A.5.
NOTES Notices
NOTES Notices give general information.
Note
It is recommended to make room for the removal of packing items in the Computer
Room and ancillary premises.
Note
In the case of a water-cooled equipment installation, you are advised to separate
water supply aisles (cold aisles) from cable aisles (hot aisles).
Note
Venetian blinds may not be used inside the Computer Room.
Notes
•
It is mandatory not to use polish and wax on floors as they may remove the anti-
static qualities of the floor covering (raised floor slabs). Once a year, specialists
must be called in to clean the raised floor, the suspended ceiling, and their
plenums.
The Computer Room must comply with the Standard NF X44-101 “Classification
of contamination by solid particles", Class 4 000 000 in force.
•
Notes
•
The air-conditioning system dries conditioned air. It is therefore mandatory for
the air-conditioning system to include a steam generation humidifier.
Radiators, fitted with thermostatic valves, are acceptable in certain ancillary
premises only.
•
Note
The Computer Room and ancillary premises must be cleaned thoroughly at frequent
intervals.
Note
Modem cable connectors differ from country to country. Customers must provide
the RJ11 adapter required to comply with national standards.
For further details, please consult your Cray Sales Representative.
Note
Power Cables are hard wired directly to the UPS without a plug, except UPS 7.5 &
10 KVA models.
Note
The Customer is responsible for supplying the complete electrical installation, from
the power delivery station through to the cable outlets at the base of the server
cabinet. The electrical installation must comply with the standards in force.
A-8