9

Equivalent Number of Feet - 

Duct Elbows and Transitions

45° elbow 

8 Inch

3 feet

3 ¼” X 10 

45° elbow

7 feet

45° elbow

10 Inch

2 feet

3 ¼” X 10 

90° elbow

15 feet

90° elbow 

8 Inch

7 feet

3 ¼” X 10 

90° flat elbow

20 feet

90° elbow

10 Inch

5 feet

3 ¼” X 10  

to 8” round

transition

4 feet

90° 3 ¼” X 10 

to 8” round

transition

25 feet

3 ¼” X 10  

to 10” round

transition

4 feet

Roof cap*

**

Wall cap with

damper*

**

* Not applicable for REMP series blowers.
** The equivalent lengths of roof and wall caps vary with 

model and configuration. For equivalent length, contact the 

manufacturer or a qualified HVAC specialist.

Blower 

Used

Blower Maximum Duct Straight Length

8 Inch Duct

10 Inch Duct

3 ¼” X 10” 

Duct

CABP3

50 feet 

(15.2 meters)

40 feet 

(12.2 meters)

40 feet 

(12.2 meters)

ILHSF8

60 feet 

(18.3 meters)

50 feet 

(15.2 meters)

50 feet

(15.2 meters)

ILHSF10

70 feet 

(21.3 meters)

80 feet 

(24.4 meters)

70 feet 

(21.3 meters)

REMP3

60 feet 

(18.3 meters)

50 feet 

(15.2 meters)

50 feet

(15.2 meters)

REMP16

70 feet 

(21.3 meters)

80 feet 

(24.4 meters)

70 feet 

(21.3 meters)

Installation Specifications

Calculating the Maximum Duct Run Length

Do not use duct work that is smaller in cross-sectional 

• 

area than the required duct sizes in the table to the 

right.
For best performance, keep the duct run as short as 

• 

possible and never exceed the maximums stated at the 

right.
The maximum straight duct length for the raised vent 

• 

system depends on the model of blower used with the 

vent system and the number of elbows and transitions 

used. The

 Equivalent Number of Feet

 for each elbow 

and transition (see table) must be subtracted from the 

maximum straight length to compensate for wind resis-

tance. To determine the maximum allowable length of 

the duct work, subtract all of the equivalent lengths of 

the elbows and transitions from the 

Blower Maximum 

Duct Straight Length

.

For example, for a raised vent system using 3 1/4” X 

10” rectangular duct, two (2) 3 1/4” X 10” 90° elbows, a 

3 1/4” X 10” rectangular to 10” round transition with a 

REMP16 remote blower:

From the 

• 

Blower Maximum Duct Straight Length

 

table, the maximum length without transitions and 

elbows is 60 feet.
The equivalent length of each 90

• 

°

 elbow is 15 feet.

The equivalent length of 45

• 

°

 elbow is 2 feet.

The equivalent length of the transition is 4 feet.

• 

The total equivalent length of the above components is: 

• 

15 feet + 15 feet + 4 feet + 2 feet = 36 feet.
The maximum amount of straight duct that can be used 

• 

with a REMP16 and the above components is: 60 feet - 

34 feet = 24 feet.

Содержание RV30

Страница 1: ...ludes installation instructions for optional cabinet blower Dacor model CABP3 Part No 85515 Rev H Use these downdraft raised vents only with approved Dacor cooktops See the installation instructions f...

Страница 2: ...ller In the interest of safety and to minimize problems read these installation instructions completely and care fully before you begin the installation process Leave these installation instructions w...

Страница 3: ...ican Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities When cutting or drilling into wall or ceiling do not c damage electrical wiring and other hi...

Страница 4: ...e connect only one of the specified blowers Warning General Safety Precautions To reduce the risk of fire electric shock serious injury or death when using your appliance follow basic safety precau ti...

Страница 5: ...16 14 mm 3 1 8 79 mm 2 51 mm B A Adjustable anchor legs 1 13 16 46 mm 1 15 16 49 mm 3 16 5 mm Top cap with vent down 7 178 mm 7 1 2 191 mm Front View 15 16 24 mm 28 711 mm to 34 864 mm Tolerances 1 16...

Страница 6: ...atest revision and local codes and ordinances A copy of this standard may be obtained from National Fire Protection Association 1 Batterymarch Park Quincy Massachusetts 02269 9101 Electrical Supply Re...

Страница 7: ...s cooktops a 90 degree elbow must be connected to the cooktop gas inlet see dia gram at right to avoid interference with the raised vent s front panel Installation Specifications Example of Gas Line R...

Страница 8: ...all Exhaust ILHSF series in line blower 3 1 4 X 10 to round transition Duct work Duct work Outside wall Cooktop Wall cap on outside wall Raised vent Raised vent configured for bottom exhaust Floor Wir...

Страница 9: ...0 CFM ILHSF8 600 CFM ILHSF10 1100 CFM REMP3 600 CFM REMP16 1000 CFM Nominal rating at zero inches static pressure see the CABP3 Cabinet Blower Data on page 15 for actual rating Nominal rating at zero...

Страница 10: ...Bottom exhaust configutation with rear or bottom duct routing DUCT DUCT C L CABP3 Cooktop 25 5 8 651 mm Duct connection center line A Raised vent center line Countertop 3 1 4 X 10 Duct connection Duc...

Страница 11: ...l area than the required duct sizes in the table to the right For best performance keep the duct run as short as possible and never exceed the maximums stated at the right The maximum straight duct le...

Страница 12: ...flange 2 keps nuts 1 4 20 PN 83049 2 flat washers 1 4 20 PN 83203 Insulation foam Installation Preparation warning If the electrical service does not meet the Electrical Specifications on page 4 do n...

Страница 13: ...m tape supplied with the raised vent 1 Place the blower on the floor in the orientation it will be mounted on the front of the raised vent Peel the back ing off the tape and attach it to the right and...

Страница 14: ...t surfaces Make sure power to the junction box that will sup 1 ply power to the raised vent is turned off at the circuit breaker or fuse box Remove the screws from the front of the raised vent 2 elect...

Страница 15: ...CABP3 electrical panel Wire nut 3 places To blower Electrical Wiring Remote or In line Blower Installations ILHSF or REMP series REMP series blower shown Floor Raised vent electrical connections see...

Страница 16: ...lower and check for obstructions interfering with the raising mechanism Replace the vent cover or cabinet blower and make sure it is properly centered over the opening on the front of the raised vent...

Страница 17: ...iring Diagram Airflow CFM Cubic feet minute Static pressure inches of water 0 1 0 2 0 3 0 4 0 5 0 100 200 300 400 500 600 CABP3 Blower Performance POWER CONTROL CIRCUIT BOARD TO PUSH BUTTON CIRCUIT BO...

Страница 18: ...16 Notes...

Страница 19: ......

Страница 20: ...Dacor 600 Anton Blvd Suite 1000 Costa Mesa CA 92626 Phone 800 793 0093 Fax 626 403 3130 www Dacor com...

Отзывы: