts 02269-9101

Electrical Supply Requirements

Power must be supplied by a separate, grounded, single 

phase circuit protected by a properly sized circuit breaker 

or time delay fuse and rated at 120 Vac, 60 Hz, 15 Amps. 

The above specifications are for reference only. If the 

• 

power supply requirements shown above do not agree 

with those listed on the product data label, use the rat-

ings on the label.
The suggested location of the junction box supplying 

• 

power to the unit is to the bottom right of the unit, pro-

viding local codes permit.
Install 3 conductor wiring/conduit with minimum cur-

• 

rent carrying capacity of 8 Amps to supply power to the 

blower from the raised vent when turned on. See the 

following pages for further details.
When installing a remote or in-line blower run the wir-

• 

ing/conduit parallel to the duct work and connect it to 

the blower and raised vent on the ends. There are two 

7/8” access holes in the bottom of the raised vent for 

connecting the wiring to the blower and connecting the 

vent to the power supply junction box.

Installation Specifications

General Countertop Layout

Vertical

non-combustible

surface rear wall

Notches required for some rasied vent

installations, see cooktop 

installation instructions

Backsplash

Countertop

overhang

See the cooktop installation 

instructions for exact countertop 

and cabinet dimensions

Flush with back side

of cabinet front

Countertop Height:  

 

Min: 30 ¼” (768 mm)  

 

Max: 37 ¼” (946 mm)

All tolerances: +1/16”, -0, (1.6 mm, 0)  

unless otherwise stated

Electrical Layout

Electrical access 

holes in bottom

Connection to 

cabinet blower

Cabinet 

blower

Connection to 

junction box

Connection to 

remote/in-line 

blower

Содержание RV30

Страница 1: ...ludes installation instructions for optional cabinet blower Dacor model CABP3 Part No 85515 Rev H Use these downdraft raised vents only with approved Dacor cooktops See the installation instructions f...

Страница 2: ...ller In the interest of safety and to minimize problems read these installation instructions completely and care fully before you begin the installation process Leave these installation instructions w...

Страница 3: ...ican Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities When cutting or drilling into wall or ceiling do not c damage electrical wiring and other hi...

Страница 4: ...e connect only one of the specified blowers Warning General Safety Precautions To reduce the risk of fire electric shock serious injury or death when using your appliance follow basic safety precau ti...

Страница 5: ...16 14 mm 3 1 8 79 mm 2 51 mm B A Adjustable anchor legs 1 13 16 46 mm 1 15 16 49 mm 3 16 5 mm Top cap with vent down 7 178 mm 7 1 2 191 mm Front View 15 16 24 mm 28 711 mm to 34 864 mm Tolerances 1 16...

Страница 6: ...atest revision and local codes and ordinances A copy of this standard may be obtained from National Fire Protection Association 1 Batterymarch Park Quincy Massachusetts 02269 9101 Electrical Supply Re...

Страница 7: ...s cooktops a 90 degree elbow must be connected to the cooktop gas inlet see dia gram at right to avoid interference with the raised vent s front panel Installation Specifications Example of Gas Line R...

Страница 8: ...all Exhaust ILHSF series in line blower 3 1 4 X 10 to round transition Duct work Duct work Outside wall Cooktop Wall cap on outside wall Raised vent Raised vent configured for bottom exhaust Floor Wir...

Страница 9: ...0 CFM ILHSF8 600 CFM ILHSF10 1100 CFM REMP3 600 CFM REMP16 1000 CFM Nominal rating at zero inches static pressure see the CABP3 Cabinet Blower Data on page 15 for actual rating Nominal rating at zero...

Страница 10: ...Bottom exhaust configutation with rear or bottom duct routing DUCT DUCT C L CABP3 Cooktop 25 5 8 651 mm Duct connection center line A Raised vent center line Countertop 3 1 4 X 10 Duct connection Duc...

Страница 11: ...l area than the required duct sizes in the table to the right For best performance keep the duct run as short as possible and never exceed the maximums stated at the right The maximum straight duct le...

Страница 12: ...flange 2 keps nuts 1 4 20 PN 83049 2 flat washers 1 4 20 PN 83203 Insulation foam Installation Preparation warning If the electrical service does not meet the Electrical Specifications on page 4 do n...

Страница 13: ...m tape supplied with the raised vent 1 Place the blower on the floor in the orientation it will be mounted on the front of the raised vent Peel the back ing off the tape and attach it to the right and...

Страница 14: ...t surfaces Make sure power to the junction box that will sup 1 ply power to the raised vent is turned off at the circuit breaker or fuse box Remove the screws from the front of the raised vent 2 elect...

Страница 15: ...CABP3 electrical panel Wire nut 3 places To blower Electrical Wiring Remote or In line Blower Installations ILHSF or REMP series REMP series blower shown Floor Raised vent electrical connections see...

Страница 16: ...lower and check for obstructions interfering with the raising mechanism Replace the vent cover or cabinet blower and make sure it is properly centered over the opening on the front of the raised vent...

Страница 17: ...iring Diagram Airflow CFM Cubic feet minute Static pressure inches of water 0 1 0 2 0 3 0 4 0 5 0 100 200 300 400 500 600 CABP3 Blower Performance POWER CONTROL CIRCUIT BOARD TO PUSH BUTTON CIRCUIT BO...

Страница 18: ...16 Notes...

Страница 19: ......

Страница 20: ...Dacor 600 Anton Blvd Suite 1000 Costa Mesa CA 92626 Phone 800 793 0093 Fax 626 403 3130 www Dacor com...

Отзывы: