© 2020 All rights reserved. Data subject to change without notice.
13
Rev. B | 2020.11
LPT-M - Operation Manual
Magnetic Sensors
Use a magnetic wand to access menu options and initiate
calibration without opening the enclosure.
Audible Alarm
Standard internal buzzer, rated 90 dB @ 10 cm, enable/disable
INPUT/OUTPUT
Communication
Modbus® RTU over RS-485
Modbus® ID: 100 (default, confi gurable)
Baud rate: 19,200 (default, confi gurable)
Data bits: 8
Start bits: 1
Stop bits: 1
Parity: none
Analog signal
4-20 mA input signal from ESH-A Remote Sensor
Relay
One SPDT dry contact relay, 30 volts, 2 Amps maximum
ENVIRONMENTAL
Operating Temperature
-20°C to 40°C / -4°F to 104°F
NOTE:
Low temperature option available to -40°C / -40°F) (
Sensor
dependent, some extremely cold applications may require a small
internal silicone heater to maintain temperature stability for sensor.
Contact CETCI for details)
Operating Humidity
15 - 90% RH non-condensing