mportant If the equipment is installed in a room equipped with water sprinklers or
sprays, water pipes must only be loaded subsequent to a primary
detection.
mportant
It is recommended to install water detection leads, connected to alarm or
remote surveillance centers and/or to a water circuit shut-off device.
mportant It is mandatory not to install hardware or furniture on one or more
perforated / damper slabs in the Computer Room.
mportant We strongly recommend the installation of a dynamic safety device to
automatically cut off the electric power supply to equipment if ambient
temperature exceeds the critical threshold of 30°C.
mportant Lightning flashes to, or nearby, structures (or services connected to the
structures) are hazardous to people, to the structures themselves, their
contents and installations as well as to services. The application of
lightning protection measures, in compliance with the Lightning Protection
Standards NF C15-100 and IEC 62305 in force is essential.
mportant The raceways must comply with the European requirements of the
Standard EN 50.174-1-2 in force. In the case of a non raised-floor
equipped computer room, this standard contains recommendations about
the cabling way and protection.
mportant You are advised to provide for a thermometer and a flow meter at chilled
water production level in order to monitor heat and flow parameters.
mportant You are advised to clearly label the inlet and outlet water hoses.
mportant The equipment grounding conductor wire (PE) must be integrated in the
same wireway as the phase and neutral wires.