ENGLISH 

 

16 

 

It is advisable to use pipes having a minimum diameter of 1’’, to avoid the decrease of pump performance.  

 

The pump is suitable for vertical or horizontal installations. 

 

Connect a rigid or flexible pipe to the 1¼” delivery of the pump. 

 

The maximum submersibility of the pump depends on the length of the power cable: 12m (39.4 ft) in the case of a cable 15m (49.2 ft) long; 7m 

(23 ft) in the case of a cable 10m (32.8 ft) long. Check the details on the technical data plate, as shown in figure 4. 

 

In order to always guarantee a good water flow, it is advisable not to exceed the following heights between the service taps and the pump (see 

figure 7). 

 

45/90 

35/120 

35/90 

20 m (65.6 ft) 

13 m (42.6 ft) 

13 m (42.6 ft) 

 

 

To facilitate installation in the tank, it is possible to remove the power cable and/or pass it through another passage hole. To 

remove it, follow the instructions on the product's quick guide. The electrical cable has a quick connection. 

Have this operation carried out by qualified personnel. Check the earth connection before commissioning the product. 

 

The pump has: 

 

An air vent valve (see figure 8). This valve allows the pump to prime in a very short time. If the water level is lower than the valve level, 

some water may escape from the vent valve. 

 

A small spring and diaphragm expansion tank (in the case of DTRON3 pumps). This limits the number of pump restarts and 

compensates for small system losses. The tank protects the pump in case of water hammer. The tank does not require any refilling or 

maintenance.  

 

An overpressure valve, which prevents water hammer. In case of ice in the delivery pipe with a submerged pump, this valve protects 

the pump from breakage. 

Installation in a well. 

Install the pump so that the pump suction is at least 1 m (3.28ft) above the bottom of the well to prevent the intake of sand and impurities. Use 

rigid metal pipes to hang the pump and secure the pipes with brackets at the top of the well. 

 

Installation in a tank 

The minimum dimensions for the pump passage in the collecting tank are 180x185 mm (7.09x7.28 in). 

Hold the pump slightly up from the bottom so as to avoid possible noises/vibrations transmitted to the tank. 

The pump will make noise if it is placed on the bottom of the tank. 

 

To avoid obstruction of the suction passages, it is recommended to check periodically that no dirt has accumulated in the 

collection trap (leaves, sand, etc.). 

 

Installation with FLOAT KIT (accessory) 

In the case of  DTRON3 pumps, an NFC level float can be added. 

This accessory, once placed in the appropriate seat in the pump, communicates with the electronic board without the aid of electrical 

connections. 

The minimum overall dimensions of the pump with float inside a well or tank are as follows: 

-

 

The minimum recommended distance between the end of the pump float and the wall is 3cm (1.18 in) (see figure 10). 

-

 

The minimum recommended distance between the float of the suction pipe and the wall (in the case of version X) is 10cm (3.94 in) 

(see figure 10). 

 

3

 

FIRST INSTALLATION 

 

The pump and the control panel, if present, must be connected to the same power mains, avoiding their being galvanically 

separated, as for example due to the presence of open isolation transformers or switches, even single-phase ones.  

In particular condominium or industrial contexts, where single-phase users can be connected to different phases of the three-

phase distribution provided by the public operator, the control panel and the pump might not be able to communicate. 

 

Содержание DTron 3

Страница 1: ...Fig Fig Image Abb Afb Fig Obr Kuva Fig Fig ekil Rys bra Fig Fig 1 Fig 2 Fig 3 Fig 5...

Страница 2: ...Fig 6 Fig 7 Fig 8 Fig 9...

Страница 3: ...Fig 10 Fig 11 Fig 12...

Страница 4: ...danger for personal safety Notes and general information WARNINGS Read this documentation carefully before installation Installation and operation must comply with the local safety regulations in forc...

Страница 5: ...he products that it may consider necessary or useful without affecting their essential characteristics who lack experience or knowledge on condition that they are under supervision or after they have...

Страница 6: ...nly use the pump in clean water The pump must not be used to pump salt water sewage inflammable corrosive or explosive liquids e g petroleum petrol thinners greases oils The temperature of the liquid...

Страница 7: ...r with I n 30 mA and that the earth system is efficient Any extension cables comply with the regulations in force 2 1 Mechanical Installation Install the pump in a location that is not exposed to free...

Страница 8: ...ve protects the pump from breakage Installation in a well Install the pump so that the pump suction is at least 1 m 3 28ft above the bottom of the well to prevent the intake of sand and impurities Use...

Страница 9: ...ressure above the CUT IN The pump stops even when there is no water safeguarding the motor see ANTI DRYRUN function Various alarms 4 2 Pump On OFF The pump motor is powered by the electronic control b...

Страница 10: ...scribed here is also effective if starting is set to Manual mode 5 2 Auto mode In this mode the pump power supply is supplied to the motor according to the evolution of the user s requirements and the...

Страница 11: ...e the plug out of the socket If the power cable or any electrical part of the pump is damaged the repair or replacement must be carried out by the manufacturer or by their technical assistance service...

Страница 12: ...e in MONITOR mode pressure on the delivery of the DTRON3 pump 6 motor power status 4 DISABLE status of the pump XX current faults alarms 5 8 10 11 connection status of the COM BOX with the DTRON s 8 T...

Страница 13: ...ons Figure 12 2 and Reset Select Figure 12 3 simultaneously for at least 3 seconds or wait for 1 minute without touching any button on the interface When switched on the COM BOX is in Monitor mode by...

Страница 14: ...resented in the barometric scale by flashing Instead the current value of the CUT IN is highlighted with the corresponding LED lit with a steady light Too low a CUT IN value could prevent the pump tur...

Отзывы: