1.5.2.
Service Clearance
According to cabinet model, it is mandatory to comply with the service clearance
requirements indicated in the following figures.
mportant
• When a cabinet is equipped with a Cool Cabinet Door, more service
clearance is required as shown below.
Aisles must be at least 80 cm wide to allow passageway for stretchers.
Full access to equipment is mandatory for maintenance operations.
Customers are advised to plan ahead and to provide space for
extenstions.
•
•
•
1.5.2.1.
Standard Cabinet Service Clearance (Single and Dual)
150 cm
100 cm
Figure 4. Example of standard cabinet service clearance (single and dual)
1.5.2.2.
Water-Cooled Cabinet Service Clearance (Single and Dual)
(59 in)
cm
Rear
(59 in)
Figure 5. Example of water-cooled service clearance (single and dual)
Chapter 1.
Fitting out the Premises
1-7
150 cm
Front
in)
300 cm
(118,2 in)
100
(39.4
150 cm
150 cm
Front
(59 in)
300 cm
(118,2 in)
100 cm
(39.4 in)
150 cm
(59 in)
Rear
Front
(59 in)
100 cm
(39.4 in)
100 cm
(39.4 in)
Rear
(39.4 in)
Front
150 cm
(59 in)
100 cm
(39.4 in)
100 cm
(39.4 in)
Rear
100 cm
(39.4 in)