EZT-550 Controller Manual
30
5.4 Power Recovery
The power recovery screen allows you to select how the chamber is to respond to a power outage once the
power is restored. To adjust the recovery action, select Power Recovery from the Setup menu.
Recovery State on Power-Up
Set the recovery mode for the chamber. Select the desired mode by checking the appropriate check box and
press the set button.
Terminate
Select terminate to have the chamber default to the off state on power-up. If a profile was
active prior to the power outage, the profile will also be stopped.
Hold
Select hold to have the chamber return to operation at the same point it was prior to the power
outage. If a profile was running, the profile will still be active; however, it will remain in hold
until manually set to continue.
Continue
Select continue to have the chamber pick-up where it left off on loss of power. If a profile was
running prior to the power outage, it will resume where it left off and continue through the rest
of the profile.
Power Out Time
The power out time sets the time in seconds that power is allowed to be off for the hold and continue recovery
actions to execute. If the power remains off longer than the set period, the chamber will default to the off state
(terminate) on power-up.