LPT-M - Operation Manual
6.10.3 Test Gas Reading Response / Send Test Reading to Controller
NOTE:
Before conducting this test, notify the appropriate people so unnecessary distress or
response is not caused.
NOTE:
This functionality is available in fi rmware version 1.29 onwards.
This test allows you to send a forced gas reading to the controller without having to expose the
sensor to actual gas, so you can make sure the LPT-M is connected to the controller properly
after installation and is still initiating an appropriate response from the controller during routine
maintenance checks. The test only applies to the channel you have chosen.
In the Sensor Confi guration Menu (passcode 3032) press either ARROW key to scroll through the
menu and select the channel for which you want to test the gas reading response.
Press ENTER and use the ARROW keys to scroll through the menu and choose TEST. Press ENTER and
use the ARROW key to increase or decrease the value and the ENTER key to move to the next digit.
NOTE:
You will only be able to enter a value that falls within the factory confi gured range of the
sensor. If you try to enter a number outside that limit, the value will return to a valid value.