In large system applications, if the recommended maximum cable length needs to be exceeded, an
LNK-XT Network Extender can be used to boost the waning signal strength. One LNK-XT extends the
network length by an additional 610 m (2000 ft). It is recommended that an LNK-XT be installed
approximately every 32 LPT-M devices, or when a drop in voltage is detected.